Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
24’
(7.3 mm)
Minor Motion, IR
Major Motion, IR
20’
(6 mm)
8’
(2.4 mm)
8’
(2.4 mm)
24’
(7.3 mm)
20’
(6 mm)
0
10 ft
(3 mm)
12’
(3.7)
12’
(3.7)
6 ft
(1.7 mm)
15 ft
(4.6 mm)
24 ft
(7.3 mm)
50 ft
(15.3 mm)
Model # OAWC-P-120W
Model # OAWC-P-120W-R
Passive Infared Wall/Corner Mounted Low
Voltage Occupancy Sensor
• Readallinstructionsonbothsidesofthissheetrst
• Planallcomponentlocationscarefully
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
• ForUsewithGreengateSwitchpacks&SystemsOnly
• DonotrunanyGreengateLowVoltageWiringinthe
sameconduitaspowerconductors
General Information
Technology:PassiveInfrared(PIR)
Power Requirements:
Input:
• 10-30VDCfromGreengateSwitchpackorGreengate
system.Maximumcurrentneededis25mApersensor
Output:
• OpencollectoroutputtoswitchuptotenGreengate
Switchpacks.BASwithIsolatedFormCRelay(-Rmodel)
IsolatedFormCRelayRatings:1A30VDC/VAC
Time Delays:Self-Adjusting,15seconds/test(10minAuto),
orSelectable5,15,30minutes
Coverage:1200sq.ft.
Light Level Sensing:0to300foot-candles(-Rmodel)
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Housing:
• Mediumimpactinjectionmoldedhousing
PolycarbonateresincomplieswithUL94V0
Size:4.4"x3.4"x2"(112mmx86.4mmx50.8mm)
LED Indicators:RedindicatesPIRdetection
Specifications
Description
TheOAWC-PWall/CornerMountLowVoltageOccupancySensorisaPassiveInfrared(PIR)motion sensinglightingcontrol,used
forenergysavingsandconvenience.Whenmotionisdetected,thebluewireiselectronicallyconnectedtotheredwire,energizing
therelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,thebluewireisdisconnectedfromthered,causingtherelay
toopenturningOFFtheload.Theredleadis10to30VDCsupply,theblackleadiscommonandtheblueistherelaycontrol.
PIR Technology
Thesensor’ssegmentedlensdividestheeldofviewintosensorzonesanddetectsthechangesintemperaturethatarecreated
whenaperson,orpartofapersonassmallasahand,passesintooroutofasensorzone.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtimedelayinreal-
time.Byadjustingsensitivityandtimedelayautomatically,thesensorismaximizingthepotentialenergysavingsthatareavailablein
theparticularapplication.
TheDaylightingfeature(-Rmodelonly)preventslightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONafteramomentaryoccupancy.Thesensor
willswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetectmotion30seconds
following theinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
InAutomaticOnMode,thelightsturnONwhenapersonenterstheroom.InManualONMode,thelightsareturnedONby
activatingamomentaryswitch(model#GMDS-*)thatisconnectedtothesensor.Whenusedwith2levellighting(-Rmodelonly),
bi-levelAutomaticONcanbeachievedwhichallowsZone1tocomeONautomaticallyuponoccupancy.Zone2doesnotcomeON
unlesstheoccupantpressestheoptionalmomentaryswitch.
Location
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthe
presenceofobstacles.Followthecoveragediagramconcerningmajorandminormotion
coverage.Thesensormusthaveaclearviewoftheareatobecontrolled.Thesensorwill
not“see”throughglass.Mountingheightshouldnotexceed12feet.Optimummounting
heightis10feet.Mountthesensorsothedevicefacestheopenportionoftheroom and
arefacinganearbywall,do or,window,orotherobstructingobject.Avoidpointinginto
hallways.Topreventfalseactivation,thesensorshouldbemountedawayfromtheair
supplyductaminimumof4to6feet.Mountingatxtureheightismosteffective.For
typicalplacementrefertoLocationDiagram.
Installation
TheOAWC-P-120Wcanbemountedtothewall,ceiling,junctionboxorroundxturewithraceway. Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the
branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a
fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance with
the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by
frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2. Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsforall
connections)CAPALLUNUSEDWIRELEADS.
3. Mountunittowall,ceiling,junctionbox,orroundxturewithraceway.
4. TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5. Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
Occupancy Sensor Mounted to Wallboard
Occupancy Sensor Mounted to Round Fixture with Raceway
Occupancy Sensor Mounted to Octagon Box
Occupancy Sensor Mounted to Drop Ceiling
Location Diagram
Coverage
Occupancy Sensor Mounted to Octagon Box with Mud Ring
SENSOR WIRE LEAD LEGEND
Black (Common)
Red (10-30 VDC)
Blue (Control)
Yellow (Control)
Brown (Switch-Blue Lead Control)
Brown/White (Switch-Yellow Lead Control)
Sensor’s Isolated Relay
Orange (Normally Open)
Gray (Common)
Purple (Normally closed)
Yellow
Blue
Red
Black
Recommended Wire: 18-3 AWG stranded non-shielded
Brown/White
Brown
Gray
Purple
Orange
Optional Greengate GMDS Switch-
Blue Control Lead-Manual ON/OFF
To Additional Sensors.
Maximum of 5 sensors
per switchpack.
Switchpack
Blue
Load 1
White
**Hot
Blue
Hot
Neutral
Line
**Use Black Lead for 120 VAC
Use Orange Lead for 277 VAC
Cap Unused Lead
Black (Common)
Red (15 VDC)
Blue (Control)
One Sensor, One Switchpack
P/N 9850-000140-01