1. Prior to installation or removal:
• Depressurize and vent system
• Drain below sensor level
2. Confirm chemical compatibility before use.
3. Do not exceed maximum temperature/pressure specifications.
4. Wear safety goggles or faceshield during installation/service.
5. Do not alter product construction.
6. Dispose of properly; DO NOT INCINERATE!
USE THE ATTACHED ADHESIVE LABEL TO PRESERVE
THE SAFETY INSTRUCTIONS!
Caution / Warning / Danger
Indicates a potential hazard. Failure to follow all warnings
may lead to equipment damage, injury, or death
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during
installation and service of Signet products.
Pressurized System Warning
Sensor may be under pressure, take caution to vent
system prior to installation or removal. Failure to do so
may result in equipment damage and/or serious injury.
Hand Tighten Only
Overtightening may permanently damage product threads
and lead to failure of the retaining nut.
Do Not Use Tools
Use of tool(s) may damage product beyond repair and
potentially void product warranty.
Refer to your local Georg Fischer Sales office for the most
current warranty statement.
All warranty and non-warranty repairs being returned must
include a fully completed Service Form and goods must be
returned to your local GF Sales office or distributor.
Product returned without a Service Form may not be
warranty replaced or repaired.
Signet products with limited shelf-life (e.g. pH, ORP, chlorine
electrodes, calibration solutions; e.g. pH buffers, turbidity
standards or other solutions) are warranted out of box but not
warranted against any damage, due to process or application
failures (e.g. high temperature,
chemical poisoning, dry-out) or
mishandling (e.g. broken glass,
damaged membrane, freezing
and/or extreme temperatures).
Thank you for purchasing the Signet line of Georg Fischer
measurement products.
If you would like to register your product(s), you can now
register online in one of the following ways:
• Visit our website www.gfsignet.com.
Under Service and Support click on
Product Registration Form
• If this is a pdf manual (digital copy), click here
Warranty Information
Product Registration
Safety Information
General
Compatibility
Digital (S3L) models .......... 8900, 9900, 9950
4 to 20 mA models ............ PLC
Wetted materials
Sensor housing................. PVDF
Diaphragm ........................ Ceramic
Seal................................... FKM
Process connection
-3X, -7X............................. 1/2 in. Union male thread,
where X = U, L, or H
Rear connection ................... 3/4 in. NPT male thread
Cable type ............................ 3 cond + shield, 22 AWG
Standard cable length
-3X, -7X............................. 4.6 m (15 ft)
Sensor Accuracy................... ±1% of full scale @ 25 °C
Thermal sensitivity shift ........ ±0.03% of full scale per °C
Shipping weight .................... 0.3 kg (0.65 lb.)
Electrical
Power Requirements
Digital (S3L) models .......... 5 to 6.5 VDC ±10%, <1.5 mA
4 to 20 mA models ............ 12 to 24 VDC ±10% regulated
Short circuit & reverse polarity protected
Digital (S3L) output
Type .................................. Serial ASCII, TTL level 9600 bps
Accuracy ........................... ±1% of full scale @ 25 °C
Repeatability ..................... ±0.5% of full scale
Resolution......................... 0.01 psi (0.001 psi for -XU)
Update rate ....................... <100 ms
4 to 20 mA output
Accuracy ........................... ±32 μA
Repeatability ..................... ±0.5% of full scale
Resolution......................... <5 μA
Span.................................. Field-scaleable
(see page 6 for factory settings)
Max loop impedance......... 100 Ω@ 12 V
325 Ω@ 18 V
600 Ω@ 24 V
Update rate ....................... <100 ms
Operating range (Max. pressure for accuracy specifications):
-XU.................................... 0 to 0.7 bar (0 to 10 psig)
-XL .................................... 0 to 3.4 bar (0 to 50 psig)
-XH.................................... 0 to 17.2 bar (0 to 250 psig)
Vacuum range
-XU ...........-0.1 to 0.7 bar
(-1.5 to 10 psi)
-XL ............-0.41 to 3.4 bar
(-6 to 50 psi)
-XH ...........-0.96 to 17.2 bar
(-14.6 to 250 psi)
Proof pressure
(Max. pressure without damage)
-XU ...........1.4 bar
(20 psig)
-XL ............5.2 bar
(75 psig)
-XH ...........20.7 bar
(300 psig)
0
-40 -20 0 20 40 60 80 100 120
°F
°C -40 -4 32 68 104 140 176 212 248
(bar)
(psi)
1.7
3.4
5.2
6.9
8.6
10.3
25
50
75
100
125
150
12.1
175
13.8
200
225 15.5
275 19.0
-XH
-XL
-XU
Specifications
22450 Pressure Sensor