Global Fire Equipment JUNO NET Instruction manual

Revision 0.12June 15, 2004
JUNO-NET
Fire Alarm Control Panel
CONNECTION
SCHEMATICS
GLOBAL
FIRE EQUIPMENT

Typical System Schematic
Revision 0.10October 11, 2003
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
ISO ISOOPT ZMU TMP BGU LSM I/O +
24 V
CON
DET
CON
DET
CON
DET
EOL
6K8
ION
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
SNDSNDSND
EOL
10K
EOL
ALL AUX RELAYS RATED AT
50V AC/DC 1 AMP RESISTIVE
12V
+
12V
++
POWER SUPPLY
LEN
110V/230V
A.C.
REPEATER
FIRE
FAULT
PRE
ALARM
CLASS CHANGE
OR
REMOTE EVAC.
MAX CURRENT
PER LAMP
=100mA
AUX 1
PSU
CON 2
CON 5
CON 1
CON 6
AUX 2
PSU BELL 1 BELL 2
24v
BATT
EARTH
PAL
NO
NO
NO
FIR
NC
NC
NC
REPEATS
AUX 2
FAULT AUX 1
FLT
C
C
C
EVAC
ZONE
MPX
OUT PF E SF24v0v 0v
0v
MAX 3A FAST ACTING
J-NET-LPCON
J-NET-CON

ON
12345678
ADDRESS
C1 NC NO C2 NC NO C3 NC NO ++
++
OUT
LOOP INPUTS
24V
24V
L2 L1 IN-1 IN-2 IN-3
3 I/O UNIT
PIC
ON
123456
PIC
LSC-ISO
+24
+24
OV
OV
+S
-S
L2L2
L1 L1
ADDRESS
PIC
I/O -
ISO
IN
IN
L1
L1
L2
L2
NO
C
NC
0V +24
ON
12345678
ADDRESS
OKO
RELAY
++
LOOP 24V
L1 L2
ON
12345678
ADDRESS
FAULT
ZONE D
FIRE
FAULT
ZONE C
FIRE
FAULT
ZONE B
FIRE
FAULT
ZONE A
FIRE
ON
Z+
Z+
Z+
Z+
Z-
Z-
Z-
Z-
QUAD
ZMU
PIC
ON
12345678
PIC
INPUT UNIT
INPUT
LOOP
L2 L1
ADDRESS
ON
12345678
ZONE MONITORING UNIT
(ZMU)
LOOP
EXT 24V
Z+ Z-
+
-
L2 L1
ADDRESS
PIC
DET
12345678
TOP
HAUT
OBEN
NO POLARITY FOR WIRES COMING FROM MODULE
OR
COMING FROM THE INSTALLATION
(SHADED AREA CONNECTS FROM MODULE ONLY)
12345678
++ __
++ __
12345678
VIPER
BGU-KAC
B
A
S
E
S
O
U
N
D
E
R
Must connect to
24V power supply
Must connect to
24V power supply
Must connect to
24V power supply
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
Revision 0.10October 11, 2003

CONNECTION SCHEMATIC
EXTERNAL SUPPLY
FOR ZONE
ON
12345678
ZONE MONITORING UNIT
(ZMU)
LOOP
EXT 24V
Z+ Z-
+
-
L2 L1
ADDRESS
PIC
DET
NOTE: IF USED WITH EXTERNAL
POWER SUPPLY, (J1 & J2)
SHOULD BE OPEN
J1&J2
L1 OUT
L1 IN
L1 OUT
L1 IN
L2
L2
4K7
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
GLOBAL
FIRE EQUIPMENT
ZMU
ELECTRICAL CHARACTERISTICS
The ZMU is an addressable module, compatible with a version of the meter bus protocol used by several panel
manufacturers, and which allows the connection of a number of conventional smoke or heat detectors and manual call-
points, to an addressable fire detection system. This means that from a detection and alarm processing point of view, that
group of detection devices is given an address and considered as an unique alarm source. Using this module is a natural
option in the protection of large areas, like underground parking lots, where the expense of using addressable detectors is
not justifiable, even though the configuration of the rest of the building requires those. This module can draw its power
from the communication loop which dispenses with the need for an additional power supply connection, or be supplied
from an external power supply unit. This is defined by removing the two jumpers installed as a default. The unit controls a
zone of conventional detectors with a 4K7 ohm passive E.O.L. Because the current drawn from the loop can be
significant, especially in Fire and S.C. Fault conditions, the number of modules that can be supplied is limited. The current
status is visualized locally by a dual color LED, where the green light means a normal current condition, a red light signals a
fire condition and no light indicates a fault. The unit monitors the external power supply, reporting a fault if the auxiliary
power is not present. The ZMU is available as an electronic module with four fixing holes, or as a boxed unit for individual
module installations. The module detects and reacts to four bands of zone current which are interpreted and signaled to
the control panel and which are as follows:
0 TO NORMAL - FAULT REPORTED NORMAL TO ALARM - NORMAL REPORTED ALARM TO SHORT CCT - FIRE REPORTED SHORT CCT - FAULT REPORTED
SUPPLY CURRENT (NORMAL)
SUPPLY CURRENT (O.C. FAULT)
SUPPLY CURRENT (S.C.FAULT)
SUPPLY CURRENT (FIRE)
EXTERNAL SUPPLY SIDE
ADDRESSABLE LOOP SIDE
LOOP CURRENT (NORMAL)
LOOP CURRENT (O.C. FAULT)
LOOP CURRENT (S.C.FAULT)
LOOP CURRENT (FIRE)
2,9
1,5
1,5
3,1
7
1,5
60
30
mA mA
MECHANICAL CHARACTERISTICS
DIMENSIONS
WIRE CAPACITY
WEIGHT 30 grams
H: 20 W: 60 D: 60 (mm)
UP TO 2,5 mm2

CONNECTION SCHEMATIC
L1 OUT
L1 IN
L1 OUT
L1 IN
L2
L2
4K7
L1 OUT
L1 IN
L1 OUT
L1 IN
L2
L2
4K7
L1 OUT
L1 IN
L1 OUT
L1 IN
L2
L2
4K7
L1 OUT
L1 IN
L1 OUT
L1 IN
L2
L2
4K7
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
GLOBAL
FIRE EQUIPMENT
QUAD-ZMU
++
LOOP 24V
L1 L2
ON
12345678
ADDRESS
FAULT
ZONE D
FIRE
FAULT
ZONE C
FIRE
FAULT
ZONE B
FIRE
FAULT
ZONE A
FIRE
ON
Z+
Z+
Z+
Z+
Z-
Z-
Z-
Z-
QUAD
ZMU
PIC
EXTERNAL SUPPLY
FOR ZONE
ELECTRICAL CHARACTERISTICS
0 TO NORMAL - FAULT REPORTED NORMAL TO ALARM - NORMAL REPORTED ALARM TO SHORT CCT - FIRE REPORTED SHORT CCT - FAULT REPORTED
SUPPLY CURRENT (NORMAL)
SUPPLY CURRENT (O.C. FAULT)
SUPPLY CURRENT (S.C.FAULT)
SUPPLY CURRENT (FIRE)
EXTERNAL SUPPLY SIDE
ADDRESSABLE LOOP SIDE
LOOP CURRENT (NORMAL)
LOOP CURRENT (O.C. FAULT)
LOOP CURRENT (S.C.FAULT)
LOOP CURRENT (FIRE)
1,5
1,5
1,5
1,5
7 / CCT
1,5
60
30
/ CCT
/ CCT
/ CCT
mA mA
MECHANICAL CHARACTERISTICS
DIMENSIONS
WIRE CAPACITY
WEIGHT 130 grams
H: 20 W: 75 D: 148 (mm)
UP TO 2,5 mm2
The QUAD-ZMU is an addressable module, compatible with a version of the meter bus protocol used by several panel
manufacturers, and which allows the connection of four zones with a number of conventional smoke or heat detectors and
manual call-points, to an addressable fire detection system, using four consecutive addresses. This means that from a
detection and alarm processing point of view, each group of detection devices is given an address and considered as an
unique alarm source. Using this module is a natural option in the protection of large areas, like underground parking lots,
where the expense of using addressable detectors is not justifiable, even though the configuration of the rest of the building
requires those. This module requires the connection of 24V DC supply which is permanently monitored and allows the
connection of four standard zones of detectors with 4K7 ohm passive E.O.L. The detection zones and their supply voltage
are optically isolated from the addressable detection loop, which allows the use of a local independent power supply. If
that supply fails, a FAULT condition is reported to the control panel. The current status of each zone is visualized locally by
two LED’s, where the yellow light means a fault condition and a red light signals a fire condition and no light indicates a
normal situation. A green LED indicates that there is power on the zone connections. The individual zones of this module
detect and react to four bands of zone current which are interpreted and signaled to the control panel and are as follows:

20K
4K7
PIC
I/O - ISO
IN
IN
L1
L1
L2
L2
NO
C
NC
0V +24
ON
12345678
ADDRESS
OKO
RELAY
MONITORED
ALARM INPUT
VOLTAGE FREE
RELAY CONTACTS
EXTERNAL SUPPLY
FOR RELAY
NOTE: IF USED WITH EXTERNAL
POWER SUPPLY, (J1 & J2 on the solder side)
SHOULD BE OPEN
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
Input/Output
GFE
J1
J2
IO-ISO REV.: C
The I/O-ISO is an addressable module, compatible with a version of the meter bus protocol used by several panel
manufacturers, which allows the connection of a normally open contact to an addressable fire detection system,
providing at the same time an output relay contact to control ancillary equipment.
This is normally used to signal alarm or fault situations in machinery or other alarm situations like flooding etc..., and
controlling ancillary equipment, by means of the Fire detection system.
The module is supplied from the detection loop and monitors the monitored switch. This is done by placing a 22K
ohms E.O.L. resistors at the connections ends and wiring a 4K7 resistor in series with the alarm switch.
The input status is visualized locally by a red LED, where the red light signals an alarm condition.
The relay operation is signaled by a yellow LED which lights when the relay is actuated.
The power for actuating the relay can be external or drawn from the detection loop. The choice is made by shorting
two pads on the solder side of the PCB for loop power, or leaving those open if an external supply is available. By
default, the unit is prepared for loop power. The external supply is optically isolated from the detection loop. The
I/O-ISO is available as an electronic module with four fixing holes, or as a boxed unit for individual module
installations. The module detects and reacts to four bands of resistance between its input terminals, which are as
follows:
ELECTRICAL CHARACTERISTICS
LOOP CURRENT (NORMAL)
LOOP CURRENT (O.C. FAULT)
LOOP CURRENT (S.C. FAULT)
LOOP CURRENT (RELAY ACTIVE)
LOOP CURRENT (FIRE)
RELAY CONTACT RATING
ADDRESSABLE LOOP SUPPLY
0,7
0,7
0,7
3,1
18,5
mA
MECHANICAL CHARACTERISTICS
WIRE CAPACITY
WEIGHT
FIXINGS
DIMENSIONS
up to 2,5mm2
30 grams
H: 15 W: 52 D: 57 (mm)
50V 1A Resistive
surface mount: 4 holes
OPEN TO 50K - FAULT REPORTED 50K TO 8K2 - NORMAL REPORTED 8K2 TO 2K2 - FIRE REPORTED 2K2 TO 0R0 - FAULT REPORTED

ON
12345678
PIC
INPUT UNIT
INPUT
LOOP
L2 L1
ADDRESS
20K
4K7
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
Input
ELECTRICAL CHARACTERISTICS
LOOP CURRENT (NORMAL)
LOOP CURRENT (O.C. FAULT)
LOOP CURRENT (S.C. FAULT)
LOOP CURRENT (FIRE)
ADDRESSABLE LOOP CURRENT
0,7
0,7
0,7
3,1
mA
MECHANICAL CHARACTERISTICS
WIRE CAPACITY
WEIGHT
FIXINGS
DIMENSIONS
up to 2,5mm2
30 grams
H: 20 W: 45 D: 53 (mm)
surface mount: 4 holes
The INPUT UNIT is an addressable module, compatible with a version of the meter bus protocol used by several
panel manufacturers, which allows the connection of a normally open contact to an addressable fire detection
system.
This is normally used to signal an alarm or fault situation in machinery or other alarm situations like flooding, etc...,
by means of Fire detection system.
The module is supplied from the detection loop and monitors the connection to the monitored switch. This is done by
placing a 22 K ohm E.O.L. at the connections end and connecting a 4K7 resistor in series with the alarm switch.
The input status is visualized locally by a red LED, where the red light signals an alarm condition.
The INPUT unit is available as an electronic module with four fixing holes, or as a boxed unit for individual module
installations. The module detects and reacts to four bands of resistance between its input terminals, which are as
follows: OPEN TO 50K - FAULT REPORTED 50K TO 8K2 - NORMAL REPORTED 8K2 TO 2K2 - FIRE REPORTED 2K2 TO 0R0 - FAULT REPORTED

20K
4K7
MONITORED
ALARM INPUT
VOLTAGE FREE
RELAY CONTACTS
EXTERNAL SUPPLY
FOR RELAYS
EXTERNAL SUPPLY
FOR RELAYS
NOTE: REQUIRES EXTERNAL
SUPPLY FOR RELAY OUTPUT
ON
12345678
ADDRESS
C1 NC NO C2 NC NO C3 NC NO ++
++
OUT
LOOP INPUTS
24V
24V
L2 L1 IN-1 IN-2 IN-3
3 I/O UNIT
PIC
SAME AS IN 1
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
Triple Input / Output
The 3 I/O-ISO is an addressable module, compatible with a version of the Meter bus protocol used by several panel
manufacturers, which allows the connection of three normally open contacts to an addressable fire detection system,
providing at the same time three output relay contacts to control ancillary equipment. This is normally used to signal
alarm or fault situations in machinery or other alarm situations like flooding etc..., and controlling ancillary
equipment, by means of the Fire detection system. The module is supplied from the detection loop and monitors the
connection to the monitored switches. This is done by placing a 22K ohms E.O.L. resistors at the connections ends
and wiring a 4K7 resistor in series with the alarm switches. The input status is visualized locally by three red LED's
which signal a fire condition at the inputs, and a yellow common fault LED. The relay operation is signaled by three
red LEDs which light when the respective relays are actuated. The power for actuating the relays is derived from an
external P.S.U. The external supply is optically isolated from the detection loop. The 3 I/O-ISO is available as an
electronic module with four fixing holes. The module detects and reacts to four bands of resistance between its input
terminals, which are as follows:
ELECTRICAL CHARACTERISTICS
LOOP CURRENT (NORMAL)
LOOP CURRENT (O.C. FAULT)
LOOP CURRENT (S.C. FAULT)
LOOP CURRENT (FIRE)
RELAY CONTACT RATING
ADDRESSABLE LOOP SUPPLY
0,7
3,1
3,1
3,1
mA
MECHANICAL CHARACTERISTICS
WIRE CAPACITY
WEIGHT
FIXINGS
DIMENSIONS
up to 2,5mm2
80 grams
H: 20 W: 72 D: 88 (mm)
50V 1A Resistive
surface mount: 4 holes
OPEN TO 50K - FAULT REPORTED 50K TO 8K2 - NORMAL REPORTED 8K2 TO 2K2 - FIRE REPORTED 2K2 TO 0R0 - FAULT REPORTED

EXTERNAL
POWER SUPPLY
EXTERNAL
POWER SUPPLY
ON
123456
PIC
LSC-ISO
+24
+24
OV
OV
+S
-S
L2L2
L1 L1
ADDRESS
OUTPUT TO
CONVENTIONAL
SOUNDERS
END OF LINE: 10K RES.
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
LSC-ISO
TECHNICAL CHARACTERISTICS EXTERNAL SUPPLY
12 - 30 Volts DC
30 grams
H: 19 W: 48 D: 58 (mm)
500 Volts DC/max.
1.9mA max..
1A max.
LOOP SOUNDER CONTROL MODULE WITH AMP MONITORED OUTPUT1
The LSC-ISO is an externally powered sounder control module, designed mechanically to be mounted inside a
standard module box The main feature of this module is its capability to drive and monitor a bell output with a
maximum output of 1A. The wiring to the sounders is monitored for short and open circuit in quiescent mode
requiring a single 10K ohm resistor to be placed at the end of the monitored line. A six way DIL switch of which only
the first five sections are used allows programming of addresses 94 to 125. The output of the module is by a two way
terminal block where the line of conventional sounders is connected. The output can either be pulsed or continuous.
The protocol used by the LSC-ISO is only compatible with GFE's range of panels. A maximum number of 32
modules can be connected to each addressable loop. The current derived to the sounder output is limited to 1A
which protects the output from overloading if the output is accidentally shorted. When the line monitored is correctly
terminated by a 10K ohm resistor an analogue value of 16 is returned upon interrogation of the device. If the
sounder line is either interrupted or short circuited at any point, a fault value of 4 is returned. When in alarm, the
analogue value reported by the device is always 17. This signals to the control panel that the sounder controller has
responded to its activation command.
WORKING VOLTAGE:
QUIESCENT CURRENT CONSUMPTION:
ALARM CURRENT CONSUMPTION:
OPERATING TEMPERATURE:
HUMIDITY: DIMENSIONS:
WEIGHT:
17-40 VOLTS DC
750uA MAX.
1.5mA MAX.
0 - 85°C
30 - 95% NON-CONDENSING
WORKING VOLTAGE:
QUIESCENT CURRENT CONSUMPTION:
ALARM CURRENT CONSUMPTION:
ISOLATION:

The LSCM1 is a loop powered sounder control module, designed mechanically to be mounted inside any
conventional sounder or beacon with up to 40mA consumption. The main features of this module are its low power
consumption in quiescent mode and its electronic and mechanical simplicity which make it a reliable and
economical piece of equipment. A six way DIL switch allows assigning of the address pertaining to each sounder, in
the range from 94 to 125. The first five switches define this address, where an "all off" setting corresponds to address
94. Switch #6 defines the operation mode of the module; If this switch is OFF, the module responds as an GFE
sounder controller, if it is in the ON position, its operation will be equivalent to an Apollo Sounder Circuit Controller.
The output of the module is by two leads that are simply connected to the terminals of the sounder or beacon which
are relevant. The output can either be pulsed or continuous. The protocol used by the LSCM1 is only compatible
with GFE's range of panels. When exposed to a XP95 interrogation format the module just continues its power
management function without disturbing the communication of other XP95 devices in the loop. The current derived
to the sounder output is limited to 40mA which protects the loop from overloading if the output is accidentally
shorted. When a sounder is connected to the module's output an analogue value of 16 is returned upon
interrogation of the device. If no connection is made to the output, a fault value of 4 is returned. When in alarm, the
analogue value reported by the device is always 17. This signals to the control panel that the sounder controller has
responded to its activation command.
TECHNICAL CHARACTERISTICS
15 grams
H: 16 W: 37 D: 31 (mm)
WORKING VOLTAGE:
QUIESCENT CURRENT CONSUMPTION:
ALARM CURRENT CONSUMPTION:
OPERATING TEMPERATURE:
HUMIDITY:
DIMENSIONS:
WEIGHT:
17-40 VOLTS DC
330uA MAX.
40mA MAX. (load dependent)
0 - 85°C
30 - 95% NON-CONDENSING
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
LSCM1
LOOP SOUNDER CONTROL MODULE
ON
123456
PIC
RED
BLACK
TO SOUNDER
OR
SOUNDER BEACON
24V
0V

12345678
TOP
HAUT
OBEN
NO POLARITY FOR WIRES COMING FROM MODULE
OR
COMING FROM THE INSTALLATION
(SHADED AREA CONNECTS FROM MODULE ONLY)
...TO THE NEXT DEVICE
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
MCPA-KAC
OPERATING TEMPERATURE:
HUMIDITY:
0,35 mA
3,1 mA
0 - 85°C
30 - 95% NON-CONDENSING
ADDRESSABLE MANUAL CALL-POINT UNIT
MCPA-KAC
ELECTRICAL CHARACTERISTICS MECHANICAL CHARACTERISTICS
LOOP CURRENT (NORMAL)
LOOP CURRENT (FIRE)
ADDRESSABLE LOOP CURRENT
WIRE CAPACITY
WEIGHT
FIXINGS
DIMENSIONS
up to 2,5mm2
150 grams
H: 52 W: 87 D: 87 (mm)
surface mount: 4 holes
Both the MCPA-KAC and the MCPA-LP are addressable manual call-points, compatible with a version of the meter
bus protocol used by several panel manufacturers, used for signaling an emergency or fire situation to an
addressable fire detection control panel. The main features of these units are their low quiescent power consumption
and low cost. An 8 way DIL switch is used for setting the address of the unit within the communication loop.
Addresses 0 to 125 can be programmed in binary code, where a switch in the “OFF” position represents a “0”. This
unit returns an analog value of 16 when the glass is intact and a value of 64 when the glass panel has been pressed.
The unit is provided with a bi-color LED which signals with a green light flash when the unit is being interrogated by the
control panel. When in ALARM, the LED is illuminated in red by command of the control panel.
MCPA-KAC for UK market (BS Compliant)
(valid with the JUNO-NET panel only)
The MCPA-KAC manual call point uses a new communication mechanism that gives a typical alarm
response time of approximately one second and yet does not use Apollo's patented interrupt bit solution. This
new communication system is fully compatible with all our addressable modules, SAM's, S90, XP95 and
Discovery detectors. Like Apollo's interrupt based system, the more call points on a loop, the longer the time
from activation to alarm.
NEW !!

ON
12345678
L2
L2 L2
L1 L1
ADDRESS
LOOP 1
OUT
LOOP 2
OUT
LOOP 3
OUT
LOOP 1
RETURN
LOOP 2
RETURN
LOOP 3
RETURN
Analogue Loop
Connection Board
CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
MCPA-LP
OPERATING TEMPERATURE:
HUMIDITY:
0,35 mA
3,1 mA
0 - 85°C
30 - 95% NON-CONDENSING
ADDRESSABLE MANUAL CALL-POINT UNIT (LOW-PROFILE)
MCPA-LP
ELECTRICAL CHARACTERISTICS MECHANICAL CHARACTERISTICS
LOOP CURRENT (NORMAL)
LOOP CURRENT (FIRE)
ADDRESSABLE LOOP CURRENT
WIRE CAPACITY
WEIGHT
FIXINGS
DIMENSIONS
up to 2,5mm2
80 grams
H: 28 W: 120 D: 80 (mm)
surface mount: 2 holes
Both the MCPA-KAC and the MCPA-LP are addressable manual call-points, compatible with a version of the meter
bus protocol used by several panel manufacturers, used for signaling an emergency or fire situation to an
addressable fire detection control panel. The main features of these units are their low quiescent power consumption
and low cost. An 8 way DIL switch is used for setting the address of the unit within the communication loop.
Addresses 0 to 125 can be programmed in binary code, where a switch in the “OFF” position represents a “0”. This
unit returns an analog value of 16 when the glass is intact and a value of 64 when the glass panel has been pressed.
The unit is provided with a bi-color LED which signals with a green light flash when the unit is being interrogated by the
control panel. When in ALARM, the LED is illuminated in red by command of the control panel.

CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
VULCAN-A
123456
SWEEPING
TONE
ALTERNATING
HIGH-FREQUENCY
TONE
ALTERNATING
LOW-FREQUENCY
TONE
CONTINUOUS
TONE
L1 L1 L2 L2
CONNECTIONS AND TONE CONFIGURATIONS FOR
ADDRESSABLE SOUNDER
VULCAN
TO
DETECTOR
BASE
= JUMPER
CHARACTERISTICS STANDARD SHADOW
SUPPLY VOLTAGE:
CURRENT CONSUMPTION QUIESCENT:
CURRENT CONSUMPTION ALARM:
ADDRESS RANGE:
TONES:
PROTECTION RATING:
17-40 V DC
0.8 mA
3.5 mA
94 - 125 (32/Loop)
4 TONES SELECTED BY JUMPERS
IP44
17-40 V DC
0.8 mA
3.5 mA
(64/Loop)
SHADOW
DIMENSIONS:
SOUND OUTPUT- CONTINUOUS
WEIGHT:
SOUND OUTPUT- SWEEP:
SOUND OUTPUT- ALTERNATING:
SOUND OUTPUT- HIGH PITCH:
75 grams
DIAM.: 112 - HEIGHT: 37 (mm)
85 dB @ 1 METRE
85 dB @ 1 METRE
85 dB @ 1 METRE
92 dB @ 1 METRE
This sounder is an ultra low power base sounder, intended to be used both as a stand-alone low profile sounder, or as
a combined detector plus sounder assembly. When configured as a SHADOW sounder, by cutting the appropriate
link, these sounders become invisible to the fire alarm control panel. This characteristic means that although the
panel can control the activation of the sounders - in up to 32 groups per loop - each of these groups can have more
than one and up to 64 sounders because the devices are not reporting back to the panel. This also means that device
addresses 94 to 125, hereto reserved for addressable sounders, can be concurrently used by other device types, i.e.
detectors and call points, meaning that at this stage the total numbers of sounders per loop is raised to 64 together
with up to 125 other devices, detectors etc... This implies that the sounders are monitored individually, but
solely as part of the detection loop.
NOT
+
123456
ON
OFF SWITCHES 1-5: REGULAR ADDRESSES FROM 094 TO 125 IN BINARY
SWITCH 6: : LOOP SOUNDER
: APOLLO SOUNDER CIRCUIT CONTROLLER
OFF GFE
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
PROGRAMMING DATA FOR VULCAN ADDRESSABLE BASE SOUNDER
123456
+
+
+
+
_
_
_
_

CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
VIPER-SE-A
123456
SWEEPING
TONE
ALTERNATING
HIGH-FREQUENCY
TONE
ALTERNATING
LOW-FREQUENCY
TONE
CONTINUOUS
TONE
L1 L1 L2 L2
CONNECTIONS AND TONE CONFIGURATIONS FOR
ADDRESSABLE SOUNDER
VIPER - SE (SPECIAL EDITION)
TO
DETECTOR
BASE
= JUMPER
123456
ON
OFF SWITCHES 1-5: REGULAR ADDRESSES FROM 094 TO 125 IN BINARY
SWITCH 6: : LOOP SOUNDER
: APOLLO SOUNDER CIRCUIT CONTROLLER
OFF GFE
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
PROGRAMMING DATA FOR VIPER-SE ADDRESSABLE BASE SOUNDER
123456
+
+
+
+
_
_
_
_
CHARACTERISTICS
125 grams
DIAMETER: 100 - HEIGHT: 85 (mm)
This addressable sounder is a surface mountable unit available in red and white colors with very low power consumption
as its main characteristic. It has a sound output of up to 92dBA with less than 5mA power consumption @ 24V. It is
possible to place up to 96 sounders or 64 sounder/beacons in a single loop, 32 of which can be given a response address,
the remaining being shadow sounders.
STANDARD SHADOW
SUPPLY VOLTAGE:
CURRENT CONSUMPTION QUIESCENT:
CURRENT CONSUMPTION ALARM:
ADDRESS RANGE:
TONES:
PROTECTION RATING:
17-40 V DC
0.8 mA
3.5 mA
94 - 125 (32/Loop)
4 TONES SELECTED BY DIL SWITCH
IP65
17-40 V DC
0.8 mA
3.5 mA
(64/Loop)
SHADOW
+
DIMENSIONS:
SOUND OUTPUT- CONTINUOUS
WEIGHT:
SOUND OUTPUT- SWEEP:
SOUND OUTPUT- ALTERNATING:
SOUND OUTPUT- HIGH PITCH:
85 dB @ 1 METRE
85 dB @ 1 METRE
85 dB @ 1 METRE
92 dB @ 1 METRE

CONNECTION SCHEMATIC
GLOBAL
FIRE EQUIPMENT
VIPER-SE-C
CONNECTIONS AND TONE CONFIGURATIONS FOR
SOUNDER
VULCAN/VIPER-SE
CONVENTIONAL
SWEEPING
TONE
ALTERNATING
HIGH-FREQUENCY
TONE
ALTERNATING
LOW-FREQUENCY
TONE
++ C- C-
NOTE: TO OBTAIN CONTINUOUS TONE
CONNECT 0V TO C- TERMINALS (SHORT BETWEEN - AND C-)
= JUMPER

26.
1 2 3 4 5 6 7 8
ON
27.
1 2 3 4 5 6 7 8
ON
28.
1 2 3 4 5 6 7 8
ON
29.
1 2 3 4 5 6 7 8
ON
30.
1 2 3 4 5 6 7 8
ON
31.
1 2 3 4 5 6 7 8
ON
32.
1 2 3 4 5 6 7 8
ON
41.
1 2 3 4 5 6 7 8
ON
42.
1 2 3 4 5 6 7 8
ON
37.
1 2 3 4 5 6 7 8
ON
38.
1 2 3 4 5 6 7 8
ON
39.
1 2 3 4 5 6 7 8
ON
40.
1 2 3 4 5 6 7 8
ON
33.
1 2 3 4 5 6 7 8
ON
34.
1 2 3 4 5 6 7 8
ON
35.
1 2 3 4 5 6 7 8
ON
36.
1 2 3 4 5 6 7 8
ON
43.
1 2 3 4 5 6 7 8
ON
44.
1 2 3 4 5 6 7 8
ON
45.
1 2 3 4 5 6 7 8
ON
46.
1 2 3 4 5 6 7 8
ON
47.
1 2 3 4 5 6 7 8
ON
48.
1 2 3 4 5 6 7 8
ON
49.
1 2 3 4 5 6 7 8
ON
50.
1 2 3 4 5 6 7 8
ON
51.
1 2 3 4 5 6 7 8
ON
52.
1 2 3 4 5 6 7 8
ON
53.
1 2 3 4 5 6 7 8
ON
54.
1 2 3 4 5 6 7 8
ON
55.
1 2 3 4 5 6 7 8
ON
56.
1 2 3 4 5 6 7 8
ON
57.
1 2 3 4 5 6 7 8
ON
58.
1 2 3 4 5 6 7 8
ON
59.
1 2 3 4 5 6 7 8
ON
60.
1 2 3 4 5 6 7 8
ON
61.
1 2 3 4 5 6 7 8
ON
62.
1 2 3 4 5 6 7 8
ON
63.
1 2 3 4 5 6 7 8
ON
64.
1 2 3 4 5 6 7 8
ON
73.
1 2 3 4 5 6 7 8
ON
74.
1 2 3 4 5 6 7 8
ON
69.
1 2 3 4 5 6 7 8
ON
70.
1 2 3 4 5 6 7 8
ON
71.
1 2 3 4 5 6 7 8
ON
72.
1 2 3 4 5 6 7 8
ON
65.
1 2 3 4 5 6 7 8
ON
66.
1 2 3 4 5 6 7 8
ON
67.
1 2 3 4 5 6 7 8
ON
68.
1 2 3 4 5 6 7 8
ON
75.
1 2 3 4 5 6 7 8
ON
105.
1 2 3 4 5 6 7 8
ON
106.
1 2 3 4 5 6 7 8
ON
101.
1 2 3 4 5 6 7 8
ON
102.
1 2 3 4 5 6 7 8
ON
103.
1 2 3 4 5 6 7 8
ON
104.
1 2 3 4 5 6 7 8
ON
107.
1 2 3 4 5 6 7 8
ON
108.
1 2 3 4 5 6 7 8
ON
109.
1 2 3 4 5 6 7 8
ON
110.
1 2 3 4 5 6 7 8
ON
111.
1 2 3 4 5 6 7 8
ON
112.
1 2 3 4 5 6 7 8
ON
113.
1 2 3 4 5 6 7 8
ON
114.
1 2 3 4 5 6 7 8
ON
115.
1 2 3 4 5 6 7 8
ON
116.
1 2 3 4 5 6 7 8
ON
117.
1 2 3 4 5 6 7 8
ON
118.
1 2 3 4 5 6 7 8
ON
119.
1 2 3 4 5 6 7 8
ON
120.
1 2 3 4 5 6 7 8
ON
121.
1 2 3 4 5 6 7 8
ON
122.
1 2 3 4 5 6 7 8
ON
123.
1 2 3 4 5 6 7 8
ON
124.
1 2 3 4 5 6 7 8
ON
125.
1 2 3 4 5 6 7 8
ON
76.
1 2 3 4 5 6 7 8
ON
77.
1 2 3 4 5 6 7 8
ON
78.
1 2 3 4 5 6 7 8
ON
79.
1 2 3 4 5 6 7 8
ON
80.
1 2 3 4 5 6 7 8
ON
81.
1 2 3 4 5 6 7 8
ON
82.
1 2 3 4 5 6 7 8
ON
83.
1 2 3 4 5 6 7 8
ON
84.
1 2 3 4 5 6 7 8
ON
85.
1 2 3 4 5 6 7 8
ON
86.
1 2 3 4 5 6 7 8
ON
87.
1 2 3 4 5 6 7 8
ON
88.
1 2 3 4 5 6 7 8
ON
89.
1 2 3 4 5 6 7 8
ON
90.
1 2 3 4 5 6 7 8
ON
91.
1 2 3 4 5 6 7 8
ON
92.
1 2 3 4 5 6 7 8
ON
93.
1 2 3 4 5 6 7 8
ON
94.
1 2 3 4 5 6 7 8
ON
95.
1 2 3 4 5 6 7 8
ON
96.
1 2 3 4 5 6 7 8
ON
97.
1 2 3 4 5 6 7 8
ON
98.
1 2 3 4 5 6 7 8
ON
99.
1 2 3 4 5 6 7 8
ON
100.
1 2 3 4 5 6 7 8
ON
9.
1 2 3 4 5 6 7 8
ON
10.
1 2 3 4 5 6 7 8
ON
5.
1 2 3 4 5 6 7 8
ON
6.
1 2 3 4 5 6 7 8
ON
7.
1 2 3 4 5 6 7 8
ON
8.
1 2 3 4 5 6 7 8
ON
1.
1 2 3 4 5 6 7 8
ON
2.
1 2 3 4 5 6 7 8
ON
3.
1 2 3 4 5 6 7 8
ON
4.
1 2 3 4 5 6 7 8
ON
11.
1 2 3 4 5 6 7 8
ON
12.
1 2 3 4 5 6 7 8
ON
13.
1 2 3 4 5 6 7 8
ON
14.
1 2 3 4 5 6 7 8
ON
15.
1 2 3 4 5 6 7 8
ON
16.
1 2 3 4 5 6 7 8
ON
17.
1 2 3 4 5 6 7 8
ON
18.
1 2 3 4 5 6 7 8
ON
19.
1 2 3 4 5 6 7 8
ON
20.
1 2 3 4 5 6 7 8
ON
21.
1 2 3 4 5 6 7 8
ON
22.
1 2 3 4 5 6 7 8
ON
23.
1 2 3 4 5 6 7 8
ON
24.
1 2 3 4 5 6 7 8
ON
25.
1 2 3 4 5 6 7 8
ON
DIP SWITCH ADDRESSING
GLOBAL
FIRE EQUIPMENT
Other manuals for JUNO NET
1
Table of contents
Other Global Fire Equipment Control Panel manuals

Global Fire Equipment
Global Fire Equipment Junior V4 Manual

Global Fire Equipment
Global Fire Equipment ORION PLUS User manual

Global Fire Equipment
Global Fire Equipment ORION PLUS Guide

Global Fire Equipment
Global Fire Equipment JUNIOR MINI-REP User manual

Global Fire Equipment
Global Fire Equipment NODE+ User manual
Popular Control Panel manuals by other brands

May Manufacturing
May Manufacturing MVS504DZ Operation guide

GESTRA
GESTRA SPECTORcontrol II Original Installation Instructions

MOBA
MOBA MCE Lasers DUO 2 v2 Operator's manual

GRASS VALLEY
GRASS VALLEY JUPITER CONTROL PANEL S100 - datasheet

DAB
DAB E-BOX 2G M Instruction for installation and maintenance

APS
APS TS400-D133 manual