manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Greengate
  6. •
  7. Accessories
  8. •
  9. Greengate OAC-U-2000-MV User manual

Greengate OAC-U-2000-MV User manual

Installation Instructions
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Coverage
Model # OAC-U-2000-MV
Model # OAC-U-2000-DMV
Ultrasonic Ceiling Mounted Line
Voltage Occupancy Sensor
• Readallinstructionsonbothsidesofthis
sheetrst
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
General Information
Power Requirements:
120to347VAC,50/60Hz-NeutralRequired
120VAC:
• Incandescent/Tungsten-0to800W,50/60Hz
• Fluorescent/Ballast-0to1200W,50/60Hz
MotorLoad:¼HP@125VAC
230VAC:
• Fluorescent/Ballast-0to1200W,50/60Hz
277VAC:
• Fluorescent/Ballast-0to2700W,50/60Hz
347VAC:
• Fluorescent/Ballast-0to1500W,50/60Hz
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Specifications
Description
Ultrasonic
Activated
TheOAC-UCeilingMountLineVoltageOccupancySensorisanUltrasonic(US)motionsensinglightingcontrol,
usedforenergysavingsandconvenience.Thesensorproducesalowintensity,inaudiblesoundtodetectoccupancy
inaroom.Changesinthesensor’sacousticwavecausedbymotion,suchaswalkingintheroom,reachingfora
telephoneorswivelinginachair,willcausethelightstoturnON.Thesensordoesnotrespondtoaudiblesound.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityand
timedelayinreal-time.
Location
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeandthepresenceofobstacles.Decrease
totalcoverageareaby15%for“soft”rooms(forexample,heavydraperiesorheavycarpeting).Thesensormusthavea
clearviewoftheareatobecontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnotexceed12
feet.Optimummountingheightis8to10feet.Mountthesensorsothegrillesfacetheopenportionoftheroomand
arenotfacinganearbywall,door,windoworotherobstructingobject.Avoidpointingintohallways.Mountingatxture
heightismosteffective.*Topreventfalseactivation,thesensorshouldbemountedawayfromtheairsupplyducta
minimumof4to6feet.
Installation
TheOAC-Usensorcanbemountedtoastandard2.125"deepx4"octagonor2.125"deepx4"foursquareelectrical
box(foursquareboxrequiresatwo-gangmudring).
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be
turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker
is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked
“SWD”. All installations should be in compliance with the National Electric Code and all state and
local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2.Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsfor
allconnections)CAPALLUNUSEDWIRELEADS.
3.Mountunittoceiling,junctionboxorroundxturewithraceway.
4.TurnpowerbackONatthebranchcircuitbreakerandwait2minutesfortheunittostabilize.
5.Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
0
12 ft
(3.65 m)
16 ft
(4.87 m)
12 ft
(3.65 m)
16 ft
(4.87 m)
20 ft
(6.096m)
20 ft
(6.096m) 23 ft
(7.01 m)
5 ft
(1.52 m)
5 ft
(1.52 m)
32 ft
(9.75 m)
32 ft
(9.75 m)
15 ft
(4.57 m)
23 ft
(7.01 m)
15 ft
(4.57 m)
10 ft
(3 m)
10 ft
(3 m)
0
OAC-U-2000 Coverage Diagram
Load 1
Neutral
120-347 VAC
Line
Blue
White
Black
Red
Red
Load 2
Red leads are non-polorarity sensitive.
Manual or Automatic-On Control of Two Standard Switchpacks
Load 1
Neutral
120-347 VAC
Line
White
Blue
Black
One Sensor, One Switchpack
30 ft
9.14 m
30 ft
9.14 m
OAC-U-2000
P/N 9850-000183-02
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Warranties and Limitation of Liability
DIP Switch Settings Troubleshooting
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.ThisappliestotimedelayandUSsensitivity.Inpreparationforthe
InstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,the
unitwilltime-out15secondsafterthelastmotiondetected.Coverageandsensitivitycanbeconrmedbywatching
theGreen(US)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONfor¼secondwitheachmotion.(IfLEDs
donotturnON,gotoInstallerAdjustments-SensitivityAdjustmentssection)
2.Standstillsixtoeightfeetawayfromthesensorforveseconds.LEDsshouldnotturnON.(IfanyLEDturns
ON,noteLEDandgotoInstallerAdjustments–SensitivityAdjustmentsection)
3.Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
Adjustmentssection)
4.Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingsection)
5.TheunitwillremaininTestModefor10minutesthenautomaticallyexitTestModeandgointothe10minute
TimeDelayUserModesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.To
forceinto10min.UserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofits
currentposition,wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillashonceper1/4second.
Installer Adjustments
34
Not UsedOverride
LEDs
(DMV model only) (DMV model only)
Daylighting Bathroom Mode Relay Swap
Pot 1 - Blue (0-300 FC)
Ultrasonic
(-R model only)
Pot 2 - Green
Not UsedNot Used
Relay 2
Relay 1 & 2
(DMV model only)
LED Indicators Functionality
During Installer/Test Mode While in User Mode
LED Flashing Speed LEDswillashonceper¼second LEDswillashoncepersecond
Duration 10minutes 10to30minutes
1234567891011 12
ON
Daylight Sensor Adjustment
Ultrasonic Sensitivity Adjustment
Issue Possible Causes Suggestions
Lights
Will Not
Turn ON
automatically
DaylightingFeatureEnabled IfalllightsarerequiredtoturnON
adjustdaylightpotentiometer
Powerinterruption Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Lights
Will Not
Turn OFF
automatically
Override MakesuresensorisnotinOverrideMode(DIPSwitch8up)
Sensorinstalledclosetoanairvent Sensorsshouldbeinstalledminimum4-6feetaway
fromanyairventandoutofpathofheavyairow
Sensorinstalledclosetoindirectlighting Sensorsshouldbemountedawayfromindirectlighting
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
UltrasonicSensitivitysetHigh Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Sensitivity Adjustments
Ultrasonic Sensitivity (GreenLED)-Usingasmallatheadscrewdriverturnthegreenpotentiometersothatthe
arrowpointsup.
1. Standindifferentareasoftheroomandwaveyourhands.
2.IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwisein
smallincrements.RepeatStep1.
3.Standstillsixtoeightfeetawayfromsensorforveseconds.LEDshouldnotturnON.
4.IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasetheUSsensitivitybyturningtheGreen
potentiometercounter-clock-wiseinsmalldecrements.RepeatStep3.
Field-of-view outside the space
AdjustUltrasonicsensitivity.
Daylight Adjustments (0 to 300 foot-candles)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.If
thereisenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOF F.Ifthereisnotenoughlight
intheroom,thesensorwillallowthelightstoturnONwhenoccupied.HoweverthelightswillnotturnOFFifthelight
levelgoesabovethepresetvalueaspertheDaylightpotentiometer.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoarticiallightisneeded.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPSwitch10outofitscurrent
position,wait3secondsandthenbackintoitsoriginalposition.
2.SetDIPSwitch10toRelayTwoonlyorRelayOneandTwo.
3.Setthelightleveltominimum(fullyCCW).
4.Leavetheroomandletthesensortime-outsolightsareO F F.EnterthespaceandlightsshouldremainOFF.
5.MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmall
incrementsuntilthelightsareON.(Pause5secondsbetweeneachadjustment)
6.OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethe
currentillumination.
Time Delay Adjustments
Peoplewhoremainverystillforlongperiodsoftimemayneedalongertimedelaythanthedefaultsettingof10
minutes.AslongasAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,
byalternatelymakingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbe
noneedformanualadjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPSwitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPSwitches1and2down.(IfDIPSwitches1and2are
alreadydown,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Automatic Mode
InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltage
switchesareusedalongwithAutomaticONMode,activatingtheswitch(es)whiletheloadisONturnstheloadO F F.
WhentheloadisturnedOFFmanually,aslongasthesensorcontinuestodetectoccupancy,theloadsstayOF F.After
thetimedelayexpires,thelightsstayOFFandthesensorgoesbacktoAutomaticONMode.Forwiringinformationfor
theoptionalmomentarylowvoltageswitch(es),pleaseseethewiringsectionoftheinstallationinstructions.
Bathroom Mode (OAC-U-200-DMV Model Only)
Whenselected,BathroomModekeepsthesecondrelayONforanadditional10minutesaftertherstrelayhasbeen
turnedOF F.
Relay Swap (OAC-U-200-DMV Model Only)
Acommonprobleminelectricwiringiswiringthewrongwiretothewrongload.Thiscanmakecontrolofloads
confusingtoanenduser.TheRelaySwapoptionsolvestheproblembyswappingtherelaysaftertheunitiswired
andinstalled.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPSwitch8up.
Checkout and Adjustment

This manual suits for next models

1

Other Greengate Accessories manuals

Greengate PPS-4 Assembly instructions

Greengate

Greengate PPS-4 Assembly instructions

Greengate OAWC-P-120W User manual

Greengate

Greengate OAWC-P-120W User manual

Greengate OAC-DT-2000-MV User manual

Greengate

Greengate OAC-DT-2000-MV User manual

Greengate ONW-P-1001-MV-W User manual

Greengate

Greengate ONW-P-1001-MV-W User manual

Greengate OAC-DT-0501 User manual

Greengate

Greengate OAC-DT-0501 User manual

Popular Accessories manuals by other brands

Quincy lab 140AE-1 operating manual

Quincy lab

Quincy lab 140AE-1 operating manual

HomePro ZIR000 user manual

HomePro

HomePro ZIR000 user manual

DOL 20SCR Technical user guide

DOL

DOL 20SCR Technical user guide

RAB Smart Task installation manual

RAB

RAB Smart Task installation manual

Kemppi KMS 300 quick guide

Kemppi

Kemppi KMS 300 quick guide

Stearns 57,500 Series Installation and service instructions

Stearns

Stearns 57,500 Series Installation and service instructions

iGuzzini TWILIGHT COPENAGHEN manual

iGuzzini

iGuzzini TWILIGHT COPENAGHEN manual

Adelaide Annexe & Canvas Avan Deluxe installation guide

Adelaide Annexe & Canvas

Adelaide Annexe & Canvas Avan Deluxe installation guide

OHAUS 5000 instruction manual

OHAUS

OHAUS 5000 instruction manual

HOME8 WLS1300 quick start guide

HOME8

HOME8 WLS1300 quick start guide

MAXBOTIX MaxSonar quick start guide

MAXBOTIX

MAXBOTIX MaxSonar quick start guide

ioSmart iSmart56 Installation and user guide

ioSmart

ioSmart iSmart56 Installation and user guide

Focusrite Scarlett 18i8 user guide

Focusrite

Focusrite Scarlett 18i8 user guide

Velleman ED38105 user manual

Velleman

Velleman ED38105 user manual

JumpSport SkyBounce user manual

JumpSport

JumpSport SkyBounce user manual

Prima-Temp PRIYA Instructions for use

Prima-Temp

Prima-Temp PRIYA Instructions for use

Tefcold BC85I-BC85I W user manual

Tefcold

Tefcold BC85I-BC85I W user manual

Vaisala WMS302 user guide

Vaisala

Vaisala WMS302 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.