Gira 5367 Series User manual

System 3000
Blind timer and timer BT, Operating top unit BT
Blind timer and timer BT
Order no.: 5367 ..
Operating top unit BT
Order no.: 5368 ..
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.
This manual is an integral part of the product, and must remain with the end customer.
2 Device components
Figure1: 2-gang cover
Figure2: 1-gang cover
(1) Insert
1 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
(2) Cover frame
(3a) Blind/shutter up / light on, brighter
(3b) Blind/shutter down / light off, darker
(4a) Disabling function
(4b) Activate Bluetooth coupling,
Activating / deactivating automatic oper-
ation
(5) Function LED
(6) Status LED
LED display
Green Blind/shutter activated / light switched on
Red Disabling function active
Triple red flashing Cover was previously connected to another insert
Orange Automatic operation deactivated (only 2-gang cover)
Blue Bluetooth connection active
Blue flashing Bluetooth coupling mode active
Quick blue flashing Device update is being performed
Triple blue flashing Time is not set
Priorities for the LED display:
- Red LED before green or orange LED
- Blue LED before red LED
3 Intended use
– Manual and time-controlled operation of e.g. Venetian blinds, shutters, awnings, lighting
or fans
– Operation and programming with mobile end device (smartphone or tablet) via Bluetooth
with app
– Operation of switching, dimming or Venetian blind insert, 3-wire extension or DALI Power
control unit of System 3000
Default setting
– Switching times on a Venetian blind insert:
ƞ 07:00, Mo - Thu
Ɵ 21:00, Mo - Thu
ƞ 07:00, Fr
Ɵ 21:30, Fr
ƞ 09:00, Sat
Ɵ 21:30, Sat
ƞ 09:00, Sun
Ɵ 21:00, Sun
Astro function is deactivated
– Automatic summer/winter time changeover is active
No switching times are available when operating on a switching/dimming insert.
Behaviour after a mains voltage failure
Voltage failure less than power reserve
– All data and settings are preserved
– Missed switching times are not performed later
Voltage failure greater than power reserve
2 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
– The blue LED flashes three times repeatedly until the time is automatically updated when
connected with the app
– No switching operations are executed
– Switching times are preserved
4 Product characteristics
Functions directly on the cover
– Operation of blinds/shutters and lighting
– Evaluation of 2-wire or 3-wire extension, rotary extension, Bluetooth wall transmitter or
push-button
– Activating/deactivating the disabling function (only 2-gang cover)
– Activating / deactivating automatic operation (only 2-gang cover)
– Running time and ventilation position of the blind/shutter can be saved
– Switch-on brightness or switch on to last brightness with dimming insert can be saved
– Activating/deactivating night mode (only 2-gang cover)
Functions via app
– Operation of blinds/shutters and lighting with status feedback
– Indication of current blind/shutter position, dimming position or switching state
– Programming of up to 40 individual switching times
– Venetian blind and slat positions or switching and dimming values can be saved at any
switching time
– Possible to copy switching times from other devices
– Switching at sunrise and/or before sunset (Astro function)
– Astro time through position fixing
– Astro time shift can be set for each switching time
– Automatic summer/winter time changeover, can be switched off
– Call function enables a person to attract attention if required
– Random function allows switching times to be randomly executed in a time period of +/-
15 min.
– Disabling function
– Night mode
– Automatic date and time update when connecting with smartphone
– Code request for protection for time programs and configuration possible
– Save a ventilation position, blind/shutter running time, slat change-over time and change-
over time for direction change
– Switch to inverse operation for Venetian blind inserts possible
– Maximum brightness and minimum brightness for dimming insert can be set
– Sun protection and twilight functions are possible via optional brightness sensor
5 Commissioning
Install app on a mobile end device
Requirement for operation via app is a mobile end device with Bluetooth interface, running the
Android operating system or iOS.
■ Download and install the Gira System 3000 app from the iTunes App Store (iOS) or the
Google Play Store (Android).
Couple mobile end devices via Bluetooth
Precondition: The insert must be connected and switched off. The cover is placed on the insert
and the mobile end device is close to the cover.
3 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
■ Activate coupling mode:
2-gang cover: Press the button (4b) for longer than 4 seconds.
1-gang cover: With the load switched off, press the buttons (3a) and (3b) for longer than
4 seconds.
The blue LED flashes slowly. The coupling mode is active for one minute.
■ Start the Gira System 3000 app and search for device to be coupled.
The "Gira Timer" cover is displayed in the app.
■ Perform coupling.
The coupling mode is automatically exited after successful coupling. The blue LED lights
up to confirm an active connection.
A maximum of 8 mobile end devices can be coupled with a cover. When coupling the 9th
device, the least used device will be deleted.
To be able to perform position movements of the blind/shutter on a Venetian blind insert,
a reference movement is performed in the upper end position after the programming. This
reference movement should not be stopped.
6 Operation of Venetian blind and shutters
All settings and operations are also possible via app.
Moving the blind/shutter
■ Press button (3a) or (3b) for longer than one second.
The blind/shutter moves in the desired direction to the end position or stops when the but-
ton is pressed again.
If a ventilation position has been saved, the blind stops in the ventilation position when
moving down (see Saving the ventilation position).
When executing via a Bluetooth wall transmitter, the blind/shutter is activated as long as
pressure is applied to the button.
Adjusting the slats
■ Press the button (3a) or (3b) for less than one second.
Saving blind/shutter running time
To perform positioning movements, the blind/shutter running time has to be saved beforehand.
To save blind/shutter running time, the Venetian blind must be moved to the upper end position
and the status LED (6) switch off automatically.
■ From the top end position, press the button (3b) for longer than second.
The blind/shutter moves in the lower end position direction.
■ Press and hold down the buttons (3a) and (3b).
The blind/shutter remains stopped, but continues to move after 4 seconds.
■ As soon as the blind/shutter has reached the lower end position, release the buttons and
press button (3b) within the next 4 seconds.
The running time is saved. The blind/shutter moves back to the upper end position.
Saving the ventilation position
To save the ventilation position, the Venetian blind must be moved to the upper end position
and the status LED (6) switch off automatically.
■ From the top end position, press the button (3b) for longer than second.
The blind/shutter moves in the lower end position direction.
■ Press and hold down the buttons (3a) and (3b).
The blind/shutter remains stopped, but continues to move after 4 seconds.
4 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
■ As soon as the desired ventilation position has been reached, release the buttons and
press the button (3a) within the next 4 seconds.
The ventilation position is saved. The blind/shutter moves back to the upper end position.
If the ventilation position is saved again, the old value is overwritten.
7 Operation of lighting
All settings and operations are also possible via app.
Switching the light
■ Press button (3a) or (3b) for less than 0.4 seconds.
With a dimming insert, the light switches to the brightness that was last set or a saved
brightness.
Switch light on with minimum brightness
■ Press the button (3b) for longer than 0.4 seconds.
Adjusting the brightness
■ Press button (3a) or (3b) for longer than 0.4 seconds.
Setting the colour temperature
Only with DALI Power control unit.
■ In the switched-on state, press button (3a) or (3b) twice at the top or bottom within 0.4
seconds (double-click). The light switches off and on again.
The device is in colour temperature mode.
■ Long press button (3a) or (3b) to change the colour temperature.
After a further double click, the device switches back to normal operation and signals this
with a short switching off and on again. After one minute without operation, the device
also returns to normal operation.
Saving the switch-on brightness / colour temperature
■ Adjusting the brightness
■ Set colour temperature (only DALI Power control unit)
■ Press the buttons (3a) and (3b) for longer than 4 seconds.
Switch-on brightness / colour temperature is saved. For confirmation, the light is switched
off briefly and switched on again.
Deleting the switch-on brightness / colour temperature
■ Press button (3) briefly: Light switches on with the saved switch-on brightness and colour
temperature.
■ Without changing the brightness, press buttons (3a) and (3b) for longer than 4 seconds.
The switch-on brightness has been deleted.
Switching on takes place at the last brightness / colour temperature value set. For con-
firmation, the light is switched off briefly and switched on again.
8 Activate functions
Activating / deactivating automatic operation (only 2-gang cover)
■ Press button (4b) briefly.
The automatic mode is activated / deactivated.
When automatic operation is deactivated, the function LED (5) turns orange. Saved trav-
elling times are not executed.
5 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
Activating/deactivating the disabling function (only 2-gang cover)
The disabling function disables extension operation and operation via the app and deactivates
automatic operation. Manual operation using buttons (3a) and (3b) continues to be possible.
With Venetian blinds, extension operation in the "UP" direction (wind alarm) continuous to
be possible.
■ Press the button (4a) for longer than 4 seconds.
The disabling function is activated or deactivated.
The function LED (5) turns red if the disabling function is active.
The disabling function can also be set with the app (parameter list). With the 1-gang
cover, the status LED (6) is illuminated when the disabling function is active.
Activating/deactivating night mode (only 2-gang cover)
In night mode, the status and function LEDs are not permanently lit, but only for 5 seconds after
a button is pressed.
■ Press the buttons (4a) and (4b) for longer than 4 seconds.
Night mode is activated: The function LED turns red for 3 seconds.
Night mode is deactivated: The function LED turns green for 3 seconds.
With the 1-gang and 2-gang covers, the night mode can be set with the app (parameter
list).
Call function
The function enables a person to attract attention if required. A call can be triggered via a 2-wire
extension, Bluetooth wall transmitter or push-button.
Precondition: The call function has been activated via the app.
■ Press the button of the extension.
Light flashes (1 second on, 1 second off) until the call is acknowledged by actuating any
button on the device.
Resetting the device to the factory setting
■ Press the buttons (3a) and (3b) during the first 2 minutes after switching on the mains
voltage for longer than 20 seconds until the red status LED flashes quickly.
■ Release buttons (3a) and (3b) and press briefly once again within 10 seconds.
The red status LED flashes more slowly for approx. 5 seconds.
The device is reset to default setting (default setting). The blue LED flashes three times to
indicate that the time is not set.
On a Venetian blind insert, a reference run to the upper end position is performed.
After resetting the device to the default setting, it has to be removed from the app.
On iOS equipment, the device also has to be removed manually from the list of paired
Bluetooth devices (Settings/Bluetooth). Otherwise, re-pairing will not be possible.
9 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock
Disconnect the device. Cover up live parts.
Mounting the device
Switching, dimming or Venetian blind insert or 3-wire extension are mounted and connected
properly (see instructions of the relevant inserts).
6 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
■ Fit the cover with frame on the insert.
■ Switch on mains voltage.
If the status LED (6) flashes red three times at repeated intervals, the cover was previously con-
nected to another insert. To enable operation again, either place the cover onto the correct in-
sert or press the buttons (3a) and (3b) for longer than 4 seconds.
10 Technical data
Ambient temperature -5 ... +45 °C
Storage/transport temperature -20 ... +70 °C
Accuracy per month ± 10 s
The time is updated with every connection to the app
Power reserve approx. 4 h
Radio frequency 2.402 ... 2.480 GHz
Transmission capacity max. 2.5 mW, Class 2
Transmitting range typ. 10 m
Data according to EN 60730-1
Type of action 1.B.S.T
Degree of soiling 2
Measured surge voltage 4000 V
This device includes an integrated battery. At the end of its useful life, dispose of the
device together with the battery in accordance with the environmental regulations. Do not
throw device into household waste. Consult your local authorities about environmentally friendly
disposal. According to statutory provisions, the end consumer is obligated to return the device.
11 Parameter list
Adjustable parameters via app
Depending on the insert, the following parameters can be changed with the app.
Settings for switching/dimming and Venetian blind inserts
Parameters Setting options,
Default setting
Explanations
Shifting the sun-
rise time
+/- 0 ... 120 minutes
Default setting: 0 minutes
Astro times represent the sunrise and sunset
times in the course of a calendar year. If you
want the switching to be executed in the early
morning at the start of twilight or only at full
brightness, this can be realised with this shift.
Shifting the sun-
set time
+/- 0 ... 120 minutes
Default setting: 0 minutes
Astro times represent the sunrise and sunset
times in the course of a calendar year. If you
want the switching to be executed in the even-
ing at the start of twilight or only at full dark-
ness, this can be realised with this shift.
Set the location Determination of the cur-
rent position via the GPS
function of the mobile end
device.
To adapt the Astro times to the geographical
location, the GPS function of the mobile end
device must be activated. The Astro time is
calculated once a week for the localised place.
Time change On, Off
Default setting: On
Activates automatic summer/wintertime
changeover.
7 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
Parameters Setting options,
Default setting
Explanations
Night mode On, Off
Default setting: Off
In night mode, the status LED is not perman-
ently lit, but only for 5 seconds after a button is
pressed.
Disabling function On, Off
Default setting: Off
The disabling function disables extension op-
eration and operation via the app and deactiv-
ates automatic operation. Manual operation
using buttons (3a) and (3b) continues to be
possible.
EnOcean switch MAC address
Name
Single rocker
Left rocker
Right rocker
The Bluetooth wall transmitter must be con-
nected to the device in order to be able to op-
erate it. Enter the MAC address of the
Bluetooth wall transmitter here, select the
device button to be used for operation and as-
sign a name. Up to 8 Bluetooth wall transmit-
ters can be connected to the device.
Settings for all switch and dimming inserts
Parameters Setting options,
Default setting
Explanations
Activate call func-
tion
On, Off
Default setting: Off
The function enables a person to attract atten-
tion if required. If the function is activated, a
call can be triggered via a 2-wire extension,
Bluetooth wall transmitter or push-button. If a
call has been triggered, the lighting flashes (1
second on, 1 second off) until the call is ac-
knowledged by actuating any button on the
device. A triggered call overrides all functions
of the device. The functions continue running
in the background so that the device switches
to the respective current state after acknow-
ledgement.
Settings only for dimming inserts, DALI Power control unit
Parameters Setting options,
Default setting
Explanations
Switch-on bright-
ness
1 ...100 %
Default setting: 100%
During brief operation, the output switches on
at the set switch-on brightness. Note: If the
value is above the set maximum brightness or
below the minimum brightness, then the sys-
tem will switch to the appropriate limit value.
Maximum dim-
ming value
75 ...100 %
Default setting: 100%
Specifies the maximum settable brightness.
Minimum dim-
ming value
1 ... 67 %
Default setting: 5%
Specifies the minimum settable brightness.
Colour temperat-
ure
Minimum colour temperat-
ure
2000 ... 4500 K
Minimum colour temperature: Defines the min-
imum colour temperature that can be set.
Maximum colour temperature: Defines the
8 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
Parameters Setting options,
Default setting
Explanations
Only for DALI
Power control
unit
Maximum colour temperat-
ure
5000 ... 10000 K
Switch-on colour temperat-
ure
2000 ... 10000 K
Factory setting: Minimum
colour temperature 2000 K,
maximum colour temperat-
ure 6000 K, switch-on col-
our temperature 2700 K
maximum colour temperature that can be set.
Switch-on colour temperature: The light is
switched on with a saved colour temperature.
Settings only for switch inserts
Parameters Setting options,
Default setting
Explanations
Switch-off pre-
warning
On, Off
Default setting: Off
If the switch-off warning is active, the light is
not switched off directly. The light goes off 30,
20 and 10 seconds before permanent switch-
off.
Settings only for 2-channel switch inserts
Parameters Setting options,
Default setting
Explanations
Activating switch-
on delay for
output 2
On, Off
Default setting: On
Switches the switch-on delay for output 2 on
and off.
If the parameter is switched off, output 2
switches on simultaneously with output 1.
Switch-on delay
output 2
0 s ... 60 min
Default setting: 2 min
After switching on output 1, output 2 also
switches on after the time set here has
elapsed.
Switch-off delay
for output 2
0 s ... 60 min
Default setting: 5 min
After switching off output 1, output 2 also
switches off after the time set here has
elapsed.
Settings only for venetian blind inserts
Parameters Setting options,
Default setting
Explanations
Operating mode Roller shutter
Venetian blind
Awning
Default setting: Roller shut-
ter
Roller shutter
A rolling shutter or an awning is controlled for
which the Fabric stretching function is re-
quired.
Venetian blind
A Venetian blind is controlled.
Awning
An awning is controlled for which the Fabric
stretching function is required.
9 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
Parameters Setting options,
Default setting
Explanations
Travelling time 1 ... 360 s
Default setting: 120 s
Absolute time which the blind/shutter requires
from the top to the bottom end position. The
entry is essential if position movements are to
occur.
Slat adjusting
time
0 ... 10 s
Default setting: 0 s
Absolute time for changing-over Venetian
blind slats. Here, the fabric-stretching time can
be set for the operation of awnings.
Inverse operation On, Off
Default setting: Off
Inverts the activation of the relay outputs. Dur-
ing inverted operation, the relay outputs "Up"
and "Down" should be activated in reverse.
This is required, for example, for controlling
skylights.
Blind/shutter
height ventilation
position
0 ... 100 %
Default setting: 100%
The blind/shutter stops in this position when
shutting down. This parameter is only visible in
the shutter operating mode.
Slat position
ventilation posi-
tion
0 ... 100 %
Default setting: 100%
Ventilation position in the "Venetian blind" op-
erating mode: The blind/shutter moves to the
lower end position and the slats tilt to the
value set here.
Settings with optional brightness temperature sensor
Parameters Setting options,
Default setting
Explanations
Teach brightness
sensor
Input MAC address. After entering the MAC address, the received
brightness for the controller is used by bright-
ness-dependent switching operations.
Brightness evalu-
ation
On, Off
Default setting: Off
If brightness evaluation is switched on and the
brightness threshold value is exceeded for
more than 2 minutes, sun protection is carried
out. If the brightness falls below the set bright-
ness threshold value for longer than 15
minutes, sun protection is deactivated.
Brightness
threshold
4,000 ... 80,000lux
Default setting: 20,000 lux
Brightness threshold to carry out sun protec-
tion
Sun protection
action active
Depending on the insert
used
Switching, dimming or
moving the blind/shutter
The set value is called up when the brightness
threshold value is exceeded.
E.g. for Venetian blind inserts, the set sun pro-
tection position is approached.
Sun protection
action inactive
Depending on the insert
used
Switching, dimming or
moving the blind/shutter
The set value is called up when the brightness
threshold value is not reached.
E.g. the movement to the upper end position
(0 %) can be set for Venetian blind inserts.
Temperature
evaluation
On, Off
Default setting: Off
If temperature evaluation is activated, before
implementing the sun protection, the preset
temperature threshold is checked to see if it
was exceeded. If this is not the case, the sun
protection is implemented only when the tem-
perature exceeds.
10 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
Parameters Setting options,
Default setting
Explanations
Temperature
threshold value
5 ... 50 °C, Off
Default setting: Off
Temperature threshold for temperature-de-
pendent sun protection
Dawn On, Off
Default setting: Off
When dawn is switched on, the stored action
is carried out when it exceeds the twilight
value. Depending on the insert, light is
switched or blinds are moved to a stored posi-
tion and slats are tilted.
Dusk On, Off
Default setting: Off
When dusk is switched on, the stored action is
carried out when it falls below the twilight
value. Depending on the insert, light is
switched or blinds are moved to a stored posi-
tion and slats are tilted.
Twilight threshold
value
5 ... 4,000lux
Default setting: 10 lux
If a set twilight threshold value is exceeded for
more than 4 minutes, twilight is activated. If
the brightness rises over the preset twilight
value for longer than 4 minutes, the twilight
function is deactivated. Note: A brightness /
temperature sensor is necessary for this func-
tion.
Action at dawn Depending on the insert
used
Switching, dimming or
moving the blind/shutter
The set value is called up when the twilight
threshold value is exceeded.
E.g. the movement to the upper end position
(0 %) can be set for Venetian blind inserts.
Action at dusk Depending on the insert
used
Switching, dimming or
moving the blind/shutter
The set value is called up when the twilight
threshold value is not reached.
E.g. the movement to the lower end position
(100 %) can be set for Venetian blind inserts.
12 Conformity
Gira Giersiepen GmbH & Co. KG hereby declares that the radio system type art. no. 5367 .. and
5368 .. meets the directive 2014/53/EU. You can find the full article number on the device. The
complete text of the EU Declaration of Conformity is available under the Internet address:
www.gira.de/konformitaet
13 Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your re-
sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will
forward the devices to the Gira Service Center.
11 / 12
32598122 10868257 06.07.2022

System 3000
Blind timer and timer BT, Operating top unit BT
Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-
Systeme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 - 602-0
Fax +49(0)21 95 - 602-191
www.gira.de
12 / 12
32598122 10868257 06.07.2022
This manual suits for next models
1
Table of contents
Other Gira Timer manuals