Goodwe Lynx Home FH Series User manual

V1.0-2022-10-30
Quick Installation Guide
Rechargeable Lithium Ion Battery System
(LX F9.6-30 |LX F12.8-30 |LX F16.0-30 |LX F19.2-30)
Lynx Home FH Series US

01
01 Safety Precaution
• The information in this user manual is subject to change due to product updates or other
reasons. This guide cannot replace the product labels or the safety precautions in the user
manual unless otherwise specied. All descriptions in the manual are for guidance only.
• Before installations, read through the quick installation guide. For additional information,
please see the user manual.
• All installations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
• Check the deliverables for correct model, complete contents, and intact appearance. Contact
after sales service if any damage is found or any component is missing.
• Use insulating tools and wear personal protective equipment (PPE) when operating the
equipment to ensure personal safety. Wear anti-static gloves, cloths, and wrist strips when
touching electron devices to protect the equipment from damage.
• Strictly follow the installation, operation, and conguration instructions in this guide and
relative user manual. The manufacturer shall not be liable for equipment damage or personal
injury if you do not follow the instructions. For more warranty details, please visit: https://
en.goodwe.com/warranty.
General Disclaimer
• The battery system is a high voltage system. High voltage exists when the equipment is
running. Please keep Power O before any operations to avoid danger. Strictly follow all
safety precautions outlined in this manual and safety labels on the equipment during the
operation.
• The inverter used with the battery shall be approved by the battery manufacturer. The
approved list of batteries and the matched inverter can be obtained through the ocial
website.
• Do not disassemble, modify, or replace any part of the battery or the power control unit
without ocial authorization from the manufacturer. Otherwise, it will cause electrical shock
or damages to the equipment, which shall not be borne by the manufacturer.
• Do not hit, pull, drag, squeeze or step on the equipment or put the battery into re.
Otherwise, the battery will be exploded.
• Do not place the battery in a high temperature environment. Make sure that there is no heat
source near the battery and no direct sunlight. When the ambient temperature exceeds 60 ℃,
it will cause a re.
• Do not use the battery or the power control unit if it is defective, broken, or damaged. The
damaged battery may leak electrolyte.
• To protect the battery pack and its components from damage during transportation, please
ensure that the transportation personnel are professionally trained. All operations during the
transportation have to be recorded. The equipment shall be kept in balance, thus avoiding
falling down.
• The battery equipment is heavy. Please equip the corresponding personnel according to its
weight, so that the equipment does not exceed the weight range of the human body can
carry, and smash the personnel.
• Contact after-sale service immediately if the battery is not able to be started. Otherwise, the
battery might be damaged permanently.
• Do not move the battery system if it is connected with external battery modules. Contact
after-sale service if the battery shall be replaced or added.
Safety Disclaimer
Instructions during Installation

02
Label Description
Fire
• The battery may explode when the ambient temperature exceeds 150℃. Poisonous and
hazardous gas may be released if the battery is on re.
• In the event of a re, please make sure that the carbon dioxide extinguisher or Novac1230 or
FM-200 is nearby.
• The re cannot be put out by water or ABC dry powder extinguisher. Fireghters are required
to wear full protective clothing and self-contained breathing apparatus.
If the battery module leaks electrolyte, avoid contact with the leaking liquid or gas. The
electrolyte is corrosive. It will cause skin irritation or chemical burn to the operator. Anyone
contacts the leaked substance accidentally has to do as following:
• Breath in the leaked substance: Evacuate from the polluted area, and seek immediate
medical assistance.
• Eye contact: Rinse your eyes for at least 15 minutes with clean water and seek immediate
medical assistance.
• Skin contact: Thoroughly wash the touch area with soap and clean water, and seek
immediate medical assistance.
• Ingestion: Induce vomiting, and seek immediate medical assistance.
Battery Electrolyte Leakage
Emergency Measures
Potential risks exist. Wear proper
personnel protective equipment
before any operations.
Install the equipment away from
re sources.
HIGH VOLTAGE HAZARD High
voltage exists during the
equipment’s running.
Ensure the equipment is power o
before any operations.
Keep the equipment away from
children.
Operate the equipment properly to
avoid explosion danger.
It is forbidden to dismantle the
equipment personally.
The equipment contains corrosive
electrolytes. In case of a leak in
the equipment, avoid contact the
leaked liquid or gas.
Do not short-circuit the positive
and negative pole of the
equipment. Otherwise it may
cause damage to the cables.
Batteries contain ammable
materials, beware of re. Grounding point.
Read through the user manual
before any operations.
SGS marking for United States
and Canada

03
Check Before Power ON
No. Check Item
1The battery is rmly installed in a clean place where is well-ventilated and easy to
operate.
2The PE cable, power cable, communication cable, and the terminal resistors are
connected correctly and securely.
3 Cable ties are intact, routed properly and evenly.
4 Unused ports and terminals are sealed.

04
Parts Introduction (PCU)
Right View Left View
Front View
02 Product Introduction
Parts Introduction (Battery) Parts Introduction (Battery Base)
1. Ventilation Valve 2. Cable Hole 3. Circuit Breaker
4. SOC Indicator 5. Button Indicator 6. Rectangular Connector
1. Limiting hole 2. positioning pin 3. Rectangular Connector
4. Adjustable feet installing
hole

05
1. Ventilation Valve 2. Cable Hole 3. Circuit Breaker
4. SOC Indicator 5. Button Indicator 6. Rectangular Connector
Dimensions
x 1
x 1
x 2 x 2
x 4
x 1 x 1 x 6 x 1
x 1x 6
x 4
x 2
03 Battery System Installation
Deliverables (PCU)

06
x 1 x 2
Deliverables (Battery Module)
Space Requirements
Keep the
equipment away
from children.

07
Angle Requirements
Battery Quantity Requirements
Battery 1 Battery 1 Battery 1
Battery 2 Battery 2
Battery 3
Battery 2
Battery 3
Battery 4
Battery N
3≤N≤6
PCU
PCU
PCU

08
Installation Requirement For Locking Bracket
Battery System Installation

09

10

11
Wiring Diagram for parallized battery systems
Terminal
resistor
Terminal resistor
Battery System 1
Battery System 2
Battery System N
04 Electrical Connection
Ground Cable
Communication
Cable
Power Cable for
Negative Pole
Power Cable for
Positive Pole
2≤N≤8
Terminal
resistor

12
No. Terminal/Port Silkscreen Recommended Cable Specications
1 Grounding Point 105℃ (221°F) copper cables, 10AWG.
2DC Terminal (BAT) 105℃ (221°F) copper cables, 8AWG.
3Communication
Terminal
COM1
-COM2
COM3
Top View
Installing the wiring conduit
Cable Specications

13
Connecting the PE cable
Cooper,
Connecting the Power cable
Cooper,

14
Connecting the Communication Cable
PIN COM1 COM2 COM3 Description
1CAN3H CAN3H CAN3H BMS communication for battery
system parallel connection
2CAN3L CAN3L CAN3L
3N/A N/A N/A Reserved
4CAN2H N/A N/A COM1: connects to the inverter
BMS communication port to
communication with the inverter
COM2, COM3: reserved
5CAN2L N/A N/A
6ISO_GND ISO_GND N/A PIN for grounding.
7HVIL_IN HVIL_IN N/A COM1, COM2: interlock function
COM3: reserved
8 HVIL_OUT HVIL_OUT N/A

15
Installing the terminal resistor
Installing the protection cover

16
05 Power ON and OFF
Power ON Power OFF
Turn on Turn o
Inverter Battery System
DC Breaker
(Optional)
Single battery system
NOTICE
Turn on the inverter in the system following the instructions in the user manual of the inverter.
Power ON Power OFF
Turn on Turn o
Inverter
Battery
System1
Battery
System2
Battery
System≤8
DC Breaker
(Optional) DC Breaker
(Optional)
Parallized battery systems
2≤N≤8

17
WiFi/LAN/4G
Commissioning via PV Master APP
06 Commissioning
Monitoring via SEMS Portal APP
SEMS Portal
PV Master
User Manual SEMS Portal User
Manual
For more information, please scan the following QR for User Manual.
Lynx Home FH Series
US User Manual

GoodWe Technologies Co., Ltd.
No. 90 Zijin Rd., New District, Suzhou, 215011, China
www.goodwe.com
Ocial Website
Local Contacts340-00856-01
This manual suits for next models
4
Table of contents
Other Goodwe Batteries Pack manuals