Global Fire Equipment Junior V4 Manual

Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL
OPERATION & MAINTENANCE MANUAL
VERSION - 07/2016
JUNIOR V4
FIRE ALARM CONTROL PANEL

Some functions are only available at Authorized User level of Access. To enter this mode, a validuser Code has
to be entered using the panel's front display keypad. The factory default code is: XXXXX To enter, press ENTER
then press 5 consecutive XXXXX , then press ENTER again. If code entry was successful, the words "USER
ACCESS LEVEL" will appear on the top line of the LCD display.
NOTE: Functions indicated as available to the General User do not require an access code to
be entered.
CONTENTS
1.1 Description of the fire control panel fascia......................................................................................................... 3
1.2 Alarm.............................................................................................................................................................................. 6
1.3 Reset the system......................................................................................................................................................... 7
1.4 Sound and silence the alarms................................................................................................................................. 7
1.5 Read the Fire, Fault,Test and Disabled queues.................................................................................................. 8
1.6 Active Delays............................................................................................................................................................... 9
1.7 LampTest...................................................................................................................................................................... 10
1.8 Perform a fire drill........................................................................................................................................................ 11
1.9 CaretakerTest Mode.................................................................................................................................................. 12
1.10 Disablements.............................................................................................................................................................. 14
1.10.1 Selected detectors.................................................................................................................................... 14
1.10.2 Sounders Disable....................................................................................................................................... 15
1.10.3 Auxiliary Relays........................................................................................................................................... 15
1.10.4 Enable/Disable Zones.............................................................................................................................. 16
1.11 If the panel displays a fault....................................................................................................................................... 16
1.12 If the panel displays a pre-alarm............................................................................................................................ 16
2.1 SIM CARD replacement............................................................................................................................................ 17
2.2 Replacing the Electrical Mains fuse....................................................................................................................... 18
2.3 Battery voltage and charger checks...................................................................................................................... 18
2.4 Use of programming functions for maintenance............................................................................................. 18
2.5 Getting into Programming Mode.......................................................................................................................... 19
2.6 Logbook......................................................................................................................................................................... 20
2.7 Event data sheet.......................................................................................................................................................... 21
SECTION 1 - OPERATION
SECTION 2 - MAINTENANCE
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

SECTION 1 - OPERATION
STATUS
FIRE If the LED is RED it indicates that there is a fire situation.
FAULT If the LED is AMBER it indicates a fault situation. Additional information will be
shown on the LCD display and, if applicable, on the LEDs in the FAULTS section of the
main panel (i.e. 7, 8, 9, 10).
PRE-ALARM If the LED is AMBER it indicates that a detector is in PRE-ALARM.
TEST If the LED is AMBER it indicates that the panel is in a test mode.
DISABLED If the LED is AMBER it indicates that at least one disablement exists.
SYSTEMON If the LED is GREEN it means that the panel is in ACTIVE mode. If the LED is flashing
GREEN then the panel is in INSTALLATION mode.
ZONES
ZONES Fire Zone indicator LEDs.
1.1 DESCRIPTION OF THE FIRE CONTROL PANEL FASCIA
QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

FAULTS
ALARM FAULT If the LED is AMBER it indicates that there is a problem with a loop sounder or
conventional sounder circuit.This could be an open or short circuit.
SUPPLY FAULT If the LED is AMBER it indicates that there is a Primary Supply (Electrical mains) Fault,
a Battery Fault or that there is an Earth Fault.
SYSTEMFAULT If the LED is AMBER it indicates that there is 5 Volt fault or a processor/program
failure.
KEYPAD
KEYPAD Press these buttons to toggle between menus, enter User and programming codes
and other on-screen information.
CONTROLS
BUZZER SILENCE Pressing this button will silence the internal buzzer during a FIRE or FAULT condition.
If the LED is lit, it indicates that a new FAULT or FIRE condition has occurred.
SYSTEMRESET Pressing this button restores the panel to its normal operating condition after an
alarm. Alarms must be silenced before a SYSTEM RESET can be performed. A
SYSTEM RESET does not clear any settings or disablements; it only clears FIRE and
FAULT conditions (and then only if the source of the FIRE or FAULT has been cleared).
LAMPTEST Whilst this button is depressed all of the panel’s LEDs will be illuminated and all of
the LCD display pixels will be set to black. Use this button to confirm the LEDs and
LCD display are functional.
SOUNDERS Pressing this button will activate all sounders and panel buzzers (main panel and
Repeaters). Pressing the button again will silence the sounders. If the LED is RED it
means that the SOUND ALARMS function has been activated by either pressing
SOUNDERS ACTIVATE/SILENCE switch or during an alarm or Evacuate function is
active.
DISABLEMENTS
AUXILIARY RELAYS Pressing this switch disables or enables all the relay and I/O module outputs. If the
LED is lit it means that the relay and I/O module outputs are disabled.
DELAYS ACTIVE Delays can be configured for the sounders and I/O modules using the programming
functions. Pressing this button enables or disables these delays. If the LED is AMBER
it means that the delays are active.
SOUNDERS DISABLE Pressing this button will enable/disable all sounders in the system.The LED will be lit
when sounders are disabled.
SELECTED DETECTORS Using the programming functions individual detectors can be set for SELECTIVE
DISABLEMENT. When this button is activated those detectors will be disabled
(isolated). Note that this button will only operate if at least one detector has been set
for SELECTIVE DISABLEMENT. If the LED is AMBER it means that the selected
detectors are isolated.
ACTIVATE/SILENCE
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FIRE If there is more than one FIRE pressing this button will display the next FIRE report on
the LCD display for 20 seconds. Subsequent presses will step through all the FIRE
reports. If the LED is flashing RED it means that there are FIRE reports to be reviewed.
If the LED is steady RED then all FIRE reports have been reviewed.
FAULT If there is more than one FAULT, or if there is at least one FAULT and a FIRE, pressing
this button will display the next FAULT report on the LCD display for 20 seconds.
Subsequent presses will step through all the FAULT reports. If the LED is flashing
AMBER it means that are FAULT reports to be reviewed. If the LED is steady AMBER
then all FAULT reports have been reviewed.
TEST If there are ZONES in test mode then pressing this button will show those ZONES on
the LCD display. If more ZONES are in test mode than can be shown on the LCD
display at one time then subsequent presses of the button will step through all the
ZONES in test mode. If the LED is AMBER it means that one or more ZONES are in test
mode.
DISABLED If there are disablements then pressing this button will show the disablements on
the LCD display. If there are more disablements than can be shown on the LCD
display at one time then subsequent presses of this button will step through all the
disablements. If the LED is AMBER it means that there is at least one disablement.
NOTE: The functions of some switches will only be operational after entering the authorized user or
programming access codes.
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
To do this press the
BUZZER SILENCE button.
Pressing this button will:
- Silence the internal buzzer
- turn off BUZZER SILENCE LED
To stop Sounders, press
SOUNDER ACTIVATE/SILENCE button.
The LED will also turn off after pressing.
The STATUS - FIRE LED will remain lit RED.
The STATUS
FIRE LED
will illuminate RED.
The fire control
panel buzzer will
sound continuously.
The location of the
alarm (or alarms)
will be shown on
the fire control
panel LCD display.
1.2 ALARM (AuthorizedUser Access)
If the fire alarm control panel signals an ALARM the following events will take place:
The sounders, I/O modules and other outputs will operate in accordance with their programming.
EVACUATE IN ACCORDANCE WITH THE SITE PROCEDURE
The BUZZER SILENCE
LED will be illuminated.
The SOUNDERS ACTIVATE/SILENCE
LED will be illuminated.
If more than one
alarm has occurred
the QUEUE REVIEW
FIRE LED will flash
RED indicating that
further fire reports
can be displayed on
the LCD display by
pressing the QUEUE
REVIEW FIRE button.
The external RED Zone LEDs will be
illuminated for the Zones in FIRE.
ONLY WHEN AUTHORIZED should you silence the alarms
DO NOT PRESS SYSTEM RESET UNTIL THE ALARM CONDITION HAS BEEN DEALT WITH.
A
B
C
A
B
C
A
A
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
On the fire control panel:
Press the SOUNDERS ACTIVATE/SILENCE button
- All sounders turn on
- The SOUNDERS ACTIVATE/SILENCE LED
illuminates RED
- To stop sounders, press SOUNDERS
ACTIVATE/SILENCE button again
- The SOUNDERS ACTIVATE/SILENCE LED
extinguishes
1.4 SOUND AND SILENCE THE ALARMS - - )(EVACUATION) (Authorized User Access
This section shows you how to turn on and turn off all the sounders in an installation.
It is identical to a fire drill procedure.
This procedure should be used if:
- There has been an alarm and the alarm
condition no longer exists.
-There has been a fault and the fault condition
no longer exists.
After entering either the User or programming
Access Code, press the SYSTEM RESET button.
The system takes about 20 seconds to reset. The
company name, date and time will appear on
the LCD display when the reset is complete.
Any alarm and/or fault LEDs indicated by the
panel before pressing SYSTEM RESET will no
longer be illuminated after reset.
A SYSTEM RESET can only be performed once
all alarms have been silenced.
1.3 RESET THE SYSTEM (Authorized User Access)
A
A
A
A
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
1.5 READ THE FIRE, FAULT, TEST AND DISABLED QUEUES (Access level 1 - General User)
Fire, fault, test,and disabled messages are shown on the LCD display.
The LCD has a limited display area. If more messages exist than can be shown on the LCD display the FIRE,
FAULT, TEST or DISABLED LEDs illuminate on the QUEUE REVIEW area of the fascia. The following procedure
describes how to display the additional messages.
FIRE If the QUEUE REVIEW - FIRE LED is flashing RED...
Press the QUEUE REVIEW - FIRE button to display the first queued message. Press the button again to review the
next queued message. Do this until all messages have been reviewed. The LED stops flashing RED, but remains lit,
once all messages have been displayed.
After 20 seconds the first fire event will be re-displayed.
A
B
C
D
A
B
C
D
FAULT If the QUEUE REVIEW - FAULT LED is flashing AMBER...
Press the QUEUE REVIEW - FAULT button to display the first queued message. Press the button again to review the
next queued message. Do this until all messages have been reviewed. The LED illuminates steady AMBER when all
messages have been displayed.
After 20 seconds the first fault will be re-displayed unless a fire has occurred in which case the first fire will be re-
displayed instead.
TEST If the QUEUE REVIEW -TEST LED is illuminated AMBER...
Press the QUEUE REVIEW -TEST button to display the Zones in test mode. Sometimes not all the Zones in test mode
can be displayed at once, in this case press the button again to see the next set of Zones in test mode.
After 15 seconds the display will return to its quiescent state (usually the company name and current time).
DISABLED If the QUEUE REVIEW - DISABLED LED is illuminated AMBER...
Press the QUEUE REVIEW - DISABLED button to display the disablements on the LCD. Sometimes not all the
disablements can be displayed at once, in this case press the button again to see the next set of disablements.
After 15 seconds the display will return to its quiescent state (usually the company name and current time).
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
1.6 DELAYS ACTIVE (Authorized User Access)
During installation, via the programming functions, delays can be set for the sounders and I/O modules.
These delays are only active when the DELAYS ACTIVE LED is illuminated. At all other times the sounders and I/O
modules will operate immediately when / if a fire is detected.
After entering User Access code, to enable or disable these delays press the DELAYS ACTIVES button.
Note that it is also possible, via the programming functions, to set DELAYS ACTIVE to automatically turn off at night.
For details on the programmable features and delays refer to the‘Installation & Commissioning Manual’.
During an alarm condition, if the delays are active (DELAYS ACTIVE LED is lit), pressing the DELAYS ACTIVE button
will cancel the delays and every sounder programmed to be activated during a specific fire alarm condition will
activate immediately.
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
Press and hold the LAMPTEST button.
- All LEDs shown in this diagram should be illuminated
- All pixels on the LCD display should turn black
- All external Zone LEDs should be illuminated
Release the LAMP TEST button to end the test. The LEDs and LCD display will return to their
normal condition.
1.7 LAMP TEST (General User Access)
This tests that all LEDs on the fascia are functioning, that the buzzer sounds properly and that the LCD display
is fully functional.
A
A
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
A
A
1.8 PERFORM A FIRE DRILL (Access Level 2 or Authorized User Access)
To end the fire drill press the
SOUNDERS ACTIVATE/SILENCE button.
The following will occur:
-The sounders stop sounding
-The SOUNDERS ACTIVATE/SILENCE LED
extinguishes.
To start the fire drill press the
SOUNDERS ACTIVATE/SILENCE button.
The following will occur:
-All sounders turn on
-The SOUNDERS ACTIVATE/SILENCE LED
illuminates RED
EVACUATE IN ACCORDANCE WITH THE SITE PROCEDURE
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
A
B
D
C
Test mode can be activated at anytime except when:
There is a FIRE
SOUND ALARMS have been activated
Something is already in TEST MODE (Test Sounders or Test Zones)
You are in Programming Mode
You are Installation Mode
When Caretaker Test Mode is entered 'INITIALIZING' may be displayed for up to 20 seconds depending on the
system size.
Caretaker Test Mode is exited by pressing SYSTEM RESET.
Indication of Caretaker Test Mode
The TEST LED will be lit
The buzzer will sound for 0.5 seconds every 5 seconds (same as FAULT indication).
ALARM SILENCE will not stop this.
The message “ DETECTOR TEST MODE “ will be displayed on the LCD
The Zones in test mode will be displayed on the LCD - “ ALL ZONES “
1.9 CARETAKER TEST MODE - - Authorized User Access(One-Man Walk-Through Test)
D
A
B
C
Entry and Exit of Caretaker
Test Mode
Press the QUEUE REVIEW - TEST
button first,
then the CONTROLS - LAMP TEST
button momentarily.
(The FAULTS - PROC FAULT LED will
light momentarily, this is OK).
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

Logging
Individual detector tests are not logged (they would fill the log very quickly)
Entry to Caretaker Test Mode is logged
Devices Under Test
All detectors and callpoints in all Zones will be put into test mode
Detectors and callpoints not assigned to Zones will also be put into test mode
Indication When a Device is Tested
When a detector is activated (using smoke spray for example):
The LED on the detector is activated whilst the detector is above the fire alarm threshold
The Main Panel Conventional and Loop Sounders will operate for 1 second, if selected to do so.
(See Function 7.3)
The event is reported on the Main Panel and Repeater LCD displays for 15 seconds
Testing More Than One Device
Detectors and callpoints can only be tested one at a time. The LED must be extinguished on the current
device before moving on to test the next device. (Don't use too much smoke spray)
Disablements
All disablements for sounders, loop and detectors are ignored during Caretaker Test Mode. However
the LED on disabled detectors will not be lit when the detector is tested (all other aspects of the test
will be as normal).
Sensor sensitivity
This will not be changed on entry to test mode (so at night the sensitivity may be high and during the
day low - depending on the system settings)
Other
Whilst in Caretaker Test Mode the SOUND ALARMS button will remain functional
Caretaker Test Mode can be initiated from a Main Panel or Repeater
1.9 CARETAKER TEST MODE (continued...)
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
1.10 DISABLEMENTS (Authorized User Access)
1.10.1 SELECTED DETECTORS
SELECTED DETECTORS
When activated:
The SELECTED DETECTORS LED
will be illuminated
The STATUS - DISABLED LED
will be illuminated
The QUEUE REVIEW - DISABLED LED
will be illuminated
The disabled detectors can be reviewed
using the DISABLED QUEUE REVIEW button
Using the programming functions (see the ‘Installation & Commissioning Manual’) individual detectors can be
set for SELECTIVE DISABLEMENT. When the SELECTED DETECTORS button is activated those detectors will be
disabled. (This may be required, for example, in a building with smoke detectors inside a room reserved for
cigarette smokers. During the day it would be wise to disable these detectors in order to prevent the obvious
false alarms it would otherwise generate.)
The SELECTED DETECTORS button will only operate if there is at least one detector set to SELECTIVE DISABLEMENT.
Re-pressing the SELECTED DETECTORS button again will re-enable the detectors.
C
B
A
D
A
B
C
D
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
QUEUE REVIEW
FAULTS KEYPAD CONTROLS DISABLEMENTS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
DISABLED
TEST
FAULT
FIRE
1 2 3456 7 8
9 10 11 12 13 14 15 16
FIRE ALARM CONTROL PANEL
ENTERESC
DELAYS
ACTIVE
SELECTED
DETECTORS
SOUNDERS
DISABLE
AUXILIARY
RELAYS
SOUNDERS
ACTIVATE/SILENCE
SYSTEM RESET
LAMP TEST
BUZZER
SILENCE
MANUFACTURED IN THE E.U.
TO THE REQUIREMENTS OF EN54-2 & EN54-4
CERTIFIED 1328-CPR-0179
STATUS ZONES
C
B
A
DA
B
C
D
A
B
C
1.10.2 SOUNDERS DISABLE
To disable the relay and I/O module outputs
press the AUXILIARY RELAYS button.
The AUXILIARY RELAYS LED
illuminates AMBER.
The STATUS - DISABLED LED
illuminates AMBER.
The QUEUE REVIEW-DISABLED LED
illuminates AMBER.
Re-press the AUXILIARY RELAYS button to
re-enable the relays and I/O modules.
1.10.3 AUXILIARY RELAYS
The AUXILIARY RELAYS DISABLEMENT button enables and disables all relay and I/O module outputs. This
means that those outputs will remain unchanged if a fire or fault occurs. The outputs that are controlled by
this button include the normally energised FAULT relay, the FAULT I/O group, the EVAC relay as well as the I/O
modules fitted to the analogue loops and, of course, the auxiliary relays.
By pressing this button, all sounders on
the system will be disabled.
Its associated LED will light up.
The DISABLED LED will also be lit.
By pressing SOUNDERS DISABLE button
once more, the LED will turn off and all
sounders will re-enable
SELECTED DETECTORS
C
B
A
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

If any detector detects a pre-alarm condition, the
STATUS - PRE-ALARM LED will light up AMBER.
FOLLOW SITE SPECIFIC INSTRUCTIONS
1.12 IF THE PANEL DISPLAYS A PRE-ALARM
If the system detects a fault, the STATUS - FAULT LED
will light up AMBER.
CALLTHE MAINTENANCE ENGINEER
1.11 IF THE PANEL DISPLAYS A FAULT
1.10.4 ENABLE / DISABLE ZONES
In order to Enable/Disable a zone follow the procedure described below:
1 - Enter either a valid User or Programming Code.
2 - Select Function 3.1 (Zones Disable/Assign), using the pqarrow keys. Press ENTER when menu
3 is reached.
3 - Using the pqarrow keys once more, select function 3.1 and press ENTER.
4 - Select the zone to be disabled using the pqarrow keys and press ENTER.
5 - The present status of the zone is shown. To change it, press ENTER and change the status using
the pqarrow keys from enabled to disabled and vice versa. When selection is complete press
OK/Enter. To exit press the ESC key. Each consecutive press of the ESC key will revert back one step.
If any zones are disabled during this time, the DISABLED LED in the STATUS area of the panel's fascia
will be lit. The DISABLED LED in the QUEUE REVIEW area will also be lit. If the latter LED flashes, this
gives the indication that more than one disblement has taken place in the system. To scroll through
these multiple disablements, press the DISABLED button in the QUEUE REVIEW area.
B
ASTATUS
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
A
B
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

SIM CARD CONNECTOR
2.1 SIM CARD REPLACEMENT
This procedure is required when a software upgrade is supplied on a SIM CARD. The original SIM CARD also holds all the
system configuration (settings) so this data must first be uploaded to a PC in order that it can be downloaded into the
new SIM CARD once it has been fitted.
In some cases the replacement SIM CARD will have been pre-programmed with the site configuration. In this case it is not
necessary to upload the configuration from the original SIM CARD.
The procedure assumes that the power has been removed from the panel.
- The SIM CARD is mounted on the back
of the main board.
- Release the retaining clips by pulling in
the
direction of the arrows ( ).
- With the retaining clips held in the
released position, push the SIM CARD
forward and down until it is almost
horizontal with the main panel board.
- Lift the SIM CARD off the connector.
- To install the replacement SIM CARD,
locate it on the connector almost
horizontally with the main panel board,
push it up and back gently until the
retaining clips snap into position.
- Download the panel configuration from
the PC if SIM is not pre-programmed.
Uploading and downloading requires an
RS232 lead and PC software.
See installation Manual Section 8-4-2 for
Upload/Download instructions.
ELECTRO-STATIC SENSITIVE DEVICES (ESD)
TAKE SUITABLE ESD PRECAUTIONS WHEN
REMOVING OR INSTALLING PRINTED
CIRCUIT BOARDS.
JUNIOR MAIN BOARD
SECTION 2 - MAINTENANCE
JUNIOR SIM CARD
WARNING
ENSURE THAT THE POWER IS TURNED OFF
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

2.3 BATTERYVOLTAGE AND CHARGER CHECKS
On the panel battery connector, measure the battery voltage. This should be 27.5V +/- 0.2V. Switch off the
primary supply and check that the battery voltage does not drop significantly. Carry out a test on a detector
or manual callpoint with the primary supply disconnected to ensure that the batteries are healthy.
NOTE: B
MANUFACTURER'S RECOMMENDATION. ALWAYS USE SEALED LEAD ACID BATTERIES.
ATTERIES MUST BE REPLACED PERIODICALLY IN ACCORDANCE WITH THE
2.4 USE OF PROGRAMMING FUNCTIONS FOR MAINTENANCE
The following programming functions can be used to check that the panel is operating correctly.
Note that to use these functions the installer needs to have granted‘User Access’to the following functions. By
default, access is denied.
1 Review Historic Log
All the functions associated with reviewing events and settings.
1-1 Display Historic Log
The panel logs all events in an internal event log. It can store a rolling 2000 entries. When it is full the latest
entry is added and the oldest entry discarded.
Help is automatically displayed on entry to the function because it is not possible to display a log entry and
help at the same time.
Use pqto scroll through events in the log.
NEUTRAL
LIVE
MEANWELL
DANGER
220 VOLTS
MODEL: PS-45-27
EARTH
2.2 REPLACING THE ELECTRICAL MAINS FUSE
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

1-3 Clear Historic Log
7 Monitor Device Counts &Test
Clears the Historic Log.
1-5 Read/Clear Autostart Count
Every time the Panel's power is cycled, the Autostart count is incremented. SYSTEM RESETs from the front
panel button do not increment the Autostart count.
7-1 Device Count,Type &Value
Use this function to check that all loop devices are present.
Use pqto select the device address on that loop.
This function is also useful to confirm the address of the various different types of devices connected to the
Analogue Loop.
Note that in Installation Mode all information is live i.e. the count of devices will change as the panel learns
and device types will be updated if they change. In Active Mode only the device value is live.
7-2Test Sounders
Use this function to test the audibility of the sounders in a more comfortable manner than pressing SOUND
ALARMS.
The Panel Conventional Sounders will sound for 1 second then be silenced for 9 seconds.
7-3 Sounders onTest Activation
This function allows you to choose an audible confirmation that a device has detected a fire when in test
mode. The audible confirmation consists of a 1 second period of sounder operation.The settings selected by
this function are used by‘7-4Test Zones’and‘6-4-1 Activate ASET Mode (SAM)’.
ALL SOUNDERS ON DETECTORTEST activates the Panel Conventional and Loop Sounders.
NOTE: using this function AFTER ‘7-4 Test Zones’ and ‘6-4-1 Activate ASET Mode (SAM)’ will NOT
change the settings for the zones already in test mode and the loops already in ASET mode.
7-4Test Zones
Select the Zones you wish to put into test mode.
Exit programming mode, but DO NOT press SYSTEM RESET as this clears all test modes.
In test mode when a detector is activated the LED on the detector will be illuminated and the event will be
reported on the Panel (and Repeaters) for 15 seconds. If selected then the sounders will also operate for 1
second. The LED on the detector is not latched and will clear when the alarm level falls below the alarm
threshold for the device.
Pressing TEST QUEUE REVIEW will report the zones that are in Test Mode.
7-6 Light LED on device
This function can be used to confirm the physical location of a specific detector.
Select the device and SWITCHED ON and press ENTER. The device will typically take a few seconds to
respond.
NOTE: Reset must be pressed to switch off LEDs.
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL

KEYPAD
ENTERESC
2.5 GETTING INTO PROGRAMMING MODE
When the Panel is powered up it will be necessary to enter the panel programming mode. Familiarize yourself
with this section before proceeding to the next section in the manual and powering up the panel.
Programming mode is accessed via the front panel keypad as pictured below.
To program device and zone text messages, it is essential to use the Loader PC based software.
Logging In
To enter programming mode you need to log in.
The Panel must be powered up and must have initialized itself i.e. NOT be showing the ‘INITIALIZING’
message.
Press ENTER on the Keypad. You must now input your Installer access code. See page 6 Access Levels. You
have unlimited attempts but if code entry is not started within 10 seconds then the panel will revert back
to its default screen. While entering the code you are allowed up to 5 seconds between key presses.
Function Selection
The programming functions are arranged using a menu system.
To select a function or sub-menu use either pq and ENTER.
ESC takes you up a menu level.
The top level menus are:
1 Review Historic Log
3 Zones - Disable & Assign
4 Sounders - Disable & Assign
5 Input/Output - Disable & Assign
6 Device Set-up
7 Monitor Device Counts & Test
8 General
Most functions operate in a consistent manner using the standard keys.
The item that is being changed is usually highlighted with a flashing cursor.
Manufacturers of Fire Detection Equipment
globalfire.pt
OPERATING & MAINTENANCE MANUAL - 07/2016
JUNIOR V4 - FIRE ALARM CONTROL PANEL
This manual suits for next models
1
Table of contents
Other Global Fire Equipment Control Panel manuals

Global Fire Equipment
Global Fire Equipment JUNIOR MINI-REP User manual

Global Fire Equipment
Global Fire Equipment ORION PLUS Guide

Global Fire Equipment
Global Fire Equipment ORION PLUS User manual

Global Fire Equipment
Global Fire Equipment NODE+ User manual

Global Fire Equipment
Global Fire Equipment JUNO NET Instruction manual