
Operation
The Greenlee GT-16 is useful for identifying hot and neutral conductors,
finding a break in a wire, and detecting the presence of AC voltage
at outlets, switches, circuit breakers, fuses, and wires and cables,
including Romex®.
Note: Round cords may have twisted conductors. Check for hot
conductors by sliding the unit along the cord.
Note: The GT-16 can be used to find a break in a wire:
To find a break in a hot conductor, trace the wire until the signal
stops.
To find a break in a neutral conductor, connect a load between the hot
and neutral. Trace the wire until the signal stops.
1. Turn the unit on by rotating the sensitivity adjustment thumbwheel
away from the OFF position. Verify that the LED flashes periodically.
If the LED does not flash, the battery is not working and needs to be
replaced.
2. Test the unit on a known live circuit before each use.
If the unit does not function as expected on a known live circuit,
replace the battery.
If the unit still does not function as expected, call Greenlee for
technical assistance at 800-435-0786.
3. Place the tip on or near the circuit or unit to be tested. Tone and
flashing LED indicate the presence of voltage (5 VAC to 1000 VAC).
Use maximum sensitivity to detect low voltages.
Reduce sensitivity to find breaks in wires or to identify hot and
neutral conductors.
4. Test again on a known live circuit after use to verify proper
operation.
Specifications
Indicators: LED and Tone
Voltage Range: 5 VAC to 1000 VAC
Frequency Range: 50 Hz to 500 Hz
Measurement Category: Category IV, 1000 V per UL 61010
Operating Conditions:
Temperature: 0 °C to 40 °C (32 °F to 104 °F)
Less than 80% relative humidity (noncondensing)
Altitude: 2000 m (6500’) maximum
Indoor use only.
Pollution Degree: 2
Battery: One 1.5 volt battery (AAA, NEDA 24A or IEC LR03)
Measurement Categories
This definition was derived from the international safety standard for
insulation coordination as it applies to measurement, control, and
laboratory equipment. These measurement categories are explained in
more detail by the International Electrotechnical Commission; refer to
either of their publications: IEC 61010-1 or IEC 60664.
Measurement Category IV: Primary supply level. Overhead lines
and other cable systems. Some examples include cables, meters,
transformers, and other exterior equipment owned by the power utility.
Maintenance
Battery Replacement
1. Disconnect the unit from the circuit.
2. Rotate the outer battery cap clockwise and remove it.
3. Rotate the metal inner cap and remove it.
4. Replace the battery (observe polarity).
5. Replace the metal inner cap.
6. Replace the outer battery cap.
Tip
On-Off/Sensitivity Adjustment Thumbwheel
Inner Metal Cap
Battery Cap
Cleaning
Periodically wipe the case with a damp cloth and mild detergent;
do not use abrasives or solvents.
Statement of Conformity
Greenlee Textron Inc. is certified in accordance with ISO 9000 (2000) for
our Quality Management Systems.
The instrument enclosed has been checked and/or calibrated using
equipment that is traceable to the National Institute for Standards and
Technology (NIST).
Lifetime Limited Warranty
Greenlee Textron Inc. warrants to the original purchaser of these goods
for use that these products will be free from defects in workmanship
and material for their useful life, excepting normal wear and abuse.
This warranty is subject to the same terms and conditions contained in
Greenlee Textron Inc.’s standard one-year limited warranty.
For all Test Instrument repairs, contact Customer Service at
800-435-0786 and request a Return Authorization.
For items not covered under warranty (such as items dropped, abused,
etc.), a repair cost quote is available upon request.
Note: Prior to returning any test instrument, please check replaceable
batteries or make sure the battery is at full charge.
•
•
•
•
•
•