Glowworm Smart Wiring Center 2 User manual

Smart Wiring Center 2
Installation
and Servicing
The energy you need


- 1 -
1 Notes on the documentation ......................................................................................................... 2
1.1 Symbols used .....................................................................................................................2
1.2 Observe other applicable documents ...................................................................................2
1.3 Storing documents..............................................................................................................2
1.4 Validity of the instructions...................................................................................................2
2 Safety.......................................................................................................................................... 2
2.1 General safety advices.........................................................................................................2
2.2 Intended use.......................................................................................................................3
2.3 Rules and regulations..........................................................................................................3
2.4 CE label ..............................................................................................................................4
3 Description of the product ............................................................................................................ 4
3.1 Product Overview ................................................................................................................4
3.2 Product structure ................................................................................................................5
3.3 Type designation and serial number ...................................................................................11
3.4 Data plate description .......................................................................................................11
4 Mounting and installation........................................................................................................... 11
4.1 Preparing the mounting and installation.............................................................................11
4.2 Mounting the product........................................................................................................11
4.3 Electrical Installation.........................................................................................................12
5 Commissioning .......................................................................................................................... 14
5.1 Filling...............................................................................................................................14
5.2 Venting ............................................................................................................................14
5.3 Switching on.....................................................................................................................14
5.4 Multizone specic adjustment ...........................................................................................14
5.5 Restart and check..............................................................................................................14
6 User information ........................................................................................................................ 14
7 Maintenance.............................................................................................................................. 14
7.1 Trouble-shooting...............................................................................................................14
7.2 Main supply cable .............................................................................................................15
8 Decommissioning ...................................................................................................................... 15
9 Recycling and disposal ............................................................................................................... 15
9.1 Recycle the packaging.......................................................................................................15
9.2 WEEE: Recycle or dispose the product and its components...................................................15
10 Guarantee and customer service ................................................................................................. 16
11 Technical data............................................................................................................................ 16
TABLE OF CONTENTS
EN

0020140826_00 - 08/12 - Glow-worm
- 2 -
INTRODUCTION
EN
1 Notes on the documentation
1.1 Symbols used
The symbols used in the text are explained below:
Symbol Explanation
iSymbol that denotes useful tips and information
∙Symbol for a required action
The warning notes are classied in accordance with the severity
of the possible danger using the following warning signs and
signal words.
Warning symbol Signal word Explanation
aDanger Immediate danger to life or risk of
severe personal injury.
eDanger Risk of death from electric shock.
aWarning Risk of minor personal injury.
bCaution Risk of material or environmental
damage.
1.2 Observe other applicable documents
∙Observe absolutely all operating and installation instructions
enclosed with the product, for the various parts and
components of the system.
1.3 Storing documents
∙Pass these instructions and all other applicable documents to
the system user.
The system user should retain these instructions so that they are
available when required.
1.4 Validity of the instructions
These instructions apply exclusively to:
Liste type
Product Article number
Smart Wiring Center 2 0020135101
2 Safety
All electrical work performed on the equipment must be carried
out by a qualied engineer or Glow-worm Group Service engineer.
This equipment must only be installed by a qualied engineer, to
ensure that the applicable regulations and rules are adhered to.
When work on the appliance is completed, perform an operational
test and check for safety in accordance with BS EN 7671.
2.1 General safety advices
∙Before to read this chapter, also read the general safety advice
of the operating instructions.
2.1.1 Danger to life by electric shock
Touching live connections can cause serious personal injury.
∙ Before carrying out any work on the product, switch o the
power supply.
∙Secure the power supply against being switched on again.
2.1.2 Danger to life by escaping gas
Incorrect installation can cause leakages and explosion.
∙Make sure there are no stresses in the gas line.
∙Correctly position the seals.
∙Observe the legal directives and the local regulations for gas
supply companies.
2.1.3 Danger to life by escaping ue gases due to
unlocked openings
Flue gases can escape through openings in the ue pipe.
Inspection chambers in the ue gas pipe can be opened.
∙Open inspection chambers only if you are a competent person.
∙Close all inspection chambers before start-up.
2.1.4 Danger to life due to missing or not properly
working safety devices
Missing safety devices can cause life-threatening scalding and
other injuries, for example by burst pipes.
The information contained in this document do not show all
schemes required for a professional installation of safety devices.
∙Install the necessary safety devices in the system.
∙Inform the user about the function and location of safety
devices.
∙Observe the relevant national and international laws,
standards and guidelines.

0020140826_00 - 08/12 - Glow-worm
- 3 -
INTRODUCTION
EN
2.1.5 Danger of scalding due to the hot water!
∙ There is a danger of scalding at the hot water draw-o points
if the hot water temperatures are higher than 60°C. Young
children and elderly persons are particularly at risk, even at
lower temperatures.
∙Select the temperature so that nobody is at risk.
∙Explain to the user how to select the best temperature taking
into account the risk of scalding and the risk of legionella.
2.1.6 Danger due to improper use
Nonprofessional work on the product can cause damage to the
installation and as a consequence even personal injury.
∙Only work on the product if you are a competent person.
2.1.7 Risk of material damage by additives in the
heating water
Frost and corrosion protection agents can cause changes to seals,
noise during heating mode and may lead to other consequential
damage.
∙Do not use any unsuitable frost or corrosion protection agents.
2.1.8 Risk of material damage caused by unsuitable
tools
The use of unsuitable tools or improper use thereof may cause
damage, such as gas or water leaks.
∙When tightening or loosening threaded connections, always
use suitable opened spanners, but do not use pipe wrenches,
extensions, etc.
2.1.9 Risk of structural damages by escaping water
Incorrect installation can cause leakages.
∙Make sure there are no stresses in the hydraulic lines.
∙Correctly position the seals.
2.2 Intended use
State-of-the-art
The product is a state-of-the-art product which has been
constructed in accordance with recognised safety regulations.
Nevertheless, there is still a risk of injury or death to the user
or others or of damage to the product and other property in the
event of improper use or use for which it is not intended.
Intended use
The product is intended as a heating appliance for sealed
central heating installations (heating / cooling and hot water) to
consume a minimum of energy to optimize the energy bill.
Applicable documents
Intended use includes the following:
- observing the included operating, installation and
maintenance instructions for this product and any other parts
and components of the system
- installing and tting the product in accordance with the
product and system approval
- complying with all of the inspection and maintenance
conditions listed in the instructions.
Moisture and water splashes
It will be necessary to install the unit in a location where it will not
be exposed to moisture or water splashes. Observe the electrical
protection (EP) contained in the technical data.
Unintended use
Any other use than the use described in the instructions at hand
or any use extending the described use is not intended.
Any direct commercial or industrial use is also deemed to be
improper.
2.3 Rules and regulations
2.3.1 Statutory requirements
Installation of this appliance falls within the scope of the Building
Regulations 2010 (Part G). This requires that the installation
of an unvented system should be notied to the local authority
Building Control Department and the work must be carried out by
a competent person as dened in the approved document G3.
Where no British Standards exists, materials and equipment
should be t for their purpose and of suitable quality and
workmanship.
The installation of this control unit must be carried out by a
competent person approved at the time by the Health and
Safety Executive and in accordance with the rules in force in the
countries of destination.
Manufacturer’s instructions must not be taken as overriding
statutory requirements.
During the installation and activation of the control unit, the
decrees, directives, technical regulations, standards and clauses
hereafter must be complied with in the versions that are currently
in force.
- IEC 60730-2-9 Automatic electrical controls for household and
similar use: Particular requirements for temperature sensing
controls
- IEC 60730-1 Automatic electrical controls for household and
similar use: Common requirements
- IEC 60335-1 Specication for safety of household and similar
electrical appliances
- Directive on the restriction of the use of certain hazardous
substances in electrical and electronic equipment (2002/95/
EC)

0020140826_00 - 08/12 - Glow-worm
- 4 -
INTRODUCTION
EN
- Regulation concerning the Registration, Evaluation,
Authorisation and Restriction of Chemicals (REACH, No.
1907/2006)
In GB, the installation of the control unit must comply with the
requirements of the current issue of BS6798 and be carried out
by a competent person approved at the time by the Health and
Safety Executive and as described in the following regulations:
- The manufacturer’s instructions supplied.
- The Gas Safety (Installation and Use) Regulations.
- The appropriate Building Regulations (UK), The Building
Regulations (Scotland), The Building Regulations (Northern
Ireland).
- The Water Supply (water ttings) Regulations 1999 and water
byelaws 2000, Scotland.
- The Health and Safety at Work Act, Control of Substances
Hazardous to Health (COSHH).
- Any electrical work must conform to BS7671 and part P of the
building regulations where applicable.
Where no specic instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent person
approved at the time by the Health and Safety Executive and
installed in accordance with the current edition of I.S.813
“Domestic Gas Installations”, the current Building Regulations
and reference should be made to the current ETCI rules for
Electrical Installation.
GB: the following Codes of Practice apply: BS4814, BS6798,
BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700,
BS7074 Part 1 and 2, BS7593, BS7671.
IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
NOTE: For further information, see the current issue of the
Building Regulations, approved document L1 ( in the UK) and the
following current issues of:
1) Central heating system specication (CheSS) and
2) Controls for domestic central heating system and hot water.
BRECSU.
Benchmark places responsibilities on both manufacturers
and installers. The purpose is to ensure that customers are
provided with the correct equipment for their needs, that it is
installed, commissioned and serviced in accordance with the
manufacturer’s instructions by a competent person approved at
the time by the Health and Safety Executive and that it meets the
requirements of the appropriate Building Regulations.
The Benchmark Checklist can be used to demonstrate compliance
with Building Regulations and should be provided to the
customer for future reference.
Installers are required to carry out installation, commissioning
and servicing work in accordance with the Benchmark Code
of Practice which is available from the Heating and Hotwater
Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
2.3.2 Domestic Hot Water
All domestic hot water circuits, connections, ttings must be
in accordance with the relevant standards and water supply
regulations.
2.3.3 Electrical Supply
The control unit MUST be earthed. All system components shall
be of an approved type and all wiring to current I.E.E. wiring
regulations. External wiring must be correctly earthed, polarised
and in accordance with the relevant standards.
In GB, this is BS 7671.
In IE, this is the current edition of ETCI rules.
The control unit MUST be connected to a permanent 230V ac,
50Hz supply.
2.4 CE label
The CE mark indicates that the products described in these
instructions are in compliance with the following directives:
- European Directive Num. 2004-108 of the European Parliament
and the Council regarding electromagnetic compatibility
- European Directive Num. 2006-95 of the European Parliament
and the Council regarding low voltage.
3 Description of the product
3.1 Product Overview
The control unit provides a system solution which permits eBUS
controllers to be combined with room thermostats, valves,
multizone heating and domestic hot water cylinder systems.
There are 2 functional modes that can be selected with the rotary
switch :
- Multizone mode (position 0) with SWC2 functions.
- Monozone mode (position 1) with SWC1 functions.
230V~ CYL.
2 1
DHW
CH1 CH2
ON
DHW
OFF
1
2
-
+
BUS NTC
0
1
Legend
1 Rotary switch

0020140826_00 - 08/12 - Glow-worm
- 5 -
INTRODUCTION
EN
3.2 Product structure
3.2.1 Monozone operation mode
The Monozone operation mode is compatible with:
- Climapro/Climapro2RF and Climapro1/Climapro1RF range
- System and open vent boiler
It allows the “Climapro or Climapro2RF” to communicate
with the traditional 230V zone valves and DHW storage
cylinder. Information about the heat required by the cylinder
is communicated to the heating appliance. The heating
appliance (boiler) then decides whether a hot water request
has to be fulfilled and sends a signal to position the 230V
zone valves.
The initial start-up of the Smart Wiring Centre controls is
carried out together with the initial start-up of the boiler.
iIf a Smart Wiring Centre is replaced by a Smart Wiring
Centre 2 it has to be set on monozone mode.
Settings
∙Flexicom
Press “MODE” and “+” buttons simultaneously for 5 seconds.
The display shows “0”.
∙Ultracom
Press “MODE” for 5 seconds. The display shows “0”.
∙Use the “+” or “-” buttons (Ultracom use the heating control
“+” or “-” button) to scroll through to number 35.
∙Press “MODE”.
∙Use the “+” or “-” buttons to scroll through to diagnostic
number d.70.
∙Press “MODE”.
∙Change the setting using the “+” and “-” buttons. Refer to
the table, for the most appropriate setting for the specic
application.
∙Save the new value by pressing “MODE”.
∙To leave the diagnostic menu press and hold “MODE” until the
running screen is displayed again.
3.2.2 Priorities are dened as follows:
Display Meaning
0 Hot water priority
- The 3-port valve is in the heating or hot water position
depending on the operating mode.
- With 2-port valves, either the DHW valve or the CH valve is open,
both valves are closed on standby.
1 Enable mid position
- The 3-port valve is in the mid position for simultaneous heating
and hot water request, or in the heating or hot water position,
depending on the operating mode.
- With 2-port valves, both valves are open during simultaneous
heating and hot water request. Otherwise, only one valve is
always open and both valves are closed on standby.
2 Only heating mode (only for test
operation!)
- Only the CH valve is activated.
NOTE: Factory settings of boiler = 0 : hot water priority.

0020140826_00 - 08/12 - Glow-worm
- 6 -
INTRODUCTION
EN
3.2.3 Monozone mode : Open vent or system boiler with DHW cylinder, 3-Port Valve
EBUS
EBUS
1
2
-
+
BUS NTC
L N L L
16A
230V~ CYL. DHW
CH1 CH2
2 1
BUS
16A
N L
BUS
ON
DHW
OFF
1m min.
1
2
-
+
BUS NTC
L N L L
16A
230V~ CYL. DHW
CH1 CH2
2 1
ON
DHW
OFF
1
1
BUS
16A
N L
BUS
10
9
5
2
A
B11
9
8
7
5
3
4
6
4
1
C
D
5
3
1
2
4
4
9
1
2
Key
1 Climapro room thermostat
2 System boiler
3 3-port valve
4 Electrical supply
5 Smart Wiring Center 2 control unit
6 Bypass necessary with open vent boilers
7 Domestic hot water cylinder
8 NTC (not supplied)
9 Cylinder thermostat
10 Heating circuit
11 Overheating safety (if underoor heating)
A Boiler circuit return
B Boiler circuit ow
C Cold water supply
D Domestic hot water outlet
DHW cylinder with NTC DHW cylinder with thermostat
3-port valve electrical connections:
∙Connect the live wire (white or brown) of the valve to the “L” of
the CH1 connector.
∙Connect the earth wire (yellow/green) of the valve to the earth
of the DWH ON connector.
∙Connect the neutral wire (blue) of the valve to the “N” of the
DWH ON connector.
∙Connect the live wire (orange) of the valve to the "L" of the
DWH ON connector.
∙Connect the live wire (grey) of the valve to the "L" of the DWH
OFF CH2.

0020140826_00 - 08/12 - Glow-worm
- 7 -
INTRODUCTION
EN
3.2.4 Monozone mode : Open vent or system boiler with DHW cylinder : two 2-Port Valves
EBUS
EBUS
1
2
-
+
BUS NTC
N L N L
16A
230V~ CYL. DHW
CH1 CH2
2 1
ON
DHW
OFF
6
4 3
5
1
2
-
+
BUS NTC
N L N L
16A
230V~ CYL. DHW
CH1 CH2
2 1
ON
DHW
OFF
1
1
BUS
16A
N L
BUS
BUS
16A
N L
BUS
1
2
11
6
2
8
3
A
B
9
10
4
127
5
1
C
D
1m min.
10
10
1
2
6
4 3
6
Key
1 Climapro room thermostat
2 System boiler
3 DHW valve - 2-port valve
4 Heating 2-port valve
5 Electrical supply
6 Smart Wiring Center 2 control unit
7 Bypass necessary with open vent boilers
8 Domestic hot water cylinder
9 NTC (not supplied)
10 Cylinder thermostat
11 Heating circuit
12 Overheating safety (if underoor heating)
A Boiler circuit return
B Boiler circuit ow
C Cold water supply
D Domestic hot water outlet
DHW cylinder with NTC DHW cylinder with thermostat

0020140826_00 - 08/12 - Glow-worm
- 8 -
INTRODUCTION
EN
3.2.5 Multizone operation mode
The Multizone operation mode is compatible with:
- Climapro1
- system, combi and open vent boiler
The information about the heating or hot water demand is sent to
the room thermostat via the control unit to the boiler. The Smart
Wiring Centre 2 then decides if the hot water demand needs to be
fullled and drives the valves.
In this way, the boiler can store dierent target temperatures for
heating and hot water modes.
iThe multizone mode is compatible with Flexicom and
Ultracom ranges.
The multizone mode is only compatible with
Climapro1. No other room thermostats are
compatible.
The multizone mode will NOT support weather
compensation and cannot be used on Y plan systems
with three port motorised valves.
The standard installation for multizone mode is characterised by:
- 1 or 2 port valves for zoning,
- 1 or 2 Climapro1programmable wired room thermostats,
- heating zones and DHW cylinder cannot operate in parallel.
Priorities are dened as follows:
Priority levels Function
1 Domestic hot water
2 Central heating

0020140826_00 - 08/12 - Glow-worm
- 9 -
INTRODUCTION
EN
3.2.6 Multizone mode : Open vent or system boiler with DHW cylinder
EBUS
EBUS
1
2
-
+
BUS NTC
N L N L N L
EBUS
16A
1
2
-
+
BUS NTC
N L N L N L
230V~ CYL.
2 1
16A
230V~ CYL.
2 1
BUSBUS
16A
N L
BUS
BUSBUS
16A
N L
BUS
DHW
CH1 CH2
ON
DHW
OFF
0
0
16
15
10
10
2
12
7
A
B
5
13
613 7
6
8
8
1411
9
1
9
10
67 8 5
123 123
9
4 4
C
D
3
1m min.
DHW
CH1 CH2
ON
DHW
OFF
Key
1 Climapro1room thermostat "zone 1"
2 Open vent or system boiler
3 Climapro1room thermostat "zone 2"
4 Connection block (not supplied)
5 NTC (not supplied)
6 Heating zone 2 - 2-port valve
7 DHW valve - 2-port valve
8 Heating zone 1 - 2-port valve
9 Electrical supply
10 Smart Wiring Center 2 control unit
11 Bypass necessary with open vent boilers
12 Domestic hot water cylinder
13 Cylinder thermostat
14 Overheating safety (if underoor heating),
as far as possible or 1m min. of cylinder connection
15 Heating circuit zone 1
16 Heating circuit zone 2
A Boiler circuit return
B Boiler circuit ow
C Cold water supply
D Domestic hot water outlet
DHW cylinder with NTC DHW cylinder with thermostat

0020140826_00 - 08/12 - Glow-worm
- 10 -
INTRODUCTION
EN
3.2.7 Multizone mode with combi boiler
EBUS
EBUS
EBUS
1
2
-
+
BUS NTC
N L N L
16A
230V~ CYL. DHW
CH1 CH2
2 1
BUSBUS
16A
N L
BUS
ON
DHW
OFF
0
0
10
9
8
2
A
B
D
5
6
11
7
3
8
5 6
123
7
4
1
C
Key
1 Climapro1thermostat "zone 1"
2 Combi boiler
3 Climapro1thermostat "zone 2"
4 Connection block (not supplied)
5 Heating zone 2- 2-port valve
6 Heating zone 1- 2-port valve
7 Electrical supply
8 Smart Wiring Center 2 control unit
9 Heating circuit zone 1
10 Heating circuit zone 2
11 Overheating safety (if underoor heating)
A Boiler circuit return
B Boiler circuit ow
C Cold water supply
D Domestic hot water outlet

0020140826_00 - 08/12 - Glow-worm
- 11 -
INSTALLATION
EN
3.3 Type designation and serial number
Data plate location:
1
3.4 Data plate description
The data plate certies the country where the product is intended
to be installed.
The data plate contains the following data:
Abreviation/symbol Description
Brand and Product name GW Smart Wiring Center 2
Model Product article number
V/Hz Voltage / Frequency
T Temperature range
Serial-no Product serial number
See chapter Recycling
See chapter "CE label"
VA Power Consumption
4 Mounting and installation
iAll the dimensions shown of the illustrations are expressed in
millimetres (mm).
4.1 Preparing the mounting and installation
4.1.1 Considering the product location
Before choosing a site for the appliance, carefully read the safety
warnings and instructions in the user guide and installation
manual.
∙Explain these requirements to the appliance user.
∙Take all necessary precautions.
Install the system:
- in a room protected from frost,
- in a convenient location, accessible for wiring and servicing.
Do not install the control unit:
- close to heat sources such as radiators, chimney walls,
televisions, direct sunlight,
- above a cooking device capable of generating steam and
grease,
- in a room with a lot of dust or with a corrosive atmosphere.
b
Caution!
These pipes can become very hot which will damage
the cables or the system.
• The electrical cables must not be attached to or in
contact with the hydraulic pipes.
1500
185
281.3
49.5
4.2 Mounting the product
4.2.1 Opening the Smart Wiring Center 2
A
B
∙Unscrew (A) the screw securing the housing cover.
∙Pull (B) the housing cover forwards.

0020140826_00 - 08/12 - Glow-worm
- 12 -
INSTALLATION
EN
4.2.2 Wall-mounting of the product
The control unit is designed to be attached to a wall near the main
tank inside a dwelling.
235
3
3
4
1
1
2
2
Key
1 Screws
2 Attachment holes
3 Holes
4 Plugs
∙Determine the position depending on the requirements of the
preceding chapter: “Appliance location”.
4.3 Electrical Installation
eDanger!
Incorrect installation can cause electric shock or
appliance damage.
The electrical connection of the appliance must be
made only by a qualified engineer.
• Ensure system is electrically isolated.
Protect the electrical installation by following the
guidance indicated in the “Technical data”
chapter.
eDanger!
• The length of the power supply cable must not
exceed 10 metres.
∙The electrical installation in the dwelling must permit the
power supply to the equipment to be isolated by a double pole
isolation switch and be fused. The double pole isolation switch
must incorporate a gap of 3mm between the contacts.
∙Use a power cable suitable for the main connection, minimum
1.5 mm. If the cable is damaged, it must be replaced by a
qualied engineer.
The external wiring must be earthed, with correct polarity and in
accordance with current standards.
The manufacturer declines any responsibility for damages to
persons or others caused by the incorrect installation of the
appliance earthing. This includes failure to comply with current
standards.
b
Caution!
These pipes can become very hot which will damage
the cables or the system.
• The electrical cables must not be attached to or in
contact with the hydraulic pipes.
4.3.1 Description of connections
All of the internal connections are made directly to the circuit
board.
2
3
1
Key
1 Cable clamp
2 Divisible wire grommet
3 Separating high and low voltage
The circuit board connectors are divided into two parts. The left
part accepts a 230V power supply whereas the right part is used
for 24V power.
230V connectors (High voltage)
230V~ CYL.
2 1
DHW
CH1 CH2
ON
DHW
OFF
1
2
-
+
BUS NTC
230V~ CYL.
2 1
DHW
CH1 CH2
ON
DHW
OFF
1 2 3 4 5
Key
1 230V supply connector (3 pins: earth / neutral / live)
2 Cylinder thermostat connector (2 pins)
3 Heating zone 1 valve (3 pins: earth/neutral/ live)
4 DHW valve ON (3 pins: earth / neutral / live)
5 DHW valve OFF - Heating zone 2 valve (3 pins: earth/neutral/ live)

0020140826_00 - 08/12 - Glow-worm
- 13 -
INSTALLATION
EN
24V connectors (low voltage)
230V~ CYL.
2 1
DHW
CH1 CH2
ON
DHW
OFF
1
2
-
+
BUS NTC
1
2
-
+
BUS NTC
1 2
Key
1 eBUS connector (2 pins)
2 NTC connector (2 pins)
4.3.2 Main board
20 mm max.
2
1
Key
1 Electrical wires
2 Casing
When you connect the electrical wires to a connector on the main
electronic board:
∙Keep a distance of a maximum of 20 mm between connector
and the start of the insulation (2).
∙If single core wires are used (1) ensure that they are wrapped
together in an insulating sheath.
∙Fix the cables in the cable-clamps on the unit.
4.3.3 Glow-worm appliances with electrical cartridge
housing
3
2
14
5
AB
Key
1 Access from undermeath (remove rubber)
2 Cartridge housing
3 Tab
4 Retaining screws
5 Securing screw
Glow-worm open vent boilers Ultracom hxi Flexicom hx
2
1
3
Key
1 Cable strain relief
2 Connect to eBUS connection
3 Cable to smart wiring center 2 kit
i
The link wire will be necessary.
You have to add the link between L & R (a link wire is
not supplied).
1
Key
1 link wire
Glow-worm system boilers Ultracom sxi, Flexicom sx
2 2
13
Key
1 Cable to smart wiring center 2 kit
2 Connect to eBUS connection
3 link wire
i
The link wire will be necessary.
You have to add the link between 0V & 24V (a link
wire is not supplied).
4.3.4 GW appliances without electrical cartridge housing
The link wire is provided with boiler and already tted to the 24V
terminals (RT/24V). Link wire must not be removed if using with
SWC2.

0020140826_00 - 08/12 - Glow-worm
- 14 -
MAINTENANCE
EN
5 Commissioning
The commissioning should be carried out by a competent person
approved at the time by the Health and Safety Executive and in
accordance with the current issue of BS6798.
∙Completely open all the radiator thermostatic valves in the
rooms where the room thermostats were been installed.
5.1 Filling
5.1.1 Boiler
Commission the boiler according to the instructions of its
installation manual.
∙Refer to the installer manual.
5.1.2 Heating circuit
∙ Manually open the dierent heating circuit valves.
5.2 Venting
5.2.1 Boiler
Commission the boiler according to the instructions of its
installation manual.
∙Refer to the installer manual.
5.2.2 Heating circuit adjustement
Venting of the heating circuit enables the purging of any air in the
heating circuit (valves still manually opened).
∙ Open the dierent heating circuit air vent.
b
Caution!
• When venting is complete, close the different
heating circuit air vent and valves.
5.3 Switching on
∙Turn on all the appliances that make up the installation (see
the installation manual(s). Use the following order:
- Control unit
- Boiler
5.4 Multizone specic adjustment
In case of multizone mode selection (rotary switch in pos 0),
the pairing must be made between the room thermostat(s) and
control unit in the system heating (one after the other).
∙Follow the install assistant of the room thermostat "zone 1".
∙Consult the installation manual of the room thermostat in
order to carry out the operation.
∙Repeat the operation with the room thermostat "zone 2"
5.5 Restart and check
∙Check if all settings have been saved by switching the system
o and then on to ensure that any adjustments operate
correctly and check that the appliances operate safely.
∙Check if the system answers correctly to a demand:
- issue a heating demand for the heating zone 1
- issue a heating demand for the heating zone 2 (If multizone
mode is selected)
- issue a domestic hot water demand (if DWH tank is connected)
6 User information
At the end of the installation, the installer must:
- explain the operation of the appliance and its safety devices to
the user, if necessary provide a demonstration and answer any
questions;
- give the user all the required documentation,
- ll in the documents where necessary;
- advise the user of the precautions necessary to prevent
damage to the system, appliance and the building;
- remind the user to service the appliance annually.
7 Maintenance
7.1 Trouble-shooting
7.1.1 Fault diagnosis
The following checks should be performed before proceeding
onto specic diagnostics:
- Ensure that the control unit has not been disconnected from
the electricity supply and that it is connected correctly.
- Ensure that all installation’s appliances are available.
- Check the functioning of external regulatory devices (room
thermostat(s).
iThe rectification of faults described in this chapter
should be carried out by a qualified engineer and if
needed by the After Sales Service.
230V~ CYL.
2 1
DHW
CH1 CH2
ON
DHW
OFF
1
2
-
+
BUS NTC
2
13
Key
1 Fuse
2 Green LED, power supply
3 Red LED ashes, fault

0020140826_00 - 08/12 - Glow-worm
- 15 -
MAINTENANCE
EN
Fault Possible cause Solution
Green LED
permanently o
No 230 V power supply
or the fuse in the
appliance is faulty
Check that the main
voltage cable is
connected correctly.
Check the domestic
fuse for the 230 V
supply and re-connect
the power supply.
Replace the main
supply fuse in the
control unit (see
technical data).
Red LED ashes
quickly (2 Hz, 2
ashes/second)
Short circuit of
the connected
temperature sensor
(NTC) in the cylinder
Check the cable of the
temperature sensor
(NTC) for damage.
Replace the
temperature sensor
(NTC) in the cylinder.
Red LED ashes
slowly (0,5 Hz, 1
ashes/ 2 seconds)
Communications error
with the eBUS boiler.
Check that the
boiler's eBUS cable is
connected correctly
and not damaged
Check that the boiler
is turned on
Heating zone valves
not operating
Valve disconnected.
Valve doesn't open.
Check the room
thermostat(s)
compatibility and
connections.
Check the valve
connections.
Check the room
thermostat(s) pairing.
Ensure that there is
no interruption to the
electricity supply and
that the unit control
is properly connected
and turned on.
DHW valve not
operating
Fault domestic hot
water cylinder
Cylinder dual
thermostat
disconnected.
The temperature
sensor is defective or
disconnected.
Check the cylinder
dual thermostat
and temperature
connections.
Check the sensor’s
resistance.
Ensure that there is
no interruption to the
electricity supply and
that the control unit
is properly connected
and turned on.
7.2 Main supply cable
eDanger!
• The main supply cable must be replaced by a
qualified and competent electrician.
∙If the main supply cable is damaged, replace it refering to the
chapter "Electrical connection".
8 Decommissioning
∙ Switch o the product.
∙Isolate the product from the power mains.
∙De-install the product.
∙Recycle or dispose the product and its components (see
chapter 9).
9 Recycling and disposal
9.1 Recycle the packaging
- Sort the waste to separate those which can be recycled
(cartons, plastics...) from those that cannot (strapping ...).
- Recycle the product packaging according to all relevant
regulations.
9.2 WEEE: Recycle or dispose the product and its
components
The product must be recycled under the WEEE Directive (Waste
Electrical and Electronic Equipment), which species:
- the selective collection of waste electrical and electronic
equipment.
- the selective systematic treatment of certain components and
substances considered as dangerous,
- the reuse, recycling and recovery of the collected WEEE.
∙Do not dispose of your product or any of its
accessories in the household waste.
∙Make sure the old unit and any accessories are
disposed of properly.
∙Deposit the product at an appropriate collection point for the
treatment, evaluation and recycling of WEEE.
∙Observe all relevant regulations.
i By adhering to this directive, you are helping the envi-
ronment and contributing to the preservation of natu-
ral resources and the protection of human health.

0020140826_00 - 08/12 - Glow-worm
- 16 -
TECHNICAL DATA
EN
10 Guarantee and customer service
We only grant a manufacturer's guarantee if a suitably qualied
engineer has installed the system in accordance with the
instructions. The system owner will be granted a guarantee in
accordance with the manufacturer's terms and conditions. For all
requests for work during the guarantee period contact your after
sales organisation on 01773 828100.
11 Technical data
Description Unit Smart Wiring Center 2
Power-supply voltage V/Hz 230/50
Power consumption VA 4
Contact load of output relays (max.) A 2
Delay fuse A T 4A/250V
Contact voltage for DHW cylinder
thermostat
V 230
Temperature sensor (NTC)
operating voltage
V 5
Thermistor NTC at 25°C kOhm 2,7
eBUS connection cable gauges mm22 x 0.75
Maximum length of eBUS cable m 300
Power cable gauge mm23 x 1.5
Maximum length of power cable m 10
Dimensions :
Height mm 185
Length mm 281.3
Depth mm 49.5
Electrical protection IP20
Electrical classication II


0020140826_00 - 08/12 Subject to engineering changes
GLOW-WORM
Nottingham Road,
Belper, Derbyshire.
DE56 1JT
Because of our constant endeavour for
improvement, details may vary slightly
from those shown in these instructions.
www.glow-worm.co.uk The energy you need
Table of contents
Other Glowworm Control Unit manuals
Popular Control Unit manuals by other brands

OilGear
OilGear EPC 300 Series user manual

Hansen
Hansen EZ-SRV Series Specifications, Applications, Service Instructions & Parts

Gravotech
Gravotech XCOM Operating and maintenance manual

Tyco Fire Product
Tyco Fire Product STAR SPRINKLER S370 instructions

Fleck
Fleck 7700 quick start guide

Richter
Richter KSE/F Series Installation and operating manual