Greengate OAWC-P-120W User manual

Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
24’
(7.3 mm)
Minor Motion, IR
Major Motion, IR
20’
(6 mm)
8’
(2.4 mm)
8’
(2.4 mm)
24’
(7.3 mm)
20’
(6 mm)
0
10 ft
(3 mm)
12’
(3.7)
12’
(3.7)
6 ft
(1.7 mm)
15 ft
(4.6 mm)
24 ft
(7.3 mm)
50 ft
(15.3 mm)
Model # OAWC-P-120W
Model # OAWC-P-120W-R
Passive Infared Wall/Corner Mounted Low
Voltage Occupancy Sensor
• Readallinstructionsonbothsidesofthissheetrst
• Planallcomponentlocationscarefully
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
• ForUsewithGreengateSwitchpacks&SystemsOnly
• DonotrunanyGreengateLowVoltageWiringinthe
sameconduitaspowerconductors
General Information
Technology:PassiveInfrared(PIR)
Power Requirements:
Input:
• 10-30VDCfromGreengateSwitchpackorGreengate
system.Maximumcurrentneededis25mApersensor
Output:
• OpencollectoroutputtoswitchuptotenGreengate
Switchpacks.BASwithIsolatedFormCRelay(-Rmodel)
IsolatedFormCRelayRatings:1A30VDC/VAC
Time Delays:Self-Adjusting,15seconds/test(10minAuto),
orSelectable5,15,30minutes
Coverage:1200sq.ft.
Light Level Sensing:0to300foot-candles(-Rmodel)
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Housing:
• Mediumimpactinjectionmoldedhousing
PolycarbonateresincomplieswithUL94V0
Size:4.4"x3.4"x2"(112mmx86.4mmx50.8mm)
LED Indicators:RedindicatesPIRdetection
Specifications
Description
TheOAWC-PWall/CornerMountLowVoltageOccupancySensorisaPassiveInfrared(PIR)motion sensinglightingcontrol,used
forenergysavingsandconvenience.Whenmotionisdetected,thebluewireiselectronicallyconnectedtotheredwire,energizing
therelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,thebluewireisdisconnectedfromthered,causingtherelay
toopenturningOFFtheload.Theredleadis10to30VDCsupply,theblackleadiscommonandtheblueistherelaycontrol.
PIR Technology
Thesensor’ssegmentedlensdividestheeldofviewintosensorzonesanddetectsthechangesintemperaturethatarecreated
whenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtimedelayinreal-
time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergysavingsthatareavailablein
theparticularapplication.
TheDaylightingfeature(-Rmodelonly)preventslightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.Thesensor
willswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetectmotion30seconds
following theinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
InAutomaticOnMode,thelightsturnONwhenapersonenterstheroom.InManualONMode,thelightsareturnedONby
activatingamomentaryswitch(model#GMDS-*)thatisconnectedtothesensor.Whenusedwith2levellighting(-Rmodelonly),
bi-levelAutomaticONcanbeachievedwhichallowsZone1tocomeONautomaticallyuponoccupancy.Zone2doesnotcomeON
unlesstheoccupantpressestheoptionalmomentaryswitch.
Location
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthe
presenceofobstacles.Followthecoveragediagramconcerningmajorandminormotion
coverage.Thesensormusthaveaclearviewoftheareatobecontrolled.Thesensorwill
not“see”throughglass.Mountingheightshouldnotexceed12feet.Optimummounting
heightis10feet.Mountthesensorsothedevicefacestheopenportionoftheroom and
arefacinganearbywall,do or,window,orotherobstructingobject.Avoidpointinginto
hallways.Topreventfalseactivation,thesensorshouldbemountedawayfromtheair
supplyductaminimumof4to6feet.Mountingatxtureheightismosteffective.For
typicalplacementrefertoLocationDiagram.
Installation
TheOAWC-P-120Wcanbemountedtothewall,ceiling,junctionboxorroundxturewithraceway. Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the
branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a
fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with
the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by
frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2. Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsforall
connections)CAPALLUNUSEDWIRELEADS.
3. Mountunittowall,ceiling,junctionbox,orroundxturewithraceway.
4. TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5. Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
Occupancy Sensor Mounted to Wallboard
Occupancy Sensor Mounted to Round Fixture with Raceway
Occupancy Sensor Mounted to Octagon Box
Occupancy Sensor Mounted to Drop Ceiling
Location Diagram
Coverage
Occupancy Sensor Mounted to Octagon Box with Mud Ring
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30 VDC)
Blue (Control)
Yellow (Control)
Brown (Switch-Blue Lead Control)
Brown/White (Switch-Yellow Lead Control)
Sensor’s Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally closed)
Yellow
Blue
Red
Black
Recommended Wire: 18-3 AWG stranded non-shielded
Brown/White
Brown
Gray
Purple
Orange
Optional Greengate GMDS Switch-
Blue Control Lead-Manual ON/OFF
To Additional Sensors.
Maximum of 5 sensors
per switchpack.
Switchpack
Blue
Load 1
White
**Hot
Blue
Hot
Neutral
Line
**Use Black Lead for 120 VAC
Use Orange Lead for 277 VAC
Cap Unused Lead
Black (Common)
Red (15 VDC)
Blue (Control)
One Sensor, One Switchpack
P/N 9850-000140-01

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Warranties and Limitation of Liability
DIP Switch Settings
Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Checkout and Adjustment
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
WallswitchOFF TurnwallswitchON
Iflowvoltageswitchoptionisused,lights
mayhavebeenturned-offmanually Presslow-voltageswitch
DaylightingFeatureEnabled IfalllightsarerequiredtoturnONadjustDIP
Switch10and/ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
Lights
Will Not
Turn ON
manually
DaylightingFeatureEnabled IfalllightsarerequiredadjustDIP
Switch10and/ordaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
Sensorinstalledclosetoanairvent Sensorsshouldbeinstalled4-6feetaway
fromanyairventandoutofheavyairow
Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
PIRactivatedbyheatsourceotherthanoccupant MoveDIPSwitch5UP
Bypass Checkwiringtomakesuresensor
orswitchpackarenotbypassed
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandPIRsensitivity.Inpreparationforthe
InstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the
unitwilltime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconrmedbywatching
theRed(PIR)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONforonesecondwitheachmotion.(IfLEDs
donotturnON,gotoInstallerAdjustments-SensitivityAdjustmentsSection)
2.Standstillsixtoeightfeetawayfromthesensorforveseconds.LEDsshouldnotturnON.(IfanyLEDturns
ON,noteLEDandgotoInstallerAdjustments–SensitivityAdjustmentsection)
3.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
5.TheunitwillremaininTestModefor5 minutesthenautomaticallyexitTestModeandgofor10min.Time
DelayUserModesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To
forceinto10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrent
position,wait3seconds,andthenbacktoitsoriginalposition)WhileinTes tMode,theLEDswillashonceper1/4second.
Installer Adjustments
Sensitivity Adjustments
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2.IftheRedLEDdoesnotturnON,checkforanyobstructions.
3.Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4.IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPSwitch5U P.
Hot
Neutral
Line
Load 1
Black
Red
Blue
Purple
Gray
Orange
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Hot
Neutral
Line
Load 2
Switchpack
Blue
Blue
**Hot
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Yellow
Brown
Brown/White
Optional Greengate GMDS Switch-
Blue Control Lead- Manual on/off
Red (15VDC)
Black(Common)
Blue (Control)
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30VDC)
Blue (Control)
Yellow (Control)
Brown (Switch-Blue Lead Control)
Brown/White(Switch-Yellow Lead Control)
Sensor's Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally Closed)
Red (15VDC)
Black(Common)
Blue (Control)
To Additional Switchpacks
10 switchpacks Maximum
Activation Activation PIR Sensitivity Daylighting Mode
Lighting SweepOverride
LEDs
10
9
8
7
50%
54
5 Minutes
15 Minutes
30 Minutes
Auto
Auto
Manual
Manual
DIP Switch
3
2
Power Pack One Power Pack Two
(-R model only)
(-R model only)
Full Disable
Disable
Disable
Enable
Enable
Enable
Auto*
*Self-Adjusts to
10 min. user mode
Default =
Time Delay
1
Disable
Enable
6
Walk-Through Mode
Half
Full
12345678910
One Sensor, Multiple Switchpacks Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPSwitch5up.
Daylight Adjustments
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyCW).
TheDaylightingfeature(-Rmodelonly)preventsthelightsfromturningONwhentheroomisadequatelyilluminated
bynaturallight.Ifthereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthere
isnotenoughlightintheroom,thesensorwillallowthelightstoturnONwhenoccupied.
Full and Half Logic Modes(SeeDIPSwitchlegend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancy
activation,shouldtheambientlightlevelexceedthepresetfoot-candlelevel.
After activation:
FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtothe
yellowcontrolleadwillturnO F F.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,after
occupancyactivation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturn
thelightsOFFwhileoccupancyisbeingdetected.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoarticiallightisneeded.Inorderforthis
featuretofunction,theyellowcontrolleadmustbewired.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrent
position,wait3secondsandthenbackintoitsoriginalposition.
2.SetDIPSwitch10toFullorHalfLogicMode.
3.Setthelightleveltominimum(fullyCCW).
4.Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainO F F.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
incrementsuntilthelightsareON.(Pause5secondsbetweeneachadjustment)
6.OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethe
currentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10
minutes.AslongasAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,
byalternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbe
noneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2are
alreadydown,toggleDIPSwitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Automatic Mode
InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltage
switchesareusedalongwithAutomaticONMode,activatingtheswitch(es)whiletheloadisONturnstheloadO F F.
WhentheloadisturnedOFFmanually,aslongasthesensorcontinuestodetectoccupancytheloadsstayO F F. After
thetimedelayexpires,thelightsstayOFFandthesensorgoesbacktoAutomaticONMode.Forwiringinformationfor
theoptionalmomentarylowvoltageswitch(es),pleaseseethewiringsectionoftheinstallationinstructions.
Manual Mode
InManualONMode,theoptionalmomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivated
thesensorwillmaintainthelightsONuntilmotionceasesandthetimedelayexpires.Whiletheroomisoccupiedthe
BASrelayremainsactive.Afterthetimedelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)
mustbeusedtoturntheload(s)ONunlessthereismotiondetectedwithinthe10secondre-triggerperiod.
Lighting Sweep Option
Ifselected,thisDIPSwitchoptionforcesaninitial60seconddelayupon“power-up”topreventfalseactivationin
buildingswithcomputercontrolsystems.
1. MoveDIPSwitch9U P.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPSwitch8U P.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).
This manual suits for next models
1
Table of contents
Other Greengate Accessories manuals
Popular Accessories manuals by other brands

seeed studio
seeed studio Fall Detection Module Pro user manual

woodmizer
woodmizer PD200 Series Safety, Operation, Maintenance & Parts Manual

Intelligent Lighting Controls, Inc.
Intelligent Lighting Controls, Inc. WIDEVIEW manual

V-tech
V-tech VC7151-302A user manual

Sleep Sense
Sleep Sense Reusable Flow Sensors user manual

Heath Zenith
Heath Zenith Wireless Chime TR-0095-RX owner's manual