GST GST-IFP4M User manual


GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page I
CONTENTS
Fire Alarm System Limitations....................................................................................... 1
Installation Precautions.................................................................................................. 3
Notices............................................................................................................................. 5
1Product Introduction ................................................................................................... 6
1.1 Standard Features................................................................................................... 6
1.2 System Limitations .................................................................................................. 6
1.3 Basic Components .................................................................................................. 7
1.4 Optional Components.............................................................................................. 7
1.4.1 LC-401 Single Loop Card.................................................................................. 7
1.4.2 LC-402 Dual Loop Card.................................................................................... 7
1.4.3 P-9966A CAN Class A Network Card................................................................ 7
1.4.4 P-9981 Zone Display Panel .............................................................................. 8
1.4.5 P-9981F Zone Display Panel............................................................................ 8
1.4.6 P-9982 Zone Display and Control Panel........................................................... 8
1.4.7 P-9982F Zone Display and Control Panel......................................................... 8
1.4.8 PR-400 or PR-400B Thermal Printer................................................................. 8
1.4.9 CA-400-R CA-400-W or CA-400-G Cabinet...................................................... 8
1.4.10 P-9983 Fiber-Optical Network Card................................................................ 8
1.4.11 P-9956-Modbus Modbus Card ........................................................................ 8
1.4.12 GST-BAT65-R GST-BAT65-W GST-BAT65-G Battery Box............................. 9
1.5 Peripheral Devices .................................................................................................. 9
Accessories................................................................................................................. 10
1.6 Defining Tool...........................................................................................................11
2Installation.................................................................................................................. 12
2.1 Component Inspection........................................................................................... 12
2.2 Install the Cabinet.................................................................................................. 12
2.2.1 Install the cabinet of panel .............................................................................. 12
2.2.2 Install the cabinet of battery............................................................................ 14
2.3 Install Components................................................................................................ 16
2.3.1 Battery Power ................................................................................................. 16
2.3.2 Installing Circuit modules................................................................................ 18
2.3.3 Installing Zone Display and Control Panel ...................................................... 20
2.3.4 Installing Glass Door....................................................................................... 22
2.3.5 Installation of Labels on the Front Panel......................................................... 23
2.3.6 Installation of Labels on the Zone Display and Control Panel (ZCP) .............. 25
2.4 Start-up Check....................................................................................................... 26
2.5 External Connection.............................................................................................. 26
2.5.1 AC Power Connection..................................................................................... 26

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page II
2.5.2 Battery Connection ......................................................................................... 27
2.5.3 Signaling Line Circuits (SLC) Connection....................................................... 28
2.5.4 Notification Appliance Circuits (NAC) Note: Synchronization of the audible and
visible alarm signal is only provided on a notification circuit basis or on a DI-M9305
controlled zone basis. .............................................................................................. 29
2.5.5 Relays............................................................................................................. 31
2.5.6 INPUT (Limit to non-monitored)...................................................................... 31
2.5.7 CAN Network Connection............................................................................... 32
2.5.8 Optical Network Connection............................................................................ 32
2.5.9 Hybrid Network Connection ............................................................................ 33
2.5.10 Modbus Card Connection ............................................................................. 33
2.5.11 GST-MP Voice Evacuation System Master Panel......................................... 34
2.5.12 GST-MNA2C/GST-MNA2F Network Annunciator.......................................... 34
2.5.13 UL Power-limited Wiring Requirements ........................................................ 35
2.6 Connection Inspection........................................................................................... 37
2.7 Setup FACP and Define Devices........................................................................... 37
2.8 Field Device Commission...................................................................................... 37
3Indication & Control................................................................................................... 38
3.1 LED Indicators....................................................................................................... 38
3.2 Functional keys...................................................................................................... 40
3.3 Service / Program Keys:........................................................................................ 41
3.4 User Interface........................................................................................................ 42
4Operations.................................................................................................................. 45
4.1 Programming on FACP.......................................................................................... 45
4.1.1 Basic Setting................................................................................................... 45
4.1.2 Program.......................................................................................................... 50
4.1.3 Advanced Setting............................................................................................ 60
4.2 Programming the FACP Through GST-IFPx-Def Defining Tool.............................. 62
4.2.1 Download thru USB interface.......................................................................... 62
4.2.2 Download thru Ethernet interface ( the external computer connected must be
located at the same room with the control panel ).................................................... 63
4.2.3 Dongle............................................................................................................. 63
4.2.4 Remote access to read panel status............................................................... 63
4.2.5 Bacnet ( the external device connected must be located at the same room with
the control panel ).................................................................................................... 64
4.2.6 CPU Backup ................................................................................................... 66
4.3 User Setup............................................................................................................. 67
4.3.1 Soft keyboard Setup ....................................................................................... 67
4.3.2 Display Setup.................................................................................................. 67
4.3.3 Test Setup....................................................................................................... 67
4.3.4 Clock Setup..................................................................................................... 68
4.3.5 Print Setup...................................................................................................... 69

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page III
4.3.6 Day/Night Mode.............................................................................................. 69
4.3.7 Language Setup.............................................................................................. 70
4.3.8 Project Information.......................................................................................... 71
5Equipment operation and information browsing .................................................... 72
5.1 Equipment operation ............................................................................................. 72
5.2 Devices information Browsing ............................................................................... 74
5.3 Record Browsing................................................................................................... 79
6Operating Instructions .............................................................................................. 81
6.1 Panel Control Keys................................................................................................ 81
6.1.1 ACKNOWLEDGE (User password)................................................................. 81
6.1.2 SILENCE ALARM (User password)................................................................ 81
6.1.3 MANUAL ALARM (User password)................................................................. 81
6.1.4 RESET (User password)................................................................................. 81
6.2 Positive Alarm Sequence....................................................................................... 82
6.3 Walk Test............................................................................................................... 82
7Default Programming ................................................................................................ 83
Appendix A Basic System Connection ....................................................................... 84
Appendix B Electrical Specifications.......................................................................... 85
B.1 Electrical Specifications......................................................................................... 85
B.1.1 AC Power ....................................................................................................... 85
B.1.2 Battery............................................................................................................ 85
B.1.3 Signaling Line Circuit (SLC)............................................................................ 85
B.1.4 Notification Appliance Circuit (NAC)............................................................... 85
B.1.5 Auxiliary Power (NAC2/AUX programmed as AUX) ....................................... 85
B.1.6 Relays............................................................................................................. 86
B.1.7 Input................................................................................................................ 86
B.1.8 CAN Network.................................................................................................. 86
B.1.9 Fiber-Optical Network..................................................................................... 86
B.2.0 Modbus Communication –for supplementary use only.................................. 86
B.2 Typical Configuration of SLCs............................................................................... 86
Appendix C Compatible Devices................................................................................. 88
C.1 Series Addressable Detectors............................................................................... 88
C.1.1 Smoke Detectors (Photoelectric).................................................................... 88
C.1.2 Heat Detectors ............................................................................................... 88
C.1.3 Combination Heat Photoelectric Smoke Detector .......................................... 88
C.1.4 Detector Bases............................................................................................... 89
C.2 Manual Pull Stations............................................................................................. 89
C.3 Loop Isolators ....................................................................................................... 89
C.4 Control Modules.................................................................................................... 89
C.5 Horn / Strobes / Signal Synchronization Module................................................... 90
C.6 Base...................................................................................................................... 90

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page IV
Appendix D Battery Calculations................................................................................. 91
Appendix E Operating Instructions............................................................................. 94
Limited Warranty........................................................................................................... 95

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 1
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire
insurance!
An automatic fire alarm system –typically made up of smoke detectors, heat detectors,
manual pull stations, Notification Appliances, and a fire alarm control with remote
notification capability–can provide early warning of a developing fire. Such a system,
however, does not assure protection against property damage or loss of life resulting from
a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a
protected premises following the recommendations of the current edition of the National
Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations,
State and local codes, and the recommendations contained in installation and operation
manual of the detectors, which is made available at no charge to all installing dealers. A
study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in as many as 35% of all fires.
While fire alarm systems are designed to provide early warning against fire, they do not
guarantee warning or protection against fire. A fire alarm system may not provide timely or
adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in
chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second-floor
detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing
chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit
particle or smoke flow.
Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls
where detectors are located.
Smoke particles may be blown away from detectors by air outlets.
Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density levels
are not created by a developing fire at the location of detectors, the detectors will not go
into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photoelectric sensing chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast-flaming fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth, neither type of detector is
necessarily best nor may a given type of detector not provide adequate warning of a fire.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 2
Smoke detectors cannot be expected to provide adequate warning of fires caused by
arson, children playing with matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper storage of flammable materials,
etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their
sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time. For this reason, the
rate-of-rise feature of each detector should be tested at least once per year by a qualified
fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the FACP and in
rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on
the other side of closed or partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or those who have recently
consumed drugs, alcohol or medication.
Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do
not respond or comprehend the meaning of the signal. It is the property owner's
responsibility to conduct fire drills and other training exercise to make people aware
of fire alarm signals and instruct them on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or
permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the
system will operate from standby batteries only for a specified time and only if the
batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the FACP. It is
essential to use only equipment listed for service with your FACP.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep
the entire fire alarm system in excellent working order, ongoing maintenance is required
per the manufacturer's recommendations, and UL and NFPA standards. At a minimum,
the requirements of Chapter 10 of NFPA 72 shall be followed. Environments with large
amounts of dust, dirt or high air velocity require more frequent maintenance. A
maintenance agreement should be arranged through the local manufacturer's
representative. Maintenance should be scheduled monthly or as required by National
and/or local fire codes and should be performed by authorized professional fire alarm
installers only. Adequate written records of all inspections should be kept.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm FACP.
Disconnect all sources of power before servicing. Control unit and associated equipment
may be damaged by removing and/or inserting cards, modules, or interconnecting cables
while the unit is energized. Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -System Reacceptance Test after Software Changes. To ensure proper
system operation, this product must be tested in accordance with NFPA 72 Chapter 14
after any programming operation or change in site-specific software. Reacceptance
testing is required after any change, addition or deletion of system components, or after
any modification, repair or adjustment to system hardware or wiring. All components,
circuits, system operations, or software functions known to be affected by a change must
be 100% tested. In addition, to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49°C/32-120°F and at 93% RH
(non-condensing), and applies to be installed in the dry indoor environment.
Like all solid state electronic devices, this system may operate erratically or can be
damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes. Consult with the Technical Services
Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to
do so can damage circuits.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads,
resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This
system contains static-sensitive components. Always ground yourself with a proper wrist
strap before handling any circuits so that static charges are removed from the body. Use
static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the FACP and associated equipment.
FACP (Fire Alarm Control Panel) operation and reliability depend upon proper installation
by authorized personnel.
It is imperative that the installer understands the requirements of the Authority Having
Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory
agencies:
Underwriters Laboratories
NFPA

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 4
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 864 Standard for Control Units and Accessories for Fire Alarm Systems

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 5
Notices
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES:
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, certain programming features or options must be limited to specific
values or not used at all as indicated below.
Program feature
or option
Permitted in
UL 864? (Y/N)
Possible settings
Settings permitted in
UL 864
Output type of
NACs
Y
Steady: a continuous output
with no coding.
March Time: 120 ppm
(pulse-per-minute) output.
Synch: a continuous output
with synchronized pulse
signal.
Temporal: Temporal-3
pattern.
“Synch” - for
compatible strobes
and horns connected
to NAC1 or NAC2
“Temporal” - for
compatible bells
connected to NAC1 or
NAC2
Output type of
AUX
Y
AUX, AUX SYNC
“AUX SYNC” - for
DI-M9305 controlled
NAC solution
“AUX” - for 24Vdc
Auxiliary power output
NAC1 NAC2
silencing
Y
Silenceable,
Non-Silenceable
Silenceable
Cause & Effect
Delay
(Output module
delay)
Y
0 –300 seconds
0 second - for
required fire signaling,
e.g. DI-M9305
controlled NAC
solution
0 –300 seconds - for
supplementary
process controls.
Consult with AHJs for
permissible
applications.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 6
1Product Introduction
GST-IFP4M is an Intelligent Fire Alarm Control Panel (FACP) designed for medium- to
large-scale facilities. It complies to UL 864 standard with features of easy installation,
operation, and maintenance. The FACP integrates an ARM7-Cotex CPU with inbuilt Linux
OS. Its friendly and graphical screen can be touchable in operation.
Inventory
The FACP is delivered with all components installed. When the shipment is received,
check to make certain that all accessories have been included:
Cabinet key
Manual
1.1 Standard Features
The FACP provides the following:
Advanced Protocol mode with 1~6 loops which meets Class A requirements.
242 addressable devices (include sensors, modules and manual call points) per loop.
Two Power-Limited Class B Notification Appliance Circuits (NAC).
Built-in three fixed relays: Alarm, Supervisory, Trouble .
Built-in two programmable relays which can be set as Alarm, Supervisory, Trouble,
Disable function.
Battery charger supports up to 66 amp hour sealed lead-acid batteries
LCD display unit of 800×480,7.0 inch color TFT LCD.
Capacitive Touch screen.
History file with 100,000 events capacity.
Advanced history filters allow sorting by event, time, date, address etc.
Up to 1000 powerful Logic Equations.
Network operation.
Ground fault detection.
Walk test, silent or audible.
PAS (Positive Alarm Sequence) per point (NFPA 72 compliant).
Password and key-protected nonvolatile memory.
User programmable password.
Field-programmable on panel, or by external computer with GST-IFPx-Def Defining
Tool and connected via Ethernet / USB port on SD-400 LCD Drive Board.
1.2 System Limitations
System expansion must take into consideration the following:
The physical limitations of the cabinet configuration.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 7
The electrical limitations of the system power supply.
The capacity of the secondary power source (standby batteries).
1.3 Basic Components
A basic FACP requires at least the following components:
A PSU-250 Main Power Supply
Supply power to the whole panel and connected devices. Monitor the status of AC
power, battery and charger, switch power between AC power and battery.
A Battery
The FACP uses only sealed lead-acid batteries for standby power. Maximum battery
capacity is 66 AH (ampere-hour). Minimum battery capacity depends upon your
system configuration; absolute minimum is 12 AH.
A Display and Keypad Module
This module includes LCD, Touch screen, display driver board, LED, Keypad board.
It provides information in graphic and word, and customers can operate the panel
using real keys and touch screen.
A Main Box Module
This module is the heart of the FACP. It includes a mother board, a CPU card, a NAC
card and a Loop card.
An Enclosure with door
The enclosure can conclude a power supply, a host cabinet, two batteries of
12V/38Ah. A display and keypad module and 8 ZCPs can be installed on the door.
1.4 Optional Components
1.4.1 LC-401 Single Loop Card
Single Loop Card has one completely Class A SLC compatible with Digital Protocol Bus.
The loop can connect maximum 242 devices. Users can add up this card to extend loop if
necessary.
1.4.2 LC-402 Dual Loop Card
Dual Loop Card has two completely Class A SLCs compatible with Digital Protocol Bus.
Each loop can connect maximum 242 devices. Users can add up this card to extend loop
if necessary.
1.4.3 P-9966A CAN Class A Network Card
The network card is essential accessory for the FACP to be networked by inserting the
card into the slot of the panel’s motherboard. Many separate FACPs can form a fire
alarm network through the card. Each panel supports Max three network cards working
simultaneously and these 3 cards can be combination of P-9966A and P-9983. Please
refer to Section2.5.7 for wiring and setting information.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 8
1.4.4 P-9981 Zone Display Panel
Zone Display Panel is used to indicate a related zone, or device states of fire, fault and
isolation. Each zone display panel can show 20 zones or devices, and every 2 indicators
for one zone or device. The user can write or print descriptions on a label for a zone, and
then put the label into the transparent box of the zone display panel.
1.4.5 P-9981F Zone Display Panel
Zone Display Panel is used to indicate a related zone, or device states of fire, fault and
isolation. Each zone display panel can show 20 zones or devices, and every 2
indicators(monochromatic led) for one zone or device. The user can write or print
descriptions on a label for a zone, and then put the label into the transparent box of ZCP.
1.4.6 P-9982 Zone Display and Control Panel
Zone Display and Control Panel is used to indicate a related zone, or device states of fire,
fault and isolation. It can also be used to disable, enable, start and stop the related
devices. Each zone display panel can show 20 zones or devices, and every 2
indicators(double color led) and 1 key for one zone or device. The user can write or print
descriptions on a label for a zone, and then put the label into the transparent box of ZCP.
1.4.7 P-9982F Zone Display and Control Panel
Zone Display and Control Panel is used to indicate a related zone, or device states of fire,
fault and isolation. It can also be used to disable, enable, start and stop the related
devices. Each zone display panel can show 20 zones or devices, and every 2
indicators(monochromatic led) and 1 key for one zone or device. The user can write or
print descriptions on a label for a zone, and then put the label into the transparent box of
ZCP.
1.4.8 PR-400 or PR-400B Thermal Printer
PR-400 or PR-400B Thermal Printer is optional. It can be directly connected to the FACP
through RS232. This printer, with its panel embedded, can be installed on the front panel
of the FACP. It can print running record of the FACP. It’s easy to operate and convenient
for checking.
1.4.9 CA-400-R CA-400-W or CA-400-G Cabinet
Either CA-400-R, CA-400-W or CA-400-G Cabinet is required. The CA-400-R Cabinet is
red, CA-400-W Cabinet is white and the CA-400-G is gray.
1.4.10 P-9983 Fiber-Optical Network Card
P-9983 card is optional for GST-IFP4M control panel, providing two LC single-mode fiber
interfaces. This card provides the same function as P-9966A CAN Class A network card.
Transmission distance is longer when this card is used to network control panels.
1.4.11 P-9956-Modbus Modbus Card
P-9956-Modbus Modbus Card is optional for supplementary use in GST-IFP4M control
panel, providing standard Modbus interface for transmitting logs or history for
maintenance purposes P-9956-Modbus Modbus Card has three types of one interface:
RS232, RS485 or RS422.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 9
1.4.12 GST-BAT65-R GST-BAT65-W GST-BAT65-G Battery Box
As the control panel requires the battery with the capacity over 38Ah, an external battery
box can be used. The battery with large capacity can be placed in the box. The largest
capacity for the battery in the box is 65Ah.
The GST-BAT65-R is red, GST-BAT65-W is white and the GST-BAT65-G is gray.
1.5 Peripheral Devices
The following tables list all the devices available for the FACP.
Table 1 Series Addressable Detectors
Type
Description
I-9102(UL)
Intelligent Photoelectric Smoke Detector
I-9103(UL)
Intelligent Rate of Rise and Fixed Temperature Heat Detector
DI-M9101
Intelligent Combination Heat Photoelectric Smoke Detector
DI-M9102
Intelligent Photoelectric Smoke Detector
DI-M9103
Intelligent Rate of Rise and Fixed Temperature Heat Detector
DC-M9101*)
Conventional Combination Heat Photoelectric Smoke Detector
DC-M9102*)
Conventional Photoelectric Smoke Detector
DC-M9103*)
Conventional Rate of Rise and Fixed Temperature Heat Detector
C-9314P*)
Passive Remote Indicator
BP-9314P*)
Back Plate
DZ-03
Base for I-9102(UL) , I-9103(UL) detectors
DB-M01
Base for DI-M9101, DI-M9102, DI-M9103 , DC-M9101, DC-M9102,
DC-M9103 detectors
*) Note: Conventional detectors are to be connected through DI-M9319 Digital Zone
Monitor Module.
Table 2 Manual Call Points
Type
Description
DI-M9204
Digital Manual Call Point
DC-M9204
Innovation Manual Call Point
Table3 Input/Output Modules
Type
Description
I-M9300
Addressable Input Module
I-M9301
Addressable Output Module
DI-M9300
Digital Single Input Module

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 10
DI-M9301
Digital Single Input and Output Module
DI-M9305
Digital Single Riser Output Module
Table4 Digital Zone Monitor Module
Type
Description
DI-M9319
Digital Zone Monitor Module
Table5 Loop Isolator Module
Type
Description
DC-M9503
Loop Isolator Module
C-M9503
Loop Isolator
DC-M9504
Base Mount Isolator
Table6 Compatible Notification Appliances
Type
Quantity(max)
Description
DC-M9414W/ DC-M9414R
62
Horn
DC-M9415W/ DC-M9415R
24
Strobe
DC-M9413W/ DC-M9413R
19
Horn / Strobe
DC-M9416W/ DC-M9416R
17
SSM24-6
78
Bells
Table7 Compatible Voice Evacuation System Master Panel
Type
Description
GST-MP
Voice Evacuation System Master Panel
Table8 Compatible Network Annunciators
Type
Description
GST-MNA2C
CAN Interface Network Annunciator
GST-MNA2F
Fiber Interface Network Annunciator
Accessories
GST Series Hand Held Programmer
P-9910B Hand Held Programmer can read the address, sensitivity and device type and
program device type of addressable detectors and modules.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 11
The handheld programmer has to be separately ordered.
1.6 Defining Tool
GST-IFPx-Def Defining Tool is used for setting panel and network configuration, editing
and downloading definition of device and C&E equation. Before the system starts
operation, you need to set panel and network configuration, define the device and C&E
using this software on a computer, and then download them to the FACP.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 12
2Installation
This chapter describes the installation of the FACP. The steps below are guidance for
installation of the FACP.
1 Check if you have received all items ordered.
2 Install the cabinet.
3 Install the component (basic and optional).
4 Power up the FACP and check if it can be normally started.
5 External connection.
6 Check the lines.
7 Setup FACP and define devices using GST-IFPx-Def Defining Tool on a PC and
download them to the FACP according to engineering configuration.
8 Check and commission peripheral devices.
2.1 Component Inspection
Before installation, check the following items:
Check Engineering Requirement
Check the packing list according to engineering requirement. The main items to be
examined are: installation and operation manual, key to the FACP, battery wires, terminal
resistor and etc.
Check Internal Components and Interconnection inside the FACP
All basic internal parts have been connected (including power supply box, mother board,
main board, interface board and main front panel) before the FACP leaves the factory.
Therefore, you can mainly check the optional units ordered and the connection among
parts, including the connection between mother board and power supply, mother board
and key board, the connection of the zone indication panel with key board, etc. Please
refer to Appendix A for the internal connection diagram.
2.2 Install the Cabinet
2.2.1 Install the cabinet of panel
The cabinet mounts using three 12mm-diameter holes located in the back box. Carefully
unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be
readily accessible with sufficient room to easily install and maintain the panel. Locate the
cabinet at a proper height above the floor with the hinge mounting on the left.
The FACP can be flush-mounted or wall-mounted. The dimensions for wall-mounting are
shown in following Fig 2.1
Mark and predrill holes in the wall for the three keyhole mounting bolts using the

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 13
dimensions illustrated in following Fig 2.1.
Fig 2.1
Install three fasteners in the wall with the screw heads protruding.
Using upper ‘keyhole’ place back box over the three screws, level and secure.
Hole distance for flush-mounting: 815mm x 490mm x 144mm. Dimensions for
flush-mounting are shown in following Fig 2.2.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 14
Fig 2.2
2.2.2 Install the cabinet of battery
User needs the external cabinet of battery when battery capacity is more than 38Ah.The
battery cabinet is installed below the panel cabinet as Fig 2.3. The wiring from battery
cabinet is connected to panel through knockout. This connection is recommended. User
can choose other knockouts to connect the two cabinets according actual situation. The
battery cabinet can be flush-mounted or wall-mounted also. The dimensions for
wall-mounting are shown in following Fig 2.4. Dimensions for flush-mounting are shown in
Fig 2.5.Hole distance for flush-mounting: 560mm x 490mm x 144mm.

GST-IFP4M Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 15
Fig 2.3
Fig 2.4
Table of contents
Other GST Control Panel manuals
Popular Control Panel manuals by other brands

CAME
CAME ZLX24S instruction manual

Menvier Security
Menvier Security TS400 operating instructions

Bentel Security
Bentel Security Academy 4 Programming guide

DMP Electronics
DMP Electronics XR550 series installation guide

Simon
Simon Beta Test 7/9/01 manual

Honeywell
Honeywell Galaxy 18Galaxy Programming manual

Unitech
Unitech R16 Installer manual

Johnson Controls
Johnson Controls FRICK QUANTUM LX AcuAir maintenance

OPTIBEAM
OPTIBEAM 1605-WK200 instructions

Beckhoff
Beckhoff CP70 Series Installation and operating instructions

Bentel Security
Bentel Security KYO 320 installation manual

Cisco
Cisco TelePresence Touch 8 installation guide