Installation Instructions
Digital Wall Switch Timer
120/277 VAC
• Readallinstructionsonbothsidesofthis
sheetrst
• Planallcomponentlocationscarefully
• Installinaccordancewithalllocalcodes
• Forusewith120VACor277VAConly
• Notforusewheretemperaturesfallbelow60°For
exceed90°F
• Forindooruseonly
Electrical Ratings:
120VAC:
• Tungsten–Max.load:
10amps,960W,+/-10%60Hz
• Ballast–Max.load:
10amps,1200W,+/-10%60Hz
• MotorLoad:¼HP@120VAC
277VAC:
• Ballast–Max.load:
10amps,1200W,+/-10%60Hz
No Minimum Load Requirement
Operating Environment:
• Temperature:60°F–80°F(15°C–26°C)
• RelativeHumidity:Lessthan90%non-condensing
• Forindooruseonly
Size:
• MountingPlateDimensions:
4.15"Hx1.94"W(105.41mmx49.28mm)
• ProductHousingDimensions:
2.73"Hx1.8"Wx1.8"D
(69.34mmx45.72mmx45.72mm)
Thesolidstateintervaltimerisdesignedtocontrollightingandmotorloads.Momentarilypressingthestart/stop
buttonlocatedonthefrontoftheunitwillturntheloadONandstartthecount-downtime(setbytheuserutilizingthe
DIPSwitches)attheendofwhichtheloadwillturnOFF.IfthereisaneedtoturntheloadOFFbeforethecount-down
timehasexpired,presstheSTART/STOPbuttonmomentarily.TheunitcanbeprogrammedviaDIPswitchsettingsto
flickertheload(lights),and/orbeepasawarningindicatingthattheloadisabouttoturnOFF.Ascrolloptioncanbe
settotemporarilychangethepresetcount-downtimebypressingandholdingdownthestart/stopbuttonformore
than3seconds.
P/N 9850-000414-00
Description
Specifications
General Information
Model # TSW-MV-W
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned
OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the
main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations
should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is
shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the
effects of cycling.
Wiring
• LCDdisplaythatstandsoutstronglyinlightedareasandisbacklitforvisibilityindarkareas
• Tamperresistanttime-oninterval,whichcanbepreset.Inaddition,amanualscroll-upmodethatcanoverridethe
settingtemporarily–thisfeaturecanbedisabled,therebyprovidingaxedintervaltimer
• Flickeroflightsand/orbeepwarning,whichbegins2minutesbeforetime-out(eitherorbothcanbedisabled)
• Zeropowerswitchingtoprolongthelifeofrelaycontactsbyswitchinghighinrushequipmentatorcloseto
zeropower
• Incandescentlighting,ormotorloads,compatiblewithelectronicballasts
• Decoratortypefacewithmatchingwallplateincluded
Features
CAUTION: Before wiring and servicing, power to this time switch and the equipment in controls must be turned
OFF at the main panel.
WARNING: Unit must be properly grounded to operate correctly.
1. Connectthewiresasshowninthesinglepolewiringdiagram.
2. Captheunusedgroundwire.
3. Mountthetimerinsidetheelectricalboxusingthe2mountingscrewsprovided.
4. Installtheenclosedcoverplate.
5. TurnthepowerONattheelectricalpanel.
6. Whenpoweringupforthefirsttime,allow1minutefortheunittoshowOFFonthescreen.AnLCD“OFF”message
willbedisplayedasadefaultandtheloadwillbeswitchedOFF.
Installation
Wiring Diagram 1: Single Pole Wiring
Wiring Diagram 1: Three-Way Wiring
Contact Ratings:
TYPE OF LOAD 120 VAC 277 VAC
Resistive 15A 15A
Ballast 10A 10A
LEDDriver 1200W 1200W
Tungsten 960W -
Motor 1/4HP -
PilotDuty 360VA -

Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
Printed in Malaysia
Settings
• Thetamperresistanttime-onintervalcanbepreset.Inaddition,amanualscroll-upmodecanoverridethe
settingtemporarily–thisfeaturecanbedisabled,therebyprovidingafixedintervaltimer.
• Aflickerofthelightsand/orabeepwarningbegins2minutesbeforetime-out(eitherorbothcanbedisabled).
TheTSW-MVisfactorypresettomeetnewerenergycodeoverridemandates.Noadjustmentisrequired.This
settingwillprovideatwohourmaximumoperatingtimebeforeshut-off.Thescrollfeatureisactivetoallowtheuser
tochangetheoperatingtimewiththemaximumtimesettingattwohours.
Closethetimerdoorandtheunitisready.OnepressofthebottomcoverturnstheloadON.TheloadwillstayON
untilacount-downtothepresetOFFtime.PressingthebottomcoveragainwillturnloadOFF.
SET FOR:
1. 4HR:SetONforpreset4hourmaximum
countdownwhen2HRissettoOFF.(Also
usedincustomtimeprogramming.)
2. 2HR:SetONforpreset2hourmaximum
countdownwhen4HRissettoOFF.(Also
usedincustomtimeprogramming.)
3. LIMIT:Usedwithprogrammingsequence.
SwitchfromONtoOFFtolimitscrollto
matchcustomtime.
4. SCROLL:SetONallowingthetimertoscroll
toashorterruntime.SetOFFtodisable.
SwitchfromONtoOFFtosetacustomtime.(Alsousedinprogrammingsequence.)
Thetimescrollsinsteps:
•5minutestepsfrom5minutesto1hour
•10minutestepsfrom1to4hours
•30minutestepsfrom4to12hours
•1hourstepsfrom12to24hours
5. BEEPER:SetONactivatingthefeatureforabeepwarningevery15secondsstarting2minutesbeforeOFF.
6. BLINK:SetONactivatingafeatureforloadflash2minutesbeforeOFF.
1. ToturnloadON,presstheSTART/STOPbuttonmomentarily.
•TheLCDwilldisplaythecountdowntimeintervalselected.Thetimeintervalwillstartcountingdown.
Operation
1. Totesttheunit,settheDIPSwitchtotheminimaltime-outinterval(5minutes).
2. Iftheunitdoesnotfunction:
a.Check thegroundwire.Makesuretheboxhasgoodgroundandisattachedproperly.
b.Checkallotherwiringtomakesureconnectionissecure.
c.Checkifpoweristurnedbackonatthemaincircuitbreakerpanel.
d.Iftheunitstilldoesnotfunction,consultthefactory.
3. IftheloadwillnotturnOFFautomatically:
a.CheckiftheloadgoesON/OFFwhenpressingSTART/STOPbutton.Ifnot,checktheredwireforgood
connection.IfloaddoesgoON/OFF,consultthefactory.
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.