Glowworm SYSTEMPRO User manual

SYSTEMPRO
www.glow-worm.co.uk
Control unit
Installation and Servicing


- 1 -
INTRODUCTION
1 Instructions guidance.........................................................................................................................3
1.1 Product documentation...........................................................................................3
1.2 Associated documents ...........................................................................................3
1.3 Explanation of symbols...........................................................................................3
2 Product description ............................................................................................................................3
2.1 Regulation and statutory requirements ..................................................................3
2.2 Block diagram.........................................................................................................3
3 Safety instructions and regulations....................................................................................................3
3.1 Safety instructions ..................................................................................................3
3.2 Regulations.............................................................................................................4
4 Recycling ...........................................................................................................................................4
4.1 The equipment........................................................................................................4
4.2 Packaging...............................................................................................................4
INSTALLATION
5 Control unit location ...........................................................................................................................5
6 Installation..........................................................................................................................................5
6.1 Dimensions.............................................................................................................5
6.2 Scope of delivery....................................................................................................5
6.3 Installation ..............................................................................................................6
7 Electrical connections .......................................................................................................................7
7.1 External connection................................................................................................7
7.2 Internal connection .................................................................................................8
7.3 Electrical connections.............................................................................................8
8 Commissioning ..................................................................................................................................9
9 Installation menu..............................................................................................................................10
9.1 Description of buttons...........................................................................................10
9.2 Access to the installation menu............................................................................10
9.3 Description of the installation menu .....................................................................10
9.4 Installation ............................................................................................................10
9.5 Thermostat and sensor.........................................................................................10
9.6 Automatic test....................................................................................................... 11
9.7 Parameters...........................................................................................................12
9.8 Commissioning.....................................................................................................12
9.9 Component information ........................................................................................12
9.10 Options .................................................................................................................13
10 Specific adjustment..........................................................................................................................13
10.1 Resetting the control unit......................................................................................13
11 Re-check and restart........................................................................................................................13
12 User information...............................................................................................................................13
TABLE OF CONTENTS

- 2 -
MAINTENANCE
13 Trouble-shooting ..............................................................................................................................14
13.1 Fault diagnosis .....................................................................................................14
13.2 Maintenance menu...............................................................................................14
13.3 System failure codes ............................................................................................15
13.4 Control unit failures...............................................................................................16
13.5 Replacing a fuse...................................................................................................16
TECHNICAL DATA
14 SYSTEMPRO ..................................................................................................................................16
TABLE OF CONTENTS

0020094626_00 - 06/10 - Glow-worm
- 3 -
INTRODUCTION
1 Instructions guidance
1.1 Product documentation
The instructions are an integral part of the equipment and must
be handed to the user on completion of the installation in order
to comply with the current regulation.
• Carefully read the manual to allow for safe installation, use
and servicing. No liability can be accepted in the event
of damage for not complying with the guidance in this
instruction manual.
1.2 Associated documents
- User instructions
1.3 Explanation of symbols
eDANGER: Risk of electric shock.
ATTENTION: Risk of damage to the equipment or
to its surroundings.
IMPORTANT: Important information.
2 Product description
2.1 Regulation and statutory requirements
CE Mark
The CE mark indicates that the equipment described in this
manual are in compliance with the following directives:
- European Directive Num. 2004-108 of the European
Parliament and the Council regarding electromagnetic
compatibility
- European Directive Num. 2006-95 of the European
Parliament and the Council regarding low voltage
- Directive regarding telecommunications equipment (
Directive R & TTE 99/5/EEC of the Council of the European
Community)
- Low Voltage Directive 72/23/EEC.
2.2 Block diagram
EBUS
230V
IN
OUT
NTC
1
2
3
4
5
6
7
Key
1 EBUS connections
2 Input/Output, sensors
3 230 V power supply
4 Control unit
5 Wireless outdoor sensor
6 Room thermostat
7 Batteries
3 Safety instructions and regulations
3.1 Safety instructions
eIncorrect installation can cause electric shock or
appliance damage.
All electrical work performed on the equipment must be carried
out by a qualified engineer or Glow-worm Group Service
engineer.
This equipment must only be installed by a qualified and
engineer, to ensure that the applicable regulations and rules are
adhered to.
Follow the basic safety instructions:
• Stop the control unit.
• Turn off the control unit’s power supply.
INTRODUCTION

0020094626_00 - 06/10 - Glow-worm
- 4 -
• When work on the product is completed, perform an
operational test and check for safety in accordance with BS
EN 7671.
3.2 Regulations
During the installation and activation of the control unit, the
decrees, directives, technical regulations, standards and
clauses hereafter must be complied with in the versions that are
currently in force.
4 Recycling
iThe recycling of the packaging must be carried
out by the qualified professional who installed the
equipment.
4.1 The equipment
Most of the equipment is made of recyclable materials.
This symbol indicates that this appliance must not
be disposed of with household waste, that it should
be selectively collected for energy recovery, reuse
or recycling.
• Take the equipment to an appropriate collection point.
iBy complying with this directive, you will contribute
to the preservation of natural resources and the
protection of human health.
4.2 Packaging
We recommend that you recycle the packaging of the appliance
in a responsible fashion.
• Sort the waste in order to separate those elements which
can be recycled (cardboard, plastics ...) and those which
cannot be recycled.
• Dispose of the waste in accordance with existing regulations.
INTRODUCTION

0020094626_00 - 06/10 - Glow-worm
- 5 -
INSTALLATION
All the dimensions shown of the illustrations are
expressed in millimetres (mm).
5 Control unit location
• Take all necessary precautions.
Install the system:
- in a room protected from frost,
- in a convenient location, accessible for wiring and servicing
allowing for visibility of the screen.
Do not install the control unit:
- close to heat sources such as radiators, chimney walls,
televisions, sun rays,
- above a cooking device capable of generating steam and
grease,
- in a room with a lot of dust or with a corrosive atmosphere.
1500
6 Installation
6.1 Dimensions
290
264
45
6.2 Scope of delivery
3
1
2
Key
1 2 packs with 2 screws with Ø 6 mm plugs
2 2 packs containing 7 anti-tamper connectors
(one anti-tamper connector installed)
3 Control unit
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 6 -
6.3 Installation
• Ensure that the materials used for installation are compatible
with those of the control unit.
• Determine the location of the installation. See the
"Placement selection" chapter.
290
145
126,5
128
23
1
3
2
145
143,5
Key
1 Control unit
2 Lower attachment holes
3 Upper attachment holes
Step 1
• Mark the upper wall attachment point.
A
B
C
5
1
2
3
Key
1 Upper screw
2 Plug
3 Holes
• Drill a Ø 6 mm hole (3) for the upper attachment point.
• Insert the plug (2) in the hole (3).
• Tighten the upper attachment point screw (1), leaving a
5 mm gap between the screw head and the wall.
Step 2
A
C
B
D
1
2
3
4
5
6
Key
1 Hatch screw
2 Control unit hatch
3 Lower attachment holes
4 Control unit
5 Upper screw
6 Upper attachment holes
• Position the control unit (4) by aligning the screw (5) and the
upper attachment hole (6).
• Slide the control unit (4) down.
• Unscrew the 2 screws securing the hatch (1)
• Remove the control unit hatch (2).
• Level the control unit (4).
• Mark the 2 lower wall attachment points (3), in line with the
mounting holes.
• Remove the control unit (4) by sliding along the wall.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 7 -
Step 3
A
B
3
1
2
Key
1 Plugs
2 Upper attachment screws
3 Holes
• Drill Ø 6 mm holes (3) for the lower attachment points.
• Insert the plugs (1) in the holes (3).
Step 4
B
A
1
2
3
4
Key
1 Lower screws
2 Control unit
3 Upper screw
4 Upper attachment holes
• Reinstall the control unit on the wall (see step 2).
• Screw the 2 lower attachment screws (1) to attach the
control unit to the wall.
7 Electrical connections
eIncorrect installation can cause electric shock
or damage to the equipment. The electrical
connection must be made only by a qualified
engineer.
• Ensure system is electrically isolated.
• Protect the electrical installation by following the guidance
indicated in the “Technical data” chapter.
eWarning! The length of the power supply cable
must not exceed 10 metres.
• The electrical installation in the dwelling must permit the
power supply to the equipment to be isolated by a double
pole isolation switch and be fused. The double pole isolation
switch must incorporate a gap of 3mm between the contacts.
• Use a power cable suitable for the mains connection,
minimum 0.75 mm. If the cable is damaged, it must be
replaced by a qualified engineer.
The external wiring must be earthed. The polarity must be
correct and consistent with current standards.
The manufacturer declines any responsibility for damages to
persons or others caused by the incorrect installation of the
appliance earthing. This includes failure to comply with current
standards.
7.1 External connection
1
2
3
5
4
Key
1 Switch On (I) / Off (O)
2 Fuse 1AT 20mm
3 Antenna
4 RJ9 EBUS socket
5 RJ11 EBUS socket
The switch (1) is employed to cut the power supply before
making any changes to the electrical connection.
The electrical circuit of the equipment is protected internally by
a fuse (2).
The antenna is used for wireless connection with the
Climapro2 RF and the outdoor sensor.
The RJ9 EBUS (4) socket is used for diagnosing the appliance.
The RJ11 EBUS (5) socket is used for connecting the EBUS
extension board.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 8 -
7.2 Internal connection
7.2.1 230V connectors
13
LN
230V~
13
LN
REL1
13
LN
REL2
13
LN
REL3
12
LN
REL4
12
LN
REL5
12
LN
IN1
321
Key
1 230 V connector (3-pin: earth / neutral / live)
2 Connectors (3 pins: earth / neutral / live):
REL1, REL2 and REL3
3 Connectors (2 pins: live / neutral):
REL4, REL5 and IN1
Consult the system manual for electrical connections
following installation.
The connector (1) is employed to connect the electricity supply.
7.2.2 24V connectors
12
21
OUT1
12
21
OUT2
12
21
OUT3
12
21
IN2
12
21
IN3
12
21
NTC1
12
21
NTC2
12
21
NTC3
12
21
NTC4
12
-+
EBUS
12
-+
EBUS
12
-+
EBUS
21
Key
1 Connectors (2 pins)
OUT1, OUT2, OUT3, IN2, IN3, NTC1, NTC2, NTC3 and NTC4
2 EBUS connectors (2 pins)
Consult the system manual for electrical connections
following installation.
Ensure correct polarity of ebus connections.
7.3 Electrical connections
1 32
Key
1 Connector
2 Electrical wires
3 Casing
eWarning! When connecting electrical cables to a
connector in the control unit:
• Maintain a maximum distance of 20 mm between the
connector (1) and the outer insulation (3).
7.3.1 230V power supply
C
B
A
D
1
2
3
4
5
Key
1 230 V power cable
2 Break out tab
3 Anti-tamper connection
4 Power connection
5 Control unit
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 9 -
• Gently remove the break out tab (2) from the control unit with
pliers (A).
• Connect the control unit following the order (B) to (D).
• Pass the power cable (1) through the anti-tamper connector
(3).
• Connect the power supply to the 230 V connector (4)
following the instructions given on the connector.
• Tighten the power cable (1) in the anti-tamper connector (3).
7.3.2 Other connections following the electrical
installation diagram
eWarning! Risk of electric shock.
Break the grommets necessary for passing the
cables.
• Protect access to live parts, attach all cables to the control
unit with anti-tamper connectors.
Consult the system manual for electrical connections
following installation.
8 Commissioning
• Turn on the power supply to the control at the isolator.
1
2
Key
1 Control unit
2 Switch On (I) / Off (O)
• Turn on the control unit (1) with the switch (2) in position (I).
When connected for the first time, the installation
menu is displayed.
• Choose the language with the
buttons .
• Press the button to confirm.
• Enter the installer access code 96
with the keys .
• Press the button to confirm.
• Follow and confirm the steps
prompted by the initial installation
aid.
• Press the button to confirm.
Consult the system manual in order to install and
start-up the system.
Date and time
The date and time settings are configured via the Climapro2 RF.
• Refer to the Climapro2 RF instructions in order to adjust
settings.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 10 -
9 Installation menu
9.1 Description of buttons
Buttons Description
Up / down buttons
The buttons allow:
- To browse menus.
- To decrease / increase value to be adjusted.
- To reset the control unit (factory setting by pressing
simultaneously both buttons for 10 seconds).
Back button
The button allows:
- To return to the previous menu.
- To return to the previous setting.
OK button
The button allows:
- Confirmation of the selection or setting.
Menu button
The button allows:
- To access the installation menu.
- To access the maintenance menu.
- To return to the installation and maintenance
menus (at any time).
- To return to the main user screen by pressing for 3
seconds.
9.2 Access to the installation menu
• Press the button for 7 seconds.
• Enter the installer access code 96.
• Press the button to confirm.
9.3 Description of the installation menu
Menu Browsing
Use the keys :
Select by pressing the button :
Press the key :
- to return to the installation menu
screen,
- for 3 seconds to return to the main
user screen.
The control units installation menu allows you to carry out
certain adjustments to the installation.
The control unit and the room thermostat have some common
settings. Adjustments made to the control unit automatically
modify those of the Climapro2RF room thermostat.
At the end of each configuration stage, the current stage is
highlighted.
9.4 Installation
The multizone installation screen refers to the
installation of zone valves in the system (Z20 &
Z30 kits can be substituted for zone valves for two
and three zones (same temperature) respectively).
A mixer module can also be used in place of the Z11
kit which mixes one high and one low temperature
zone.
9.4.1 Modifying the installation
This menu allows you to change the diagram number when
modifying the installation’s configuration.
A diagram number is assigned to each possible installation, with
various options available. The number is indicated in the system
manual.
9.4.2 Modifying options
This menu allows you to enable or disable the options available
in the selected installation diagram.
9.5 Thermostat and sensor
Pairing (recognition) is necessary in order to use:
- the Climapro2RF room thermostat(s),
- the wireless outdoor sensor.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 11 -
A room thermostat is assigned to an area in the building. If the
property has more than one zone, carry out the adjustments for
each zone.
The system may include 1 to 6 room thermostats and a wireless
outdoor temperature sensor.
9.5.1 Pairing with the Climapro2RF room
thermostat(s)
Adjustments must be made simultaneously to the control unit
and the room thermostat.
Via the control unit:
• From the installation menu in the control unit > select on the
screen > thermostat/sensor > room stat(s) press ok button
on the control unit.
• Select the area covered by the room thermostat by pressing
the buttons .Confirm by pressing the button
.
Via the room thermostat:
• Press the button for 7 seconds.
• Enter the installer access code 96.
• Via the installer room thermostat menu > select on the
screen > RF > pairing
• Press the room thermostat button .
The control unit and the room thermostat will immediately
indicate recognition on their respective "connection in progress"
screens.
If the message "Connection error" appears, press and
repeat the operation.
9.5.2 Pairing with wireless outdoor sensor
• Consult the outdoor sensor’s installation manual in order to
carry out the operation.
The wireless outdoor sensor must be paired with
the Systempro control before installing the outdoor
sensor.
9.5.3 Outside temperature adjustment
This feature allows you to adjust the temperature measured by
the outdoor sensor (+ / - 5 ° C, with intervals of 1 ° C - factory
setting: 0).
• From the installation menu> select on the screen > 2-rmstat
/ sensor > outdoor sensor > external T ° correction
• Increase or decrease by pressing ) to display
the desired adjustment and press the button to
confirm.
9.6 Automatic test
The automatic test allows you to check:
- EBUS inputs,
- NTC inputs,
- the RF connection with the Climapro2room thermostat,
- the outdoor sensor radio connection.
The other connections are not tested and should be
visually inspected during installation or configuration
modifications.
• From the installation menu> select on the screen >
automatic test
• Switch on all the installation’s components.
• Confirm the launching of the test by pressing .
The result is displayed in seconds, indicating the status of each
appliance.
• If the status of a component is not correct, check the wiring
or relaunch the pairing.
eIsolate the electrical supply to the equipment
prior to verifying or changing a connection.
• Carry out the necessary wiring work.
Once the power has been reconnected, the control unit returns
to the current control function.
• Repeat the test.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 12 -
9.7 Parameters
This menu allows you to adjust different functions in accordance
with the connected appliances and to reset all the parameters.
9.7.1 Maximum flow heating temperature
This menu allows you to adjust the maximum flow heating
temperature (the value is adjustable between 30 ° C and 80 °
C - factory setting: 73°C).
Ensure that the maximum heating flow
temperature setting is compatible with the
installation.
• From the installation menu> select on the screen >
4-settings > heating > maximum flow temperature >
maximum flow temperature
• Increase or decrease by pressing to display the
desired value and press the button to confirm.
9.7.2 Selecting the heat curve
This function allows you to select the heating curve (value
adjustable between 0.2 and 4 - factory setting: 1.2 for the high
temperature zone and 0.6 for the low temperature zone).
Ensure that the heat curve is correctly matched
to the design of the heating system.
• From the installation menu> select on the screen >
4-settings > heating > htg curve setting > htg curve
setting
• Consult the outdoor sensor’s installation manual to
determine the curve adjustment value.
• Increase or decrease by pressing to display the
desired values and press the button to confirm.
9.7.3 Hot water, cooling and energy management
The settings available vary in accordance with the installation
diagram and the options selected.
Consult the system manual in order to install and
start-up the system.
9.7.4 Resetting parameters
This function allows you to reset the parameters of the control
unit (factory setting).
The resetting of factory settings is irreversible.
Any customised configuration of the control unit
will be lost.
9.8 Commissioning
This menu allows you to carry out the necessary operations on
the appliances following installation.
9.9 Component information
This menu enables real-time access to:
- the status of the appliances responding to a demand (ON /
OFF)
- the reading the different information available from the
appliances (temperature, pressure, flow,)
- the register of last 5 faults recorded for each appliance (date,
time, code and description of faults).
Refer to the "Troubleshooting> failure codes" chapter
for a description of the fault code displayed on the
screen.
The fault status may be “inactive” (disappeared)
"active" (still affects the installation).
- resetting the fault report.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 13 -
9.10 Options
This menu allows you to adjust the settings of the following
options:
9.10.1 Languages
This menu allows you to change languages after installation.
• From the installation menu> select > options > languages
on the screen
9.10.2 Screen
This menu allows you to adjust the brightness and contrast of
the screen
• From the installation menu> select > options > screen on
the screen
9.10.3 About
This function displays the system’s software versions.
• From the installation menu> select > parameters > about
on the screen
10 Specific adjustment
10.1 Resetting the control unit
This function allows you to reset the control unit (factory
setting).
The resetting of factory settings is irreversible.
Any customised configuration of the control unit
will be lost.
• Simultaneously press the buttons for 10
seconds.
• Confirm by pressing .
11 Re-check and restart
• Once the control unit is installed, check the operation.
• Switch the control unit on to ensure that any adjustments
operate correctly and check that the appliance operates
safely.
12 User information
At the end of the installation:
- explain the operation of the equipment and its safety devices
to the user, if necessary provide a demonstration and answer
any questions;
- give the user all the required documentation,
- fill in the documents where necessary;
- advise the user of the precautions necessary to prevent
damage to the system, appliance and the building;
- remind the user to service the appliance annually.
INSTALLATION

0020094626_00 - 06/10 - Glow-worm
- 14 -
MAINTENANCE
13 Trouble-shooting
13.1 Fault diagnosis
The following checks should be performed before proceeding
onto specific diagnostics:
- Ensure that it has not been disconnected from the electricity
network and that the control unit is connected correctly.
- Ensure that all installation’s appliances are available.
- Check the functioning of external regulatory devices (room
thermostat, remote sensor,).
13.2 Maintenance menu
The maintenance menu includes the installation menu function,
plus 2 additional functions:
- "Test Menu", within the maintenance menu,
- "After sales service Info", in the options.
13.2.1 Access to the maintenance menu
• Press the “menu” button for 7 seconds.
• Enter the installer maintenance access code 35.
• Press the button to confirm.
13.2.2 Test menu
This menu allows you to test the operation of all the appliances
and the system (boiler, HP, valve,) present in the installation.
Each element can be controlled centrally by activating its
normal start-up function or by individual component.
By entering the test menu, the control unit display’s
the following message: “the system is currently
stopped" No further heating control operations
are effected. Control is resumed upon exiting the
menus.
13.2.3 After sales service info
• From the maintenance menu> select > options > After
sales service info on the screen.
This menu provides access to After sales Service information:
- date of last access to installer menus
- the name of the company which provides the after sales
service, if entered during installation.
- the telephone number of the company which provides the
after sales service , if entered during installation.
MAINTENANCE

0020094626_00 - 06/10 - Glow-worm
- 15 -
13.3 System failure codes
Faults described in this chapter should be carried
out by a qualified engineer and if needed by the
After Sales Service.
Fault
codes Description Cause Solution
001 Failure in Ebus communication between with the
boiler
The boiler is not connected to the control
unit.
The cable polarity is reversed.
The boiler is off.
Check that the boiler is connected to the
control unit.
Check the connection’s + / - polarity.
Ensure that there is no interruption to the
electricity network and that the boiler is
properly connected and turned on.
002 Failure in Ebus communication between with the
heat pump
The heat pump is not connected to the
control unit.
The heat pump is off.
Make sure the heat pump is connected to
the control unit.
Ensure that there is no interruption to the
electricity network and that the heat pump
is properly connected and turned on.
003 Failure in Ebus communication between with the
hydraulic module
The hydraulic module is not connected to
the control unit.
The hydraulic module is off.
Make sure that the hydraulic module is
connected to the control unit.
Ensure that there is no interruption to the
electricity network and that the hydraulic
module is properly connected and turned
on.
010 Heating circuit outgoing temperature sensor failure
(open circuit)
The sensor is defective or not
properly connected to the control unit
management or hydraulic module.
Check the sensor’s connections.
Verify that the position and the operation
of the sensor are correct.
Check the sensor’s resistance.
011 Heating circuit outgoing temperature sensor failure
(short circuit) The sensor is shorted.
012 Heating circuit outgoing temperature sensor failure
low temperature (open circuit)
The sensor is defective or not properly
connected to the control unit. Check the sensor’s connections.
Verify that the position and the operation
of the sensor are correct.
Check the sensor’s resistance.
013 Heating circuit outgoing temperature sensor failure
low temperature (short circuit) The sensor is shorted.
014 Domestic water tank temperature sensor failure
(open circuit)
The sensor is defective or not properly
connected to the control unit. Check the sensor’s connections.
Verify that the position and the operation
of the sensor are correct.
Check the sensor’s resistance.
015 Domestic water tank temperature sensor failure
(short circuit) The sensor is shorted.
020 Pressure sensor failure The sensor is defective or not properly
connected to the hydraulic module.
021 Pressure too low <0.5 bar There is a leak in the heating circuit.The
degassing was not carried out correctly.
Check that there are no leaks.
Drain the heating circuit. Remove air.
Fill the installation.
030 Failure in communication with the zone 1 wireless
room thermostat.
The room thermostat is too far from the
control unit.
There is a problem with the batteries in
room thermostat.
Check the RF signal quality via the
Climapro RF installer menu.
Check the location of the thermostat.
Check that the thermostat’s batteries are
installed in their compartment.
Make sure the battery polarity is not
reversed.
Make sure the batteries are not dead.
If so, replace them with new batteries
031 Failure in communication with the zone 2 wireless
room thermostat.
032 Failure in communication with the zone 3 wireless
room thermostat.
033 Failure in communication with the zone 4 wireless
room thermostat.
034 Failure in communication with the zone 5 wireless
room thermostat.
035 Failure in communication with the zone 6 wireless
room thermostat.
036 Failure in communication with the wireless
outdoor sensor
The wireless outdoor sensor is too far
from the control unit.
Check the location of the outdoor sensor.
Check that the sensor’s power supply is
correctly provided by a photovoltaic cell.
MAINTENANCE

0020094626_00 - 06/10 - Glow-worm
- 16 -
13.4 Control unit failures
Faults described in this chapter should be carried
out by a qualified engineer and if needed by the
After Sales Service..
Description Cause Solution
No display on
screen
The power
supply is faulty.
The fuse is
damaged.
Make sure that the electricity
supply has not been interrupted.
Check that 230V supply is turned
on and present.
Check the position of the control
unit switch.
Check the control unit’s fuse.
13.5 Replacing a fuse
BC
E
D
F
A
1
2
4
3
Key
1 Fuse
2 Control unit
3 Switch On (I) / Off (O)
4 Fuse holder
• Turn off the control unit (2) with the switch (3) in position (O).
• Turn off the power supply to the control unit (2) at the
isolating switch.
• Replace the fuse following the order (A) to (F).
• Slightly turn the control unit (2) fuse holder (4) using a
screwdriver.
• Remove the fuse holder (4) and the fuse (1).
• Replace the fuse (1) following the indications given in the
Technical data chapter.
• Reinsert the fuse holder (3) in the control unit (2).
• Press and turn slightly with a screwdriver.
• Turn on the power supply to the control unit (2) at the
isolating switch.
• Turn on the control unit (2) with the switch (3) in position (I).
TECHNICAL DATA
14 SYSTEMPRO
Description Unit Control unit
Transmission / reception
frequency
MHz 868
Transmission / reception
frequency with outdoor sensor
min 15
Transmission / reception
frequency with room thermostat
min 10
Average radio signal range in
open air (*)
m 100
Average radio signal range
indoors (*)
m25
Control unit dimensions:
Height mm 264
Length mm 290
Depth mm 45
(*) Depends on the installation’s conditions and the electromagnetic
environment.
Electricals
Power-supply voltage VAC/Hz 230/50
Power cable gauge mm² 3 x 0.75
EBUS connection cable gauge mm² 2 x 0.75
Current A 0.43
Delay fuse A1
Electrical protection IP20
Electrical classification II
Surge category II
Pollution rating 2
Contact outputs fed work A8
V 230
Action auto type 1.C
TECHNICAL DATA


0020094626_00 - 06/10
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
Glow-worm, Nottingham Road, Belper, Derbyshire. DE56 1JT
Other manuals for SYSTEMPRO
2
Table of contents
Other Glowworm Control Unit manuals
Popular Control Unit manuals by other brands

MSA
MSA 610A instruction manual

Advantech
Advantech USB-4716 user manual

enphase
enphase Communications Kit 2 Quick install guide

Syntron Material Handling
Syntron Material Handling PowerPulse 7200-006-A Installation operation & maintenance

Siemens
Siemens LMV3 series Technical instructions

Hopeland
Hopeland CL7206A5 user manual

Fike
Fike TWINFLEX IRM 100-0011 Engineering and Commissioning Manual

RF-Star
RF-Star RF-BM-ND04 manual

Giacomini
Giacomini R453HY011 Instruction

NeuLog
NeuLog NUL-205 quick start guide

Espressif Systems
Espressif Systems ESP32-S2-MINI-2 user manual

Telit Wireless Solutions
Telit Wireless Solutions WL865E4-P user guide