Grundfos CIM 300 User manual

BACnet for Grundfos boosters
CIM/CIU 300 BACnet MS/TP
CIM/CIU 500 BACnet IP
Functional profile and user manual
GRUNDFOS INSTRUCTIONS


English (GB) Functional profile and user manual
Original functional profile and user manual
Table of contents
1. General information ........................4
1.1 Hazard statements..........................4
1.2 Notes ..................................4
2. Introduction .............................5
2.1 About this functional profile.....................5
2.2 Assumptions .............................5
2.3 Definitions and abbreviations ...................5
2.4 System diagram ...........................6
2.5 Specifications .............................7
3. BACnet MS/TP, CIM 300 setup..................9
3.1 BACnet bus topology ........................9
3.2 CIM 300 BACnet module ......................9
3.3 Connecting to the BACnet network ...............10
3.4 Setting the BACnet transmission speed ............10
3.5 Selecting the Device Object Instance Number ........10
3.6 Selecting the Device Object Name ...............11
3.7 Selecting the BACnet MAC address ..............11
3.8 Termination resistor ........................11
3.9 Cable length.............................11
3.10 LEDs .................................11
4. BACnet IP, CIM 500 setup....................12
4.1 Connecting the Ethernet cable..................12
4.2 Setting the industrial Ethernet protocol.............13
4.3 Setting the IP addresses .....................13
4.4 Establishing connection to the webserver ...........13
4.5 Status LEDs.............................14
4.6 DATA and LINK LEDs .......................14
5. Supported services .......................15
5.1 Data-sharing services .......................15
5.2 Device management services ..................15
6. Object overview ..........................16
6.1 Device Object ............................16
6.2 Binary inputs ............................17
6.3 Binary outputs ...........................20
6.4 Multistate inputs ..........................21
6.5 Multistate outputs .........................23
6.6 Analog inputs ............................25
6.7 Analog outputs ...........................28
6.8 Analog values............................29
7. Detailed descriptions ......................31
7.1 Control modes ...........................31
7.2 Setpoint ...............................32
7.3 BACnet communication watchdog ...............33
7.4 Fault monitoring and resetting ..................33
7.5 Control via BACnet.........................33
7.6 Product simulation .........................34
7.7 Tank-filling applications ......................34
7.8 Remote sensors (CU 352) ....................34
8. Commissioning of hardware: step-by-step setup ....35
8.1 CIM 300 ...............................35
8.2 CIU 300 ...............................35
8.3 CIM 500 ...............................35
8.4 CIU 500 ...............................36
9. Fault finding the product ....................37
9.1 CIM/CIU 300 BACnet MS/TP ..................37
9.2 CIM/CIU 500 BACnet IP .....................38
10. BACnet telegrams ........................40
10.1 BACnet MS/TP telegram overview ...............40
10.2 Telegram types ...........................40
11. BACnet MAC address, CIM 300 ................41
12. Grundfos alarm and warning codes .............42
1. General information
Read this document before you install the product.
Installation and operation must comply with local
regulations and accepted codes of good practice.
1.1 Hazard statements
The symbols and hazard statements below may appear in Grundfos
installation and operating instructions, safety instructions and
service instructions.
DANGER
Indicates a hazardous situation which, if not avoided, will
result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate personal injury.
The hazard statements are structured in the following way:
SIGNAL WORD
Description of the hazard
Consequence of ignoring the warning
• Action to avoid the hazard.
1.2 Notes
The symbols and notes below may appear in Grundfos installation
and operating instructions, safety instructions and service
instructions.
Observe these instructions for explosion-proof products.
A blue or grey circle with a white graphical symbol
indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with a
black graphical symbol, indicates that an action must not
be taken or must be stopped.
If these instructions are not observed, it may result in
malfunction or damage to the equipment.
Tips and advice that make the work easier.
4
English (GB)

2. Introduction
2.1 About this functional profile
This functional profile describes the CIM/CIU 300 for BACnet
MS/TP and the CIM/CIU 500 for BACnet Ethernet IP as part of a
communication interface with the following Grundfos booster
systems:
• Grundfos Hydro Multi-B (CU 323)
• Grundfos Hydro MPC (CU 35X)
• Grundfos Control MPC (CU 35X)
• Grundfos Hydro Multi-E.
TPED twin-head pump with MGE motors model H or later
in multipump mode and MAGNA3 Twin-head pump in
multipump mode, requires a CIM module installed in the
master pump.
The object lists for the Hydro MPC and Control MPC are identical,
so in the following, only Hydro MPC is mentioned. If not specifically
mentioned, Hydro Multi-B, Hydro MPC and Hydro Multi-E are
referred to as "booster system".
Grundfos cannot be held responsible for any problem caused
directly or indirectly by using information in this functional profile.
2.2 Assumptions
This functional profile assumes that the reader is familiar with
commissioning and programming BACnet devices. The reader
should also have some basic knowledge of the BACnet protocol
and technical specifications.
It is also assumed that an existing BACnet MS/TP or IP network is
present.
2.3 Definitions and abbreviations
ARP Address Resolution Protocol translating IP addresses
into MAC addresses
Auto-MDIX Port ensuring that both crossover cable types and non-
crossover cable types can be used
CAT5 Ethernet cable with four twisted pairs of wires
CAT5e Enhanced CAT5 cable with better performance
CAT6 High performance Ethernet cable compatible with CAT5
and CAT5e
CIM 300 Communication Interface Module 300
CIU 300 Communication Interface Unit 300
CRC Cyclic Redundancy Check: data error-detection method
CU 323 Grundfos Control Unit 323
CU 35X Grundfos Control Units 351 and 352
Device Node on the BACnet MS/TP network
DHCP
Dynamic Host Configuration Protocol for configuring
network devices so that they can communicate on an IP
network
DNS Domain Name System for resolving host names to IP
addresses
GENIbus Proprietary Grundfos fieldbus standard based on
RS-485
GENIpro Proprietary Grundfos fieldbus protocol
Grundfos GO
Grundfos application designed to control Grundfos
products via infrared or radio communication (available
for iOS and Android devices)
HTTP Hyper Text Transfer Protocol (commonly used for
navigating the world wide web)
IANA Internet Assigned Numbers Authority
Inter-network Set of two or more BACnet networks interconnected by
routers
IP Internet Protocol
LED Light-Emitting Diode
MAC Media Access Control: unique network address for a
piece of hardware
MPC Multi-Pump Controller
MS/TP Master-Slave/Token-Passing (data protocol used for
BACnet RS-485)
Ping Packet Internet Groper: software utility testing the
connectivity between two TCP/IP hosts
Router Device connecting two or more networks at the network
layer
SELV Separated or Safety Extra-Low Voltage
SMTP Simple Mail Transfer Protocol
SNTP Simple Network Time Protocol for clock synchronisation
between computer systems
TCP Transmission Control Protocol for internet
communication and industrial Ethernet communication
TCP/IP Transmission Control Protocol/Internet Protocol for
internet communication
Transmission
speed Bits transferred per second (bit/s)
Trunk cable Main RS-485 cable on a BACnet MS/TP network
URL Uniform Resource Locator: the IP address used to
connect to a server
UTC Coordinated Universal Time: the primary time standard
by which the world regulates clocks and time
UTF-8 Unicode Transformation Format (character encoding)
VPN
Virtual Private Network: network using the internet to
connect nodes
These systems use encryption and other security
mechanisms to ensure that only authorised users can
access the network and that the data cannot be
intercepted.
5
English (GB)

2.4 System diagram
Figures CIM solution for Hydro Multi-B and Solution with CIM 300 and 500 for CU 352 and CIU for Hydro Multi-E (CU 351) give an overview of
how to connect the module or unit to the Grundfos booster system that is to be connected to a BACnet network.
The Hydro MPC, Control MPC and Multi-E boosters are available in two variants. They have different CIM/CIU connections as described
below.
CIM solution
A Communication Interface Module (CIM) is an add-on communication module that you fit into the following products:
• CU 352 MPC
• CU 323 Multi-B
• Multi-E based on MGE motors model H or later
• TPED twin-head pump in multipump mode
• MAGNA3-D twin-head pump in multipump mode.
In this setup, the booster system supplies power to the module. See figure CIM solution for Hydro Multi-B below.
CIU solution
A Communication Interface Unit (CUI) is a box incorporating a power supply module and a CIM 300 BACnet module. It can either be mounted
on a DIN rail or on a wall. See figure Solution with CIM 300 and 500 for CU 352 and CIU for Hydro Multi-E (CU 351).
The unit is used with the following products:
• CU 351 MPC
• Multi-E based on MGE motors before model H.
The Hydro MPC with the CU 351 or the Hydro Multi-E controls and monitors a number of pumps (2 to 6), all connected with RS-485 cables. If
fitted with an extra GENIbus module, the Hydro MPC with the CU 351 can be connected to the unit via an RS-485 cable.
The CU 351 must have an external GENIbus module installed in order to communicate with the CIU BACnet unit.
BACnet MS/TP or IP
CIM 300/500
TM079989
CIM solution for Hydro Multi-B
Hydro MPC (CU 351)
BACnet MS/TP or IP
CIM 300/500
CU 352
CIM 300/500
with
TM079990
Solution with CIM 300 and 500 for CU 352 and CIU for Hydro Multi-E (CU 351)
6
English (GB)

2.5 Specifications
The table below provides an overview of the specifications for the Grundfos CIM/CIU 300 for BACnet MS/TP and the CIM/CIU 500 for BACnet
IP. For further details, refer to the specific sections of this functional profile.
General data Description Comments
Ambient humidity 30-95 % It is considered relative, non-condensing.
Operating temperature -20 to +45 °C
Storage temperature -25 to +70 °C
GENIbus visual diagnostics LED2 The LED is in one of the following states:
Off, permanently green, flashing red, permanently red.
BACnet MS/TP Description Comments
BACnet connector Screw-type terminal 3 pins
BACnet connection type RS-485
BACnet wire configuration 2-wire + ground Conductors: Plus, Minus and Ground
Maximum cable length [m] 1200 Equals 4000 ft
Recommended cross-section of BACnet cable 0.20 - 0.25 mm2AWG24 or AWG23
MAC address 0-127 To be set via rotary switches SW6 and SW7
Line termination On or Off To be set via DIP switches SW1 and SW2
Supported transmission speeds [bit/s] 9600, 19200, 38400, 76800 To be set via DIP switches SW4 and SW5
Data bits 8 Fixed value
Stop bits 1 Fixed value
Parity None Fixed value
BACnet visual diagnostics LED1 Red and green status LED
Maximum number of BACnet devices 32 Number can be increased by using repeaters
Grundfos BACnet vendor ID 227
BACnet segmentation support No
Character set support ANSI X3.4 and UTF8 Supported character sets
BACnet device profile B-ASC BACnet Application-Specific Controller
BACnet MS/TP master Yes CIM/CIU 300 is a BACnet MS/TP master device
Manual slave address binding No
BACnet protocol revision For hardware version R4: 4
For hardware version R8: 9
BACnet IP Description Comments
Application layer DHCP, HTTP, Ping, FTP, SMTP, SNTP,
BACnet IP Rotary switch in position 2
Transport layer UDP
Internet layer Internet protocol V4 (IPv4)
Link layer ARP, media access control (Ethernet)
Ethernet cable CAT5, CAT5e or CAT6 Supports auto cable-crossover detecting (Auto-MDIX)
Maximum cable length 100 metres at 10/100 Mbit/s Corresponds to 328 feet
Transmission speed 10 Mbit/s, 100 Mbit/s Auto-detected
Industrial Ethernet protocols PROFINET IO, Modbus TCP, BACnet IP
etc. Selected with rotary switch
BACnet protocol revision 9
CIM 300 and 500 Description Comments
Dimensions [w x h x d] [mm] 50 x 19 x 80
Power supply Supplied by the booster system
Connection to booster system 10-pin connection
CIU 300 and 500 Description Comments
CIU box dimensions (H x W x D) 182 x 108 x 82 mm
Power supply 24-240 V AC/DC Located in the unit
GENIbus connection type RS-485, 3-wire + screen Conductors: A, B and Y
Enclosure class IP54
Recommended cross-section of GENIbus cable 0.20 - 0.25 mm2AWG24 or AWG23
7
English (GB)

3. BACnet MS/TP, CIM 300 setup
3.1 BACnet bus topology
The Grundfos CIM/CIU 300 is connected as a BACnet MS/TP
master directly to the BACnet MS/TP network.
MS
S
S
M
M
BR
LT
S
LT
TM044274
Example of BACnet MS/TP network
Pos. Description
M Master
S Slave
LT Line Termination
BR Bias Resistors
The BACnet MS/TP is a multi-master system which means that
there can be more than one master on the network. It uses a token
to control access to the bus network. A master node may initiate the
transmission of a data telegram when it holds the token. Both
master and slave nodes may transmit data telegrams in response to
requests from master nodes, but slaves never hold the token.
Master nodes pass the token between them.
A BACnet MS/TP segment is a single contiguous medium to which
BACnet nodes are attached. Segments can be connected by use of
repeaters or bridges, thus forming networks.
Multiple networks may be interconnected by BACnet routers to form
a BACnet inter-network.
3.1.1 Line termination resistors
Line termination must be connected at each of the two ends of the
segment medium. The CIM/CIU 300 has optional line termination
resistor on board.
3.1.2 Bias resistors
At least one set, and no more than two sets, of network bias
resistors must exist for each segment so that an undriven
communications line is held in a guaranteed logical one state. The
bias provides a reliable way for stations to detect the presence or
absence of signals on the line. An unbiased line takes an
indeterminate state in the absence of any driving node.
The CIM/CIU 300 has no bias resistors.
3.2 CIM 300 BACnet module
1 2 3 4 5 6 7
8
9
TM041697
CIM 300 BACnet module
Pos. Designation Description
1 Plus BACnet Plus terminal, RS-485 positive
data signal
2 Minus BACnet Minus terminal, RS-485 negative
data signal
3 Ground BACnet ground terminal
4 SW1/SW2 On and off switches for termination
resistor
5 SW3/SW4/SW5
Switches for selecting the BACnet
transmission speed and the default or
custom Device Object Instance Number
6 LED1 Red and green status LED for BACnet
communication
7 LED2
Red and green status LED for internal
communication between CIM 300 and the
booster system
8 SW6
Hexadecimal rotary switch for setting the
BACnet MAC address (four most
significant bits)
9 SW7
Hexadecimal rotary switch for setting the
BACnet MAC address (four least
significant bits)
9
English (GB)

3.3 Connecting to the BACnet network
Use a screened, twisted-pair cable.
BACnet terminal Recommended colour Data signal
Plus Red Positive
Minus Green Negative
Ground Grey Ground
The ANSI/ASHRAE BACnet standard states that the cable screen
must only be earthed at one end of the segment to prevent earth
fault currents.
3.4 Setting the BACnet transmission speed
Set the transmission speed correctly before the CIM 300 is ready to
communicate on the BACnet MS/TP network. Use the DIP switches
SW4 and SW5 to set the transmission speed.
The default transmission speed is 9600 bit/s, but we recommend
higher speeds for better data throughput. All devices on the BACnet
MS/TP network must communicate at the same transmission
speed.
SW4 SW5
TM041710
BACnet transmission speed settings
3.4.1 DIP switch settings
Available transmission speeds in bit/s: 9600, 19200, 38400 and
76800.
Use the DIP switches SW4 and SW5 to select the desired speed.
Transmission speed
[bit/s] SW4 SW5
9600 OFF OFF
19200 OFF ON
38400 ON OFF
76800 ON ON
The default transmission speed is 9600 bit/s, as per the BACnet
MS/TP standard. The transmission speed is effective immediately
after setting the values of the DIP switch.
3.5 Selecting the Device Object Instance Number
The Device Object Identifier value consists of two components:
• a 10-bit Object Type (bits 22 to 31)
• a 22-bit Instance Number (bits 0 to 21).
31 22
10 bits 22 bits
21 0
Object type Instance Number
...
TM045977
Bit numbers
The Object Type is fixed and determines that it is a Device Object.
The Instance Number is a numeric code that is used to identify the
device. It must be unique inter-network-wide, that is, on all
interconnected networks.
The CIM 300 offers two different approaches to setting the BACnet
Device Object Instance Number: default and custom, both
described in the following subsections.
3.5.1 Default Instance Number
By default, the CIM 300 uses a pre-defined Device Object Instance
Number which is 227XXX where XXX is the BACnet MAC address.
This gives an Instance Number range of 227000 to 227127.
Example
The BACnet MAC address is set to 20 via the hexadecimal rotary
switches, so the Device Object Instance Number is 227020.
Related information
3.7 Selecting the BACnet MAC address
3.5.2 Custom Instance Number
To use the complete Instance Number range, set the new Instance
Number with the BACnet object Custom Device Object Instance
Number (AV, 0), and set SW3 to ON. This immediately sets the new
Device Object Instance Number.
SW3
TM041709
Device Object Instance Number
Device Object Instance Number SW3
Default (227000 + BACnet MAC address) OFF
Custom, set with object (AV, 0) ON
The default Present_Value of the Custom Device Object Instance
Number is 231.
Example
The Present_Value of the Custom Device Object Instance Number
(AV, 0) is 231, so the Device Object Instance Number is 231.
The Present_Value of the Custom Device Object Instance
Number cannot be 4194303 as this is a reserved value.
10
English (GB)

3.6 Selecting the Device Object Name
The property Device_Name is a character string that must be
unique inter-network-wide. By default, the name is constructed as
"Grundfos - XXXXXX" where XXXXXX is the current Device Object
Instance Number as described in the section Selecting the Device
Object Instance Number.
Example
The Device Object Instance Number is 227001, so the Device
Object Name is "Grundfos - 227001".
If a new name is selected, it is stored in the device and replaces the
default naming scheme.
Related information
3.5 Selecting the Device Object Instance Number
3.7 Selecting the BACnet MAC address
To set the BACnet MAC address, use the two hexadecimal rotary
switches, SW6 and SW7.
The value must be within the range of 0 to 127. An illegal value
results in a MAC address of 0.
SW6 SW7
TM041706
Setting the BACnet MAC address
For a complete overview of BACnet addresses, see section BACnet
MAC address, CIM 300.
You must set the BACnet MAC address decimally from 0
to 127 and it must be unique on the BACnet MS/TP
segment.
Related information
11. BACnet MAC address, CIM 300
3.8 Termination resistor
A termination resistor for line termination is fitted on the CIM 300
and has a value of 120 Ω. It is to be cut in if the CIM 300 is set as
the last station on the network.
The CIM 300 has two DIP switches, SW1 and SW2, for cutting the
termination resistor in and out.
SW1 SW2
TM041701
Cutting the termination resistor in and out
Status SW1 SW2
Cut in ON ON
Cut out
OFF OFF
ON OFF
OFF ON
Default setting: The termination resistor is cut out.
3.9 Cable length
The recommended maximum cable length within a BACnet MS/TP
segment is 1200 metres (4000 ft) with 0.82 mm2 (AWG 18) cable.
The connection between the BACnet modules must be made by a
screened, twisted-pair cable with a characteristic impedance
between 100 and 130 Ω.
3.10 LEDs
The CIM 300 BACnet has two LEDs:
• red and green status LED (LED1) for BACnet MS/TP
communication
• red and green status LED (LED2) for internal communication
between the CIM 300 and the Grundfos pump.
3.10.1 LED1, BACnet MS/TP communication
Status Description
Off No communication
Flashing green Communication active
Flashing red Fault in the BACnet communication
Permanently red Fault in the CIM 300 BACnet configuration
3.10.2 LED2, internal communication
Status Description
Off The CIM/CIU 300 has been switched off or is
starting up.
Flashing red There is no internal communication between
the CIM/CIU 300 and the booster system.
Permanently red The CIM/CIU 300 does not support the
connected booster system.
Permanently green Internal communication between the CIM/CIU
300 and the booster system is OK.
During startup, there may be a delay of up to 5 seconds
before the LED status is updated.
11
English (GB)

4. BACnet IP, CIM 500 setup
WARNING
Electric shock
Death or serious personal injury
‐Connect the CIM 500 only to SELV circuit.
4.1 Connecting the Ethernet cable
Use RJ45 plugs and Ethernet cable. Connect the cable shield to
protective earth at both ends.
It is important to connect the cable shield to earth through
an earth clamp or to connect the cable shield to earth in
the connector.
Maximum cable length
Speed
[Mbit/s] Cable type Maximum cable length
[m/ft]
10 CAT5 100/328
100 CAT5e, CAT6 100/328
The CIM 500 is designed for flexible network installation. The built-
in two-port switch makes it possible to daisy chain from product to
product without additional Ethernet switches. The last product in the
chain is only connected to one of the Ethernet ports. Each Ethernet
port has its own MAC address.
1
CIM
500
CIM
500
CIM
500
CIM
500
TM079841
Example of Industrial Ethernet network
Pos. Description
1 Ethernet switch
1 2
4
3
56
7
8 9
TM079842
Example of Ethernet connection
Pos. Description Designation
1 Industrial Ethernet RJ45 connector 1 ETH1
2 Industrial Ethernet RJ45 connector 2 ETH2
3 Rotary switch for protocol selection SW1
4 Data activity LED for connector 1 DATA1
5 Link LED for connector 1 LINK1
6 Data activity LED for connector 2 DATA2
7 Link LED for connector 2 LINK2
8Green and red status LED for Ethernet
communication LED1
9
Green and red status LED for internal
communication between the module and the
booster system
LED2
12
English (GB)

4.2 Setting the industrial Ethernet protocol
The CIM 500 Ethernet module has a rotary switch for selecting
industrial Ethernet protocol.
TM079751
Selecting the industrial Ethernet protocol
Pos. Description
0 PROFINET IO (default)
1 Modbus TCP
2 BACnet IP
3 EtherNet/IP
4 GRM IP (requires a contract with Grundfos)
5.E Reserved - LED1 being permanently red: invalid configuration
F
Reset to factory default
Note: The rotary switch must be set in this position for 20 seconds
to reset to factory default. During this period, LED1 flashes red and
green at the same time to indicate a reset.
Every change of the rotary switch while the module is
powered on causes the module to restart.
Related information
3.7 Selecting the BACnet MAC address
4.3 Setting the IP addresses
By default, the CIM 500 Ethernet module is set to a fixed IP
address. You can change the IP address settings from the built-in
webserver.
Default IP settings used
by the webserver
IP address:
Subnet mask:
Gateway:
192.168.1.100
255.255.255.0
192.168.1.1
IP settings for BACnet IP To be set via the webserver
4.4 Establishing connection to the webserver
You can configure the CIM 500 using the built-in webserver. To
establish a connection from a PC to the CIM 500, the following
steps are required:
• Connect the PC and the CIM 500 using an Ethernet cable.
• Configure the PC Ethernet port to the same subnetwork as that
of the CIM 500, for example, 192.168.1.101, and the subnet
mask to 255.255.255.0.
• Open a standard internet browser and type 192.168.1.100 in the
URL field.
• Log in to the webserver:
User admin (default)
Password Grundfos (default)
The user name and password may have been changed
from their default values.
Change the username and password at the first login.
TM056436
CIM 500 connected to PC via Ethernet cable
For further information on how to use the webserver, see
section Webserver configuration.
You can use both ETH1 and ETH2 to establish a
connection to the webserver.
You can access the webserver while the selected
industrial Ethernet protocol is active.
Related information
A.1.2. How to configure an IP address on your PC using Windows
10
A.1.1. Webserver configuration
13
English (GB)

4.5 Status LEDs
The CIM 500 Ethernet module has two status LEDs:
• Red and green status LED (LED1) for Ethernet communication
• Red and green status LED (LED2) for internal communication
between the CIM 500 and the Grundfos product.
LED1
Status Description
Off There is no BACnet IP communication or it is
switched off.
Flashing green The BACnet IP communication is active.
Permanently red There is a fault in the CIM 500 configuration.
Permanently red and
green There is an error in firmware download.
Flashing red and green The module is resetting to factory default.
After 20 seconds, the CIM 500 restarts.
LED2
Status Description
Off The CIM 500 is switched off.
Flashing red There is no internal communication between the
CIM 500 and the Grundfos product.
Permanently red The CIM 500 does not support the Grundfos
product connected.
Permanently green Internal communication between the CIM 500
and the Grundfos product is OK.
Permanently red and
green A memory fault occurred.
During startup, there is a delay of up to 5 seconds before
LED1 and LED2 status is updated.
Related information
4.1 Connecting the Ethernet cable
9.2 CIM/CIU 500 BACnet IP
4.6 DATA and LINK LEDs
The CIM 500 Ethernet module has two connectivity LEDs related to
each RJ45 connector.
DATA1 and DATA2
These yellow LEDs indicate data traffic activity.
Status Description
Yellow off There is no data communication on the RJ45 connector.
Yellow flashing There is data communication ongoing on the RJ45
connector.
Permanently
yellow There is heavy network traffic.
LINK1 and LINK2
These green LEDs show whether the Ethernet cable is properly
connected.
Status Description
Green off There is no Ethernet link on the RJ45 connector.
Green on The Ethernet link on the RJ45 connector is OK.
Related information
4.1 Connecting the Ethernet cable
14
English (GB)

5. Supported services
BACnet Interoperability Building Blocks (BIBBs) are collections of one or more BACnet services. These are described in terms of an "A" and a
"B" device. Both devices are nodes on a BACnet inter-network. In most cases, the "A" device acts as the user of data (client), and the "B"
device is the provider of this data (server).
The CIM/CIU 300 and 500 are BACnet Application-Specific Controllers (B-ASC) with a few additional services.
5.1 Data-sharing services
Name BACnet BIBB code Notes Initiate Execute
ReadProperty DS-RP-B The CIM 300 and 500 can be provider of data. - ●
ReadPropertyMultiple DS-RPM-B The CIM 300 and 500 can be provider of data and return multiple
values at one time. - ●
WriteProperty DS-WP-B The CIM 300 and 500 allow a value to be changed over the network. - ●
WritePropertyMultiple DS-WPM-B The CIM 300 and 500 allow multiple values to be changed over the
network. - ●
SubscribeCOV
DS-COV-B
The CIM 300 and 500 can be provider of "Change Of Value" data.
Both support up to 10 simultaneous COV subscriptions. Subscription
lifetime can be limited or unlimited.
- ●
ConfirmedCOVNotification ● -
UnconfirmedCOVNotification ● -
5.2 Device management services
Name BACnet BIBB code Notes Initiate Execute
Who-Is DM-DDB-A The CIM 300 and 500 can seek information about device attributes
of other devices and interpret device announcements.
● -
I-Am - ●
Who-Is DM-DDB-B The CIM 300 and 500 can provide information about their device
attributes and respond to requests to identify themselves.
- ●
I-Am ●
Who-Has DM-DOB-B The CIM 300 and 500 can provide address information about their
objects upon request.
- ●
I-Have ● -
DeviceCommunicationControl DM-DCC-B
The CIM 300 and 500 can respond to communication control
requests. They support both limited and unlimited duration. The
password, if required, is "Grundfos".
- ●
15
English (GB)

6. Object overview
6.1 Device Object
The following properties are supported in the Device Object (available for all pump types).
Property identifier Data type Notes Access
Object_Identifier BACnetObjectIdentifier See section Selecting the Device Object Instance Number. R
Object_Name CharacterString See section Selecting the Device Object Name for details on
object name. W
Object_Type BACnetObjectType DEVICE R
System_Status BACnetDeviceStatus OPERATIONAL R
Vendor_Name CharacterString Grundfos R
Vendor_Identifier Unsigned16 227 R
Model_Name CharacterString It shows the Grundfos pump model to which the CIM/CIU is
connected. R
Firmware_Revision CharacterString It shows the revision of the firmware in the CIM/CIU. R
Application_Software_Version CharacterString It displays the software build date, DD-MM-YYYY. R
Location CharacterString The user can enter a location here (maximum 200
characters). W
Description CharacterString The user can enter a description here (maximum 200
characters). W
Protocol_Version Unsigned It is the actual version of the BACnet protocol. R
Protocol_Revision Unsigned It is the actual revision of the BACnet protocol. R
Protocol_Services_Supported BACnetServicesSupported It shows the supported standardised protocol services. R
Protocol_Object_Types_Supported BACnetObjectTypesSupported It shows the supported standardised protocol object types. R
Object_List BACnetARRAY[N]of
BACnetObjectIdentifier It shows the array of objects available. R
Max_APDU_Length_Accepted Unsigned
CIM 300: The maximum number of bytes that may be
contained in a single APDU is fixed to 480.
CIM 500: The maximum number is 1476.
R
Segmentation_Supported BACnetSegmentation
It indicates if segmentation of messages is possible. It always
reads NO_SEGMENTATION to indicate that segmentation is
not possible.
R
APDU_Timeout Unsigned It shows the amount of time in ms before time-out. R
Number_Of_APDU_Retries Unsigned It is the maximum number of times an APDU is to be
retransmitted. R
Max_Master Unsigned
The default value is 127, but this value can be lowered by the
user to reduce transmission overhead.
The Max_Master value must be higher than or equal to the
highest MAC address used by a master node in an MS/TP
network.
W
Max_Info_Frames Unsigned It shows the maximum number of information frames sent
before the token is passed on (fixed to 1). R
Device_Address_Binding List of BACnetAddressBindings It holds address bindings to other devices, if any. R
Database_Revision Unsigned Logical revision number for the device database. R
Related information
3.5 Selecting the Device Object Instance Number
3.6 Selecting the Device Object Name
16
English (GB)

6.2 Binary inputs
Binary objects provide information from the Grundfos booster system.
ID Object name R/W Notes
MGE model H and later Twin-head pump +
MAGNA3 Twin-head pump
Hydro Multi-B
Hydro MPC
Hydro Multi-E
BI, 0 Control source status R
Status of the actual control source
0: Local control
1: Bus control
● ● ● ●
BI, 2 Rotation status R
Rotation status
0: No rotation
1: Rotation (one or more pumps running)
● ● ● ●
BI, 3 At minimum speed R 0: Not running at minimum speed
1: Running at minimum speed ● - ● ●
BI, 4 At maximum speed R 0: Not running at maximum speed
1: Running at maximum speed ● - ● ●
BI, 5 Standby pumps active R 0: Standby pumps not active
1: Standby pumps active - - ● -
BI, 6 Pressure relief active R 0: Pressure relief not active
1: Pressure relief active - - ● -
BI, 7 Soft pressure active R 0: Soft pressure not active
1: Soft pressure active - - ● -
BI, 8 Low-flow boost active R 0: Low-flow boost not active
1: Low-flow boost active - - ● -
BI, 9 Low-flow stop active R 0: Low-flow stop not active
1: Low-flow stop active H ● ● -
BI, 10 Alternative setpoint active R 0: Alternative setpoint not active
1: Alternative setpoint active - - ● -
BI, 11 Digital input 1 status R 0: Not active
1: Active ● ● ● ●
BI, 12 Digital input 2 status R 0: Not active
1: Active ● ● ● ●
BI, 13 Digital input 3 status R 0: Not active
1: Active H ● ● ●
BI, 14 Digital output 1 status R 0: Not active
1: Active ● ● ● ●
BI, 15 Digital output 2 status R 0: Not active
1: Active ● ● ● ●
BI, 16 Subpump 1 presence R 0: Subpump not present
1: Subpump present H ● ● ●
BI, 17 Subpump 1 communication status R 0: Communication OK
1: Communication fault H ● ● ●
BI, 18 Subpump 2 presence R 0: Subpump not present
1: Subpump present H ● ● ●
BI, 19 Subpump 2 communication status R 0: Communication OK
1: Communication fault H ● ● ●
BI, 20 Subpump 3 presence R 0: Subpump not present
1: Subpump present - ● ● ●
BI, 21 Subpump 3 communication status R 0: Communication OK
1: Communication fault - ● ● ●
BI, 22 Subpump 4 presence R 0: Subpump not present
1: Subpump present - ● ● ●
BI, 23 Subpump 4 communication status R 0: Communication OK
1: Communication fault - ● ● ●
BI, 24 Subpump 5 presence R 0: Subpump not present
1: Subpump present - - ● ●
17
English (GB)

ID Object name R/W Notes
MGE model H and later Twin-head pump +
MAGNA3 Twin-head pump
Hydro Multi-B
Hydro MPC
Hydro Multi-E
BI, 25 Subpump 5 communication status R 0: Communication OK
1: Communication fault - - ● ●
BI, 26 Subpump 6 presence R 0: Subpump not present
1: Subpump present - - ● ●
BI, 27 Subpump 6 communication status R 0: Communication OK
1: Communication fault - - ● ●
BI, 28 Fault simulation status R
Fault simulation status
0: Fault simulation disabled
1: Fault simulation enabled
- ● ● H
BI, 31 At power limit R
At power limit status
0: Not at power limit
1: At power limit
- - -
BI, 32 Subpump 1 auto mode R 0: Manual control
1: Auto-control - ● ● -
BI, 33 Subpump 2 auto mode R 0: Manual control
1: Auto-control - ● ● -
BI, 34 Subpump 3 auto mode R 0: Manual control
1: Auto-control - ● ● -
BI, 35 Subpump 4 auto mode R 0: Manual control
1: Auto-control - ● ● -
BI, 36 Subpump 5 auto mode R 0: Manual control
1: Auto-control - - ● -
BI, 37 Subpump 6 auto mode R 0: Manual control
1: Auto-control - - ● -
BI, 38 Setpoint influence active R 0: No influence on setpoint
1: Setpoint influence active ● - ● H
BI, 39 Max flow limit enabled R 0: Max flow limit disabled
1: Max flow limit enabled M - - H
BI, 40 Pilot pump auto mode R 0: Manual control
1: Auto-control - - ● -
BI, 41 Pilot pump presence R 0: Pilot pump not present
1: Pilot pump present - - ● -
BI, 42 Pilot pump communication status R 0: Communication OK
1: Communication fault - - ● -
BI, 43 Backup pump auto mode R 0: Manual control
1: Auto-control - - ● -
BI, 44 Backup pump presence R 0: Backup pump not present
1: Backup pump present - - ● -
BI, 45 Backup pump communication status R 0: Communication OK
1: Communication fault - - ● -
BI, 46 Subpump 1 running R 0: Not running, 1: Running H - ● ●
BI, 47 Subpump 2 running R 0: Not running, 1: Running H - ● ●
BI, 48 Subpump 3 running R 0: Not running, 1: Running - - ● ●
BI, 49 Subpump 4 running R 0: Not running, 1: Running - - ● ●
BI, 50 Subpump 5 running R 0: Not running, 1: Running - - ● ●
BI, 51 Subpump 6 running R 0: Not running, 1: Running - - ● ●
BI, 52 Pilot pump running R 0: Not running, 1: Running - - ● ●
BI, 53 Backup pump running R 0: Not running, 1: Running - - ● ●
BI, 54 Subpump 1 fault R 1: Fault H - ● ●
BI, 55 Subpump 2 fault R 1: Fault H - ● ●
BI, 56 Subpump 3 fault R 1: Fault - - ● ●
BI, 57 Subpump 4 fault R 1: Fault - - ● ●
18
English (GB)

ID Object name R/W Notes
MGE model H and later Twin-head pump +
MAGNA3 Twin-head pump
Hydro Multi-B
Hydro MPC
Hydro Multi-E
BI, 58 Subpump 5 fault R 1: Fault - - ● ●
BI, 59 Subpump 6 fault R 1: Fault - - ● ●
BI, 60 Pilot pump fault R 1: Fault - - ● ●
BI, 61 Backup pump fault R 1: Fault - - ● ●
BI, 62 Flow estimation below range R 0: Flow estimation not below range
1: Flow estimation below range - - - -
BI, 63 Flow estimation ABOVE range R 0: Flow estimation not above range
1: Flow estimation above range - - - -
BI, 64 Forced to local R 0: Not forced to local
1: Forced to local - - - -
BI, 65 Digital Input 3 status R 0: Not active
1: Active - - ● -
BI, 66 Digital Input 4 status R 0: Not active
1: Active - - ● -
BI, 67 Digital Input 5 status R 0: Not active
1: Active - - ● -
BI, 68 Digital Input 6 status R 0: Not active
1: Active - - ● -
BI, 69 Digital Input 7 status R 0: Not active
1: Active - - ● -
BI, 70 Digital Input 8 status R 0: Not active
1: Active - - ● -
H: For MGE model H and later only
M: For MAGNA3 only
19
English (GB)

6.3 Binary outputs
Binary objects are used for controlling the Grundfos booster system.
ID Object name R/W Notes
MGE model H and later Twin-head pump +
MAGNA3 Twin-head pump
Hydro Multi-B
Hydro MPC
Hydro Multi-E
BO, 0 Set control source W
It sets the control source.
Set to 1 to enable control via BACnet.
0: Local control (default)
1: Bus control
● ● ● ●
BO, 1 Relay 1 control W
It controls relay 1 if bus control is enabled and relay 1 is
set to be controlled via bus.
0: Closed (default)
1: Open
H - - H
BO, 2 Relay 2 control W
It controls relay 2 if bus control is enabled and relay 2 is
set to be controlled via bus.
0: Closed (default)
1: Open
H - - H
BO, 4 Reset fault W
It resets alarm if bus control is enabled.
(It is triggered on rising edge.)
0: No resetting (default)
1: Resetting
● ● ● ●
BO, 5 Fault simulation W
It enables fault simulation.
0: Disabled (default)
1: Enabled
- ● ● H
BO, 6 Copy settings to local W
It copies remote settings to local pump settings.
0: Disabled
1: Enabled
If enabled, change BO from 0 to "1: Bus control".
● - - H
BO, 7 Relay 3 control W
It controls relay 3 if bus control is enabled and relay 3 is
set to be controlled via bus.
0: Closed (default)
1: Open
H - - H
BO, 8 Relay 4 control W
It controls relay 4 if bus control is enabled and relay 4 is
set to be controlled via bus.
0: Closed (default)
1: Open
H - - H
BO, 9 Enable max flow limit W
It is used to limit the flow.
0: No flow limitation
1: Flow limit active
● - - H
H: For MGE model H or newer
For Multi-E with CIM in each pump: always send all commands (writings) to all pumps.
A TPED model H is essentially a Multi-E model H with two pumps.
20
English (GB)
Other manuals for CIM 300
1
This manual suits for next models
3
Table of contents
Other Grundfos Extender manuals

Grundfos
Grundfos Hydro Multi-B Installation and operation manual

Grundfos
Grundfos Hydro Solo-S CR Series User manual

Grundfos
Grundfos CMB-SP Booster PM2 User manual

Grundfos
Grundfos CMB PM1 User manual

Grundfos
Grundfos JP User manual

Grundfos
Grundfos Hydro Multi-E Series User manual

Grundfos
Grundfos Hydro Multi-E 3CRE 15-03 User manual

Grundfos
Grundfos CMB-SP PM1 User manual

Grundfos
Grundfos JP User manual

Grundfos
Grundfos Home Booster 3.0 Bar User manual