GST GST102A User manual

Installation and Operation Manual
Page I
CONTENTS
Installation Precautions............................................................................................................ 1
EN 54 Information...................................................................................................................... 2
Chapter 1 Product Overview.................................................................................................... 3
1.1 Features............................................................................................................................. 3
1.2 Technical Specifications..................................................................................................... 3
1.2.1 Operating Voltage ....................................................................................................... 3
1.2.2 Batteries...................................................................................................................... 4
1.2.3 Installation Environment.............................................................................................. 4
1.2.4 Load of Power Supply................................................................................................. 4
1.2.5 Detection Zone............................................................................................................ 4
1.2.6 Output Loop ................................................................................................................ 5
1.2.7 Remote Interface......................................................................................................... 5
1.3 Controls and Indications .................................................................................................... 5
1.3.1 Common Status Indicators.......................................................................................... 6
1.3.2 Zone Status Indicators ................................................................................................ 6
1.3.3 Operating Indicators and Keys ................................................................................... 6
1.3.4 Output Indicators......................................................................................................... 6
1.3.5 Indicators of Control Board......................................................................................... 7
1.4 Construction and Configuration......................................................................................... 7
1.4.1 Appearance................................................................................................................. 7
1.4.2 Configuration............................................................................................................... 8
1.5 Terminal Description.......................................................................................................... 9
1.5.1 Terminals on the Control Board .................................................................................. 9
1.5.2 Terminals on GST116A Extension Board.................................................................. 10
1.5.3 Terminals on Signal Output Interface Board of GST116A........................................ 10
1.5.4 Terminals on Signal Output Interface Board of GST108A.........................................11
1.5.5 Terminals on Signal Output Interface Board of GST102A/104A ...............................11
1.6 Dimensions...................................................................................................................... 12
Chapter 2 Installation.............................................................................................................. 13
2.1 Installing the Cabinet ....................................................................................................... 13
2.2 Mains Connection............................................................................................................ 13
2.3 Battery Connection.......................................................................................................... 13
2.4 Zone Input Connection .................................................................................................... 14
www.acornfiresecurity.com
www.acornfiresecurity.com

Installation and Operation Manual
Page II
2.4.1 Using end of line resistor .......................................................................................... 14
2.4.2 Using an Active End of Line Unit .............................................................................. 14
2.5 Sounder/Alarm Output Connection ................................................................................. 14
Chapter 3 System Setup......................................................................................................... 15
3.1 Setting Access Levels...................................................................................................... 15
3.1.1 Setting Access Level 1.............................................................................................. 15
3.1.2 Setting Access Level 2.............................................................................................. 15
3.1.3 Setting Access Level 3.............................................................................................. 15
3.2 Setting Sounder/Alarm Output......................................................................................... 16
3.2.1 Example for Setting Voltage Output.......................................................................... 16
3.2.2 Example for Setting Normally Open Output ............................................................. 16
3.2.3 Example for Setting Normally Closed Output........................................................... 16
3.3 Disablement of a Zone or Output .................................................................................... 16
3.3.1 Use of Disablement Function.................................................................................... 16
3.3.2 Operation Steps ........................................................................................................ 16
3.4 Setting Test Mode............................................................................................................ 17
3.4.1 Use of Test Mode...................................................................................................... 17
3.4.2 Operation Steps ........................................................................................................ 17
3.5 Programming Output Modes ........................................................................................... 17
3.5.1 Setting the FACP to Default...................................................................................... 18
3.5.2 Setting “With Manual Call Point” ............................................................................... 18
3.5.3 Setting Associated Sounders of a Zone ................................................................... 19
3.5.4 Setting Delay Time of Alarm Output.......................................................................... 20
3.6 Setting Auxiliary Functions .............................................................................................. 21
3.7 Ground Fault Checking and Auxiliary Power Setting ...................................................... 21
Chapter 4 Operation Instructions.......................................................................................... 23
4.1 Working State Description ............................................................................................... 23
4.1.1 State of Detection Zones........................................................................................... 23
4.1.2 Alarm Output State.................................................................................................... 23
4.1.3 Sounder Output State ............................................................................................... 23
4.1.4 Safe State.................................................................................................................. 23
4.1.5 Description of the Buzzer.......................................................................................... 23
4.1.6 Notes......................................................................................................................... 24
4.2Acknowledgement and Silence of Fault .......................................................................... 24
www.acornfiresecurity.com
www.acornfiresecurity.com

Installation and Operation Manual
Page III
4.3Acknowledgement and Silence of Fire Alarm.................................................................. 24
4.4 Silencing the Sounders.................................................................................................... 24
4.5 Evacuation ....................................................................................................................... 24
4.6 Self-test and Reset.......................................................................................................... 24
4.7 Setting Day/Night Mode................................................................................................... 25
Chapter 5 Calculation of Batteries Capacity ........................................................................ 26
Chapter 6 Servicing................................................................................................................. 27
6.1 Replacing the Batteries.................................................................................................... 27
6.2 Replacing the Fuses........................................................................................................ 27
6.2.1 Cautions.................................................................................................................... 27
6.3 Troubleshooter................................................................................................................. 27
Appendix 1 Wiring Diagram for GST116A FACP.................................................................. 28
Appendix 2 Wiring Diagram for GST108A FACP.................................................................. 30
Appendix 3 Wiring Diagram for GST104A FACP.................................................................. 31
Appendix 4 Wiring Diagram for GST102A FACP.................................................................. 32
Appendix 5 Appearance of GST116A FACP ......................................................................... 33
Appendix 6 Appearance of GST108A FACP ......................................................................... 33
Appendix 7 Appearance of GST104A FACP ......................................................................... 34
Appendix 8 Appearance of GST102A FACP ......................................................................... 34
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 1
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Do not attempt to install, service, or operate this unit until this manual is read and understood.
This equipment must be installed in accordance with these instructions and the appropriate
national, regional and local regulations specific to the country and location of the installation.
Consult with the appropriate Authority Having Jurisdiction (AHJ) for confirmation of the
requirements.
The FACP shall only be installed and serviced by specially trained engineers.
Disconnect all sources of power before servicing. Control unit may be damaged by removing
and/or inserting cards, modules, or interconnecting cables while the unit is energized.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the
enclosure. When possible, make all cable entries from the sides or rear. Before making
modifications, verify that they will not interfere with batteries and printed circuit board location.
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 2
EN 54 Information
GST102A/104A/108A/116A Conventional Fire Alarm Control Panel (FACP) complies
with the requirements of EN 54-2 1997 + A1: 2006 and EN 54-4 1997+A1:
2002+A2:2006. In addition to the basic requirements of these standards, the panel
conforms to the following optional requirements.
Option
EN 54-2 Clause
Control
Delays to outputs
7.11
Test condition
10
Outputs
Output to fire alarm devices
7.8
Output to fire alarm routing equipment
7.9.1
The power supply of the FACP complies with the following EN 54-4 requirements.
Power Supply Functions
EN 54-4 Clause
Power supply from the main power source
5.1
Power supply from the standby power source (batteries)
5.2
Charger
5.3
Faults
5.4
CPD Conformity Information
EN 54
√
EN 54
√
EN 54
√
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Chapter 1 Product Overview
GST102A/104A/108A/116A Conventional Fire Alarm Control Panel is designed in compliance with
EN 54-2. It’s compatible with GST C-9403 Conventional Sounder Strobe designed by EN 54-3,
C-9103 Conventional Rate of Rise and Fixed Temperature Heat Detector by EN 54-5, C-9102
Conventional Photoelectric Smoke Detector by EN 54-7, and DC-9204 Conventional Manual Call
Point by EN 54-11. The panel is easy to install and operate. Control functions are enabled by a
key switch. Programming functions are enabled by a key switch and an internal switch.
This series of panels are basically the same in application and operation, their differences are
shown in Table 1-1. GST108A will be described as the example in the following sections.
Table 1-1
FACP
Number of Detection Zones
Number of Sounder
Outputs
GST102A
2
2
GST104A
4
4
GST108A
8
4
GST116A
16
4
1.1 Features
2 to 16 zones can be detected, compatible with conventional detectors and manual call
points. Each of the 16 detection zones can be individually configured as maximum 15
conventional detectors. The total number of detectors and manual call points in a zone
shall not exceed 32.
4 sounder outputs, 1 alarm output and 1 fault output.
Able to report short circuit and open circuit of detection zones, sounder outputs and alarm
output.
Designed with standby batteries and space provision for two sealed lead-acid batteries.
Test and disable functions.
Day/night mode settable.
Programmable on manual call point connection, sound modes, sounder delay modes and
output delay modes.
Three access levels settable via a key switch and an internal switch.
Reserved repeater panel interface for fire alarm indication of multiple zones.
Providing external ports includes RESET, SILENCE, EVAC and forced Night Mode.
1.2 Technical Specifications
1.2.1 Operating Voltage
Input Voltage: 220V/230VAC+10%
-15%
Frequency: 50/60Hz
Input Current: 0.6 A
Fuse: AC250V, T2A in SPS
Recommended Wiring: 1.5mm2or above shield cable, complying with local installation
codes.
Note: External switch or circuit-breaker and external overcurrent protection devices are
required and should be installed near the equipment.
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 4
1.2.2 Batteries
Minimum Operating Voltage: 21.5V
Maximum Charging Current: 315mA
Maximum Charging Voltage: 27.6V
Battery Type: Sealed lead-acid battery
Maximum Battery Charging Capacity: 2 batteries, 7Ah/12V.
Recommended Battery Manufacturer and Model: Yuasa NP7-12
Maximum internal resistance of the batteries: 1Ω
Standby current of batteries when fully load: 0.1A
Maximum operating current of the batteries: 2.5A
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved fire cables.
1.2.3 Installation Environment
Temperature: 0℃~40℃
Relative humidity≤95%, non-condensing.
1.2.4 Load of Power Supply
The maximum output current in standby condition is 430mA(Max. a as described in Table
1 of EN 54-4 Clause 9.2.1.)
The maximum output current in alarm condition is 2.5A(Max. b as described in Table 1 of
EN 54-4 Clause 9.2.1).
1.2.5 Detection Zone
The FACP provides maximum 16 detection zones; each can be individually configured with
maximum 15 conventional detectors.
Loop Voltage: 15VDC~28VDC
Standby Current: Less than 6mA (connecting with 15 conventional detectors)
Dynamic Current: Resistance range for fire alarm is 150Ω~1.5kΩ(normally 470Ω), using
a 4.7kΩend of line resistor or AEOL (active end of line unit). The alarm current for a zone
depends on the number of conventional devices in the zone. The alarm current for a
conventional detector is about 25mA.
Maximum output current for the 16 detection zones is 400mA.
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved fire cables
Recommended Cable Length: not longer than 1000m
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 5
1.2.6 Output Loop
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved fire cables
Recommended Cable Length: not longer than 1000m
Sounder output (4 channels) and alarm output (1 channel)
Output Voltage: 18VDC~28VDC
Output Current: 300mA for each sounder output, and 300mA for fire alarm output.
End of Line Resistor: 4.7kΩ
Auxiliary Power Output
Output Voltage: 18VDC~28VDC
Output Current: 20mA normally and 500mA under fire condition.
Fault Output: Volt-free contact output, 1A/24VDC
1.2.7 Remote Interface
Recommended Wiring (subject to local installation codes):
GST fire cable
Vencroft Gold and Platignum
Nexans NX 200 and 200 Plus (LPCB tested)
Prysmian FP 200 and 200 Gold
Draka Firetuf and Firetuf Plus
And all LPCB approved Fire cables
Recommended Cable Length: not longer than 1000m
Day mode input, remote EVAC input, remote SILENCE input and remote RESET input:
contact input.
1.3 Controls and Indications
The front panel of the FACP is as in Fig. 1-1.
Fig. 1-1
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 6
1.3.1 Common Status Indicators
FIRE: It illuminates red steadily in fire condition.
Alarm Output: It illuminates red steadily when the alarm output is activated.
Common Fault: It flashes when the system enters a fault state and illuminates yellow
steadily when the system enters safe state or Mute/ACK key is pressed.
System Fault: It illuminates yellow steadily when the CPU is in fault condition. The
system enters safe state at the moment.
Disable: It illuminates yellow steadily if any zone or output is disabled.
Power Supply: It illuminates green steadily when the FACP is powered up.
Delay Mode: It illuminates yellow steadily when the system is in day mode (delay
enabled) and it flashes when there is any output delayed.
Ground Fault: It illuminates yellow steadily when there is ground fault.
Power Fault: It illuminates yellow steadily when the power (including mains, batteries,
charger and internal resistance) is in fault condition.
In Test: It illuminates yellow steadily when a zone is in test condition.
1.3.2 Zone Status Indicators
Zone RED LED: It flashes (0.5:0.5) when the zone is in fire condition. And it illuminates
red steadily after Mute/ACK key is pressed.
Zone AMBER LED: It flashes (0.5:0.5) when the zone is in fault condition. And it
illuminates yellow steadily when the zone is disabled or in test.
1.3.3 Operating Indicators and Keys
5 keys with LEDs
Disable/Enable: Pressing this key can disable or enable an output or a zone and the
LED illuminates green steadily.
Output Program: Pressing this key can set output program mode and the LED
illuminates green steadily.
Test: Pressing this key can set test status and the LED illuminates green steadily.
EVAC: Pressing this key can start all sounders for evacuation and the LED
illuminates red steadily when the sounders are started.
Silence/Resound: Pressing this key can silence all the sounders outputs; pressing
it again in fire condition, the silenced sounders output will be activated again. The
LED illuminates yellow steadily when the sounders are silenced.
5 keys
:Day/Night, for shifting operations and choosing Day or Night mode.
Cancel: For cancellation.
Enter: For confirmation.
Reset: For resetting the control panel.
Mute/ACK: Changing the silence status of the internal buzzer.
1 Control lock
Control Enable: For access level control. If it’s switched to “OFF”position, the
FACP is at the lowest access level, and only function keys under access level 1 are
accessible.
1.3.4 Output Indicators
Sounder 1 Flt/Dis: Yellow. It flashes when Sounder 1 output is in fault condition, and it
illuminates steadily when Sounder 1 output is disabled.
Sounder 2 Flt/Dis: Yellow. It flashes when Sounder 2 output is in fault condition, and it
illuminates steadily when Sounder 2 output is disabled.
Sounder 3 Flt/Dis: Yellow. It flashes when Sounder 3 output is in fault condition, and it
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 7
illuminates steadily when Sounder 3 output is disabled.
Sounder 4 Flt/Dis: Yellow. It flashes when Sounder 4 output is in fault condition, and it
illuminates steadily when Sounder 4 output is disabled.
Alarm Output Flt/Dis: Yellow. It flashes when alarm output is in fault condition and it
illuminates steadily whenAlarm Output is disabled.
1.3.5 Indicators of Control Board
The fault indicators on the control board are shown in Fig. 1-2.
Fig. 1-2
AC- It illuminates yellow steadily when mains power is in fault.
BAT- It illuminates yellow steadily when standby power is in fault.
Char- It illuminates yellow steadily when the internal charger is in fault.
BATR- It illuminates yellow steadily when internal resistance of the batteries is too high.
1.4 Construction and Configuration
1.4.1 Appearance
The appearance of the FACP is shown in Fig. 1-3.
Fault LED
X6
X5, X1, X2, X3, X4
SW2, SW3
X8
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 8
Fig. 1-3
1.4.2 Configuration
The internal construction of the FACP is shown in Fig. 1-4.
Fig. 1-4
①Control board ②Extension board or signal output interface board ③Display board
④Batteries
1.4.2.1 Configuration of GST116A
1.4.2.1.1 Typical configuration
Control board: For controlling power supply, all outputs, detection input and repeater
output for Zone 1 to 8.
Extension board: Providing detection input and repeater output for Zone 9 to 16.
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 9
Display board: For information display and key operation.
Batteries: In case mains power is cut, the FACP can automatically switch to batteries to
provide power supply for uninterrupted operation.
1.4.2.1.2 Optional configuration
Signal output interface board is an optional part of GST116A panel that can replace the extension
board by providing detection input and repeater output for Zone 9 to 16, as well as fire alarm
output and fault output for Zone 1 to 16.
1.4.2.2 Configuration of GST108A
1.4.2.2.1 Typical Configuration
Control board: For controlling power supply, all outputs, detection input, and repeater
output for Zone 1 to 8.
Display board: For information display and key operation.
Batteries: In case mains power is cut, the FACP can automatically switch to batteries to
provide power supply for uninterrupted operation.
1.4.2.2.2 Optional Configuration
Signal output interface board is an optional part for GST108A which provides fire alarm output and
fault output for Zone 1 to 8.
1.4.2.3 Configuration of GST104A
1.4.2.3.1 Typical Configuration
Control board: For controlling power supply, all outputs, detection input, and repeater
output for Zone 1 to 4.
Display board: For information display and key operation.
Batteries: In case mains power is cut, the FACP can automatically switch to batteries to
provide power supply for uninterrupted operation.
1.4.2.3.2 Optional Configuration
Signal output interface board is an optional part for GST104A which provides fire alarm output and
fault output for Zone 1 to 4.
1.4.2.4 Configuration of GST102A
1.4.2.4.1 Typical configuration
Control board: For controlling power supply, all outputs, detection input, and repeater
output for Zone 1 to 2.
Display board: For information display and key operation.
Batteries: In case mains power is cut, the FACP can automatically switch to batteries to
provide power supply for uninterrupted operation.
1.4.2.4.2 Optional Configuration
Signal output interface board is an optional part for GST102A which provides fire alarm output and
fault output for Zone 1 to 2.
1.5 Terminal Description
1.5.1 Terminals on the Control Board
Terminals on the control board are shown in Fig. 1-5.
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 10
Fig. 1-5
REPEATER OUTPUT: Output terminal for repeater panel connection.
PW ON: Power supply positive terminal for repeater panel connection.
COM 0V: Power supply negative terminal for repeater panel connection.
COM DIS: Disablement terminal for repeater panel connection.
COM DAY: Day mode terminal for repeater panel connection.
COM FIRE: Fire alarm terminal for repeater panel connection.
COM FLT: Fault terminal for repeater panel connection.
Z1~Z8: Zone indication terminals of repeater panel for Zone 1 to 8.
AUX SUPPLY (+, -): Auxiliary power terminal.
FAULT OUTPUT (NO, COM, NC): Fault output terminal.
ALARM OUTPUT (+, -): Alarm output terminals.
OUTPUT TO SOUNDER (1~4): Sounders output terminals.
DAY MODE: Day/night mode conversion terminals.
EVAC INPUT: For remote operation of EAVC.
SILENCE INPUT: For remote operation of silence.
RESETINPUT: For remote operation of reset.
BATTERY (+, -): Battery terminals.
L, G ,N: Mains input terminals.
ZONE INPUT (1~8): Zone 1 to 8 input terminals.
1.5.2 Terminals on GST116A Extension Board
Terminals on the extension board of GST116A are shown in Fig. 1-6.
Fig. 1-6
ZONE INPUT (9~16): Zone 9 to 16 input terminals.
Z9~Z16: Zone indication terminals of repeater panel for zone 9 to 16.
COM 0V: Power negative terminal for repeater panel.
1.5.3 Terminals on Signal Output Interface Board of GST116A
Terminals on signal output interface board of GST116A are shown in Fig. 1-7.
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 11
Fig. 1-7
ZONE INPUT 9~16: Input terminals for zone 9 to 16.
Z9~Z16: Indication terminals for zone 9 to 16 of the repeater panel.
COM0V: Power negative terminal of the repeater panel.
FAULT1~FAULT16: Fault output for zone 1 to 16.
ALARM1~ALARM16: Alarm output for zone 1 to 16.
1.5.4 Terminals on Signal Output Interface Board of GST108A
Terminals on signal output interface board of GST108A are shown in Fig. 1-8.
Fig. 1-8
FAULT1~FAULT8: Fault output terminals for zone 1 to 8.
ALARM1~ALARM8: Alarm output terminals for zone 1 to 8.
1.5.5 Terminals on Signal Output Interface Board of GST102A/104A
The terminals on the signal output interface board GST102A/104A are similar to GST108A, only
with fewer outputs connected.
GST102A:
FAULT1, FAULT2: Fault output for Zone 1 and 2.
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 12
ALARM1, ALARM2: Alarm output for Zone 1 and 2.
GST104A:
FAULT1~FAULT4: Fault output for Zone 1 to 4.
ALARM1~ALARM4: Alarm output for Zone 1 to 4.
1.6 Dimensions
380mm×102.7mm×320mm (L X W X H)
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 13
Chapter 2 Installation
2.1 Installing the Cabinet
The FACP is wall-mounted as in Fig. 2-1.
Note: Cable connector should be installed in the knock-out hole to avoid cable abrasion
and foreign objects.
Expansion
Bolt M5x50
Conduit
66mm
344mm
R6mm
R2.5mm
Fig. 2-1
2.2 Mains Connection
220/230VAC, 50/60Hz mains provide supply for GST108A FACP.
The incoming power cable Ground (Green/Yellow) wire should be connected to the Gterminal and
be reliably grounded. Connect the neutral (Blue) wire to terminal N and connect the Live (Brown)
wire to terminal L.
It’s recommended to use 1.5mm2or above shield cable subject to local installation codes.
Note:
The power cables shall be fixed to the enclosure using a restraint clamp for strain
relief.
Do not power the system until the installation is completed.
2.3 Battery Connection
Refer to 5 Calculation of Batteries Capacity for the size of the required batteries.
Connect the batteries as in Fig. 2-2 and then to the battery terminal XT2 on the control board.
Fig. 2-2
ControlBoardBAT-(black)
ControlBoardBAT+ (red)
Fuse F5A250V
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 14
Note:
Do not make battery connections until the installation is completed.
The fuse of the batteries may be broken if the polarity is connected incorrectly.
2.4 Zone Input Connection
Each zone can have maximum 15 fire detectors. The total number of detectors and call points in a
zone should not exceed 32. They can be connected in two ways.
2.4.1 Using end of line resistor
Connect all manual call points in front of the detectors and put a 4.7kΩresistor at the end of the
loop, as shown in Fig. 2-3.
1kΩ
Nominal
MCPPanel
Zone
Input
Terminal
4.7kΩ
Resistor
Detector (No Diode)
1 2
34
Detector (No Diode)
1 2
34
+
-
Fig. 2-3
2.4.2 Using an Active End of Line Unit
If an active end of line unit (AEOL) is used at the end of the loop, then the detectors and manual
call points can be connected at any position. Ensure the detector base is fittedwith a diode to keep
the cable continuity in case any detector is removed, as shown in Fig. 2-4.
1kΩ
Nominal
MCPPanel
Zone
Input
Terminal AEOL
Detector
1 2
34
Detector
1 2
34
+
-
Diode Diode
+
-
Fig. 2-4
2.5 Sounder/Alarm Output Connection
All sounders shall be polarity-sensitive and be connected in correct polarity. A 4.7kΩ resistor shall
be connected in parallel at the end of the loop. Fig. 2-5 shows the connection of Sounder Output 1.
Panel
Zone
Input
Terminal
4.7kΩ
Resistor
+
-
+
-
+
-
Fig. 2-5
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 15
Chapter 3 System Setup
3.1 Setting Access Levels
The FACP provides three access levels:
Level 1, for anybody to silence the buzzer by pressing Mute/ACK key.
Level 2, for person on duty to disable, test, reset the panel, silence the sounders (using
Silence/Resound key) and evacuate the building.
Level 3, for special service engineer to turn on or off the FACP and program output
modes.
3.1.1 Setting Access Level 1
Turning Control Enable lock “OFF”shown as in Fig. 3-1, the FACP is set to access level 1. “1”of
SW2 on control board should be at OFF (LEVEL 3) position as shown in Fig. 3-2. SW2 and SW3
are on the control board shown in Fig. 1-2.
SW2 SW3
Fig. 3-1 Fig. 3-2
(White cell indicates the position of switch)
3.1.2 Setting Access Level 2
Turning Control Enable lock “ON”shown as in Fig. 3-3, the FACP is set to access level 2. “1”of
SW2 should be at OFF position as shown in Fig. 3-2.
Fig. 3-3
3.1.3 Setting Access Level 3
If “1”of SW2 (Level 3) is set to ON position as shown in Fig. 3-4, whichever position the Control
Enable lock is, the FACP is set to access level 3.
SW2 SW3
Fig. 3-4
(White cell indicates the position of switch)
www.acornfiresecurity.com
www.acornfiresecurity.com

GST102A/104A/108A/116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 16
3.2 Setting Sounder/Alarm Output
4 sounder outputs and 1 alarm output can be set through Pins (Pins X1, X2, X3, X4 and X5 is
respectively corresponded to sounder output of zone 1 to 4 and alarm output ) on the control board
to one of the three types including voltage output, normally open contact output or normally closed
contact output. The default setting is voltage output.
3.2.1 Example for Setting Voltage Output
Connecting “2”with “3”and “5”with “6”of Pin X1 using jumpers will set Sounder 1 as voltage
output, refer to Fig. 3-5.
Fig. 3-5
3.2.2 Example for Setting Normally Open Output
Connecting “1”with “2”and “4”with “5”of Pin X3 using jumpers will set Sounder 3 as normally
open contact output, refer to Fig. 3-5.
3.2.3 Example for Setting Normally Closed Output
Connecting “1”with “2”and “3”with “4”of X5 using jumpers will set Alarm Output as normally
closed contact output, refer to Fig. 3-5.
Please refer to Table 3-1 for detailed settings for sounder output and alarm output.
Table 3-1
Output
Normally closed contact
Normally open contact
Voltage output
Jumpers
Jumpers
Jumpers
Sounder 1
X1/ 1&2, 3&4
X1/ 1&2, 4&5
X1/ 2&3, 5&6
Sounder 2
X2/ 1&2, 3&4
X2/ 1&2, 4&5
X2/ 2&3, 5&6
Sounder 3
X3/ 1&2, 3&4
X3/ 1&2, 4&5
X3/ 2&3, 5&6
Sounder 4
X4/ 1&2, 3&4
X4/ 1&2, 4&5
X4/ 2&3, 5&6
Alarm output
X5/ 1&2, 3&4
X5/ 1&2, 4&5
X5/ 2&3, 5&6
3.3 Disablement of a Zone or Output
3.3.1 Use of Disablement Function
In case there is any fault with a detection zone or a sounder/alarm output, it can be disabled so
that it does not affect normal operation of other zones. After the fault is removed, the disabled
detection zone or output can be enabled again. This operation applies to the 16 detection zones, 4
sounder outputs, and 1 fire alarm output.
The setting operation can be indicated by Disable/Enable key & indicator, Disable indicator and
zone indicators. There are instructions for disablement operation on the front panel.
3.3.2 Operation Steps
1 Enter Access Level 2 as described in Section 3.1.2.
2 Pressing Disable/Enable key, Disable/Enable LED illuminates steadily and the amber LED of
Zone 1 starts flashing to show Zone 1 is selected for disablement setup. Common Fault LED
will indicate a system fault condition. Other indicators, except for the above mentioned LEDs,
www.acornfiresecurity.com
www.acornfiresecurity.com
Other manuals for GST102A
1
This manual suits for next models
3
Table of contents
Other GST Control Panel manuals