GST GST102A User manual


GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page I
QUICK OPERATION GUIDE
PANEL FAULT
BUZZER:
Press the “SILENCE BUZZER” button to silence the
panel fault buzzer.
For any of the below functions you must be in Access Level 2 mode
ACCESS LEVEL
2 MODE:
Insert the 003 key and turn to the “ON” position.
PANEL ALARM
BUZZER:
Press the “SILENCE BUZZER” button to silence the
panel alarm buzzer.
WARNING
SYSTEM
ACTIVATION:
Press the “EVAC” button for manual activation of the
warning system. Alternatively, if an alarm has been
activated press the “SILENCE/RESOUND ALARM”
button to silence and reactivate the warning system.
FIRE MODE
DISABLING:
To disable zones in fire mode, press “SILENCE/RESOUND
ALARM” then “DISABLE” to disable all zones that have
been activated in fire mode.
DISABLING
ZONES:
Press the “DISABLE/ENABLE” button.
Use the “SCROLL” button to cycle through to the
desired zone or sounder output.
Press the “ENTER” button to save, Panel buzzer will
sound for 1s to indicate successful setup.
Press the “SCROLL” button to continue to addition
zones/sounder outputs.
Press the “CANCEL” or “DISABLE/ENABLE” to exit
this menu.
DISABLING
WARNING
SYSTEM:
Press the “DIS/ENABLE WARNING SYSTEM” button.
ENABLEMENT:
Repeat the disablement procedure above.
PANEL RESET:
Press the “RESET” button.
EXIT:
Turn the 003 key to the “OFF” position and remove
key.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page II
CONTENTS
Installation Precautions ............................................................................................................... 1
EN 54 Information........................................................................................................................ 2
Chapter 1 Product Overview ....................................................................................................... 3
1.1 Features............................................................................................................................. 3
1.2 Technical Specifications .................................................................................................... 3
1.2.1 Operating Voltage ....................................................................................................... 3
1.2.2 Batteries ...................................................................................................................... 4
1.2.3 Load of Power Supply................................................................................................. 4
1.2.4 Detection Zone............................................................................................................ 4
1.2.5 Output Interface .......................................................................................................... 4
1.2.6 Input Interface ............................................................................................................. 5
1.2.7 Installation and Storage .............................................................................................. 6
1.3 Controls and Indications .................................................................................................... 6
1.3.1 Common Status Indicators.......................................................................................... 6
1.3.2 Zone Status Indicators ................................................................................................ 7
1.3.3 Operating Indicators and Keys ................................................................................... 7
1.4 Configuration and Functions.............................................................................................. 8
1.4.1 Internal Components................................................................................................... 8
1.4.2 Configuration and Functions of GST-116A . ............................................................... 8
1.4.3 Configuration and Functions of GST-108A................................................................. 9
1.4.4 Configuration and Functions of GST-104A................................................................. 9
1.4.5 Configuration and Functions of GST-102A................................................................. 9
1.5 Terminal Description .......................................................................................................... 9
1.5.1 Terminals on the Control Board .................................................................................. 9
1.5.2 Terminals on Extension Board .................................................................................. 10
1.5.3 Terminals on Relay Board of RB116A .......................................................................11
1.5.4 Terminals on Relay Board of RB108A .......................................................................11
1.6 Appearance and Dimensions........................................................................................... 13
Chapter 2 Installation and Wiring .............................................................................................. 14
2.1 Installing the Cabinet ....................................................................................................... 14
2.2 Mains Connection ............................................................................................................ 16
2.3 Battery Connection .......................................................................................................... 16

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page III
2.4 Zone Input Connection .................................................................................................... 17
2.4.1 Using end of line resistor .......................................................................................... 17
2.4.2 Using an Active End of Line Unit .............................................................................. 17
2.5 Sounder/Fire Alarm Output Connections......................................................................... 17
Chapter 3 System Setup ........................................................................................................... 18
3.1 Setting Access Levels...................................................................................................... 18
3.1.1 Setting Access Level I............................................................................................... 18
3.1.2 Setting Access Level II.............................................................................................. 18
3.1.3 Setting Access Level III............................................................................................. 18
3.2 Setup of the Sounder / Alarm Output .............................................................................. 18
3.3 Disablement of a Zone or Output .................................................................................... 19
3.3.1 Use of Disablement Function.................................................................................... 19
3.3.2 Operation Basic Steps – Generally used for individually Disabling Zones or Sounder
/Alarm Outputs when the panel is in normal operation mode............................................ 20
3.3.3 Quick Disablement Function – Generally used for group Disablements of Zones or
Sounder Outputs when the panel is in Alarm mode. ......................................................... 20
3.4 Setting Test Mode............................................................................................................ 21
3.4.1 Use of Test Mode ...................................................................................................... 21
3.4.2 Operation Steps ........................................................................................................ 21
3.4.3 Test zone output mode.............................................................................................. 22
3.5 Programming Output Modes ........................................................................................... 22
3.5.1 Setting Zone “With Manual Call Point”...................................................................... 22
3.5.2 Setting Associated Sounders to a Zone ................................................................... 23
3.5.3 Setting Delay Time of Alarm Output.......................................................................... 24
3.5.4 Sounder Output Mode............................................................................................... 24
3.6 Supervisory Mode............................................................................................................ 26
3.6.1 Use of Supervisory Function..................................................................................... 26
3.6.2 Programming a Zone to Supervisory ........................................................................ 26
3.7 Setting Auxiliary Functions .............................................................................................. 27
3.8 Ground Fault Detection.................................................................................................... 27
3.9 Auxiliary Power Setting.................................................................................................... 27
3.10 Restore Default Settings................................................................................................ 28
Chapter 4 Operation Instructions .............................................................................................. 29
4.1 Working State Description ............................................................................................... 29

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page IV
4.1.1 State of Detection Zones .......................................................................................... 29
4.1.2 Alarm Output State.................................................................................................... 29
4.1.3 Sounder Outputs State ............................................................................................. 29
4.1.4 Safe State ................................................................................................................. 29
4.1.5 Description of the Buzzer.......................................................................................... 30
4.1.6 Others........................................................................................................................ 30
4.2 Acknowledgement and Silence of Fault .......................................................................... 31
4.3 Acknowledgement and Silence of Fire Alarm.................................................................. 31
4.4 Silencing the Sounder Outputs........................................................................................ 31
4.5 Evacuation ....................................................................................................................... 31
4.6 Self-test and Reset .......................................................................................................... 31
Chapter 5 Calculation of Batteries Capacity ............................................................................. 32
Chapter 6 Servicing................................................................................................................... 33
6.1 Replacing the Batteries.................................................................................................... 33
6.2 Replacing the Fuses ........................................................................................................ 33
6.2.1 Follow the Steps Below to Replace F1 ..................................................................... 33
6.2.2 Follow the Steps Below to Replace 5A Fuse............................................................ 33
6.3 Troubleshooting ............................................................................................................... 34
Compliance information............................................................................................................. 35
WEEE Information..................................................................................................................... 36
Limited Warranty ....................................................................................................................... 37
Product warnings and disclaimers ............................................................................................ 37

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 1
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Do not attempt to install, service, or operate this unit until this manual is read and understood.
This equipment must be installed in accordance with these instructions and the appropriate
national, regional and local regulations specific to the country and location of the installation.
Consult with the appropriate authority having jurisdiction for confirmation of the requirements.
The CIE shall only be installed and serviced by specially trained fire alarm system technicians.
Disconnect all sources of power before servicing. The CIE may be damaged by removing
and/or inserting cards, modules, or interconnecting cables while the unit is energized.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the
enclosure. When possible, make all cable entries from the sides or rear. Before making
modifications, verify that they will not interfere with batteries and printed circuit board location.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 2
EN 54 Information
GST102A/104A/108A/116A Conventional Fire Alarm Control Panel (FACP) complieswith
the requirements of EN 54-2 1997 + A1: 2006 and EN 54-4 1997+A1: 2002+A2:2006. In
addition to thebasic requirements of these standards, the panel conforms to the following
optional requirements.
Option
EN 54-2 Clause
Control
Delays to outputs
7.11
Test condition
10
Outputs
Output to fire alarm devices
7.8
Output to fire alarm routing equipment
7.9.1
The power supply of GST102A/104A/108A/116A complies with the following EN 54-4
requirements.
Power Supply Functions
EN 54-4 Clause
Power supply from the main power source
5.1
Power supply from the standby power source (batteries)
5.2
Charger
5.3
Faults
5.4
CPD Conformity Information
2831
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao,
Hebei, P. R. China 066004
11
GST102A 2831-CPR-F4050
GST104A 2831-CPR-F4051
GST108A 2831-CPR-F4049
GST116A 2831-CPR-F4052
EN 54-2 1997 + A1: 2006
EN 54-4 1997 + A1: 2002 + A2: 2006
Control and indicating equipment for fire detection and fire
alarm systems for buildings
Provided Options:
Delays to outputs
Test condition
Output to fire alarm devices
Output to fire alarm routing equipment
Please refer to this manual for other technical data.
EN 54
√
EN 54
√
EN 54
√

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Chapter 1 Product Overview
GST102A/104A/108A/116A Conventional Fire Alarm Control Panel is designed in compliance with
EN 54-2. It’s compatible with GST C-9403 Conventional Sounder Strobe designed by EN 54-3, C-
9103 Conventional Rate of Rise and Fixed Temperature Heat Detector by EN 54-5, C-9102
Conventional Photoelectric Smoke Detector by EN 54-7, and DC-9204 Conventional Manual Call
Point by EN 54-11. The panel is easy to install and operate. Control functions are enabled by a key
switch. Programming functions are enabled by a key switch and an internal switch.
This seriesofpanels are basically the same in applicationand operation, their onlymain differences
being the amount of zones and the size of the cabinets, see table 1-1.
Table 1-1
FACP
Number of Detection
Zones
Number of Sounder
Outputs
GST102A
2
3
GST104A
4
3
GST108A
8
3
GST116A
16
3
1.1 Features
Supports up to 16 detection zones, with conventional detectors and manual call points;
the maximum number of external conventional points per zone is 32.
Three sounder outputs, one alarm output, one fault output and one disable/supervisory
output.
Able to report short and open circuits of zones, sounder outputs and alarm output.
Test and disable functions
Programmable on manual call point connection, sound modes, sounder delay modes and
output delay modes.
Three access levels settable via the key switch and the internal switch.
Reserved repeater panel interface for fire alarm indication of multiple zones.
Designed with standby batteries and space provision for two sealed lead-acid batteries.
The maximum number of points per CIE as shown in Table 1-2.
FACP
GST102A
GST104A
GST108A
GST116A
Max points
≤64
≤128
≤256
<512
1.2 Technical Specifications
1.2.1 Operating Voltage
Input Voltage: 220V/230VAC+10%
-15%
Frequency: 50/60Hz
Input Current: 0.8 A
Fuse: 250VAC, T2A in SPS
Recommended Wiring: 1.5mm2 or above of shield cable, complying with local installation
code.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 4
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: External overcurrent protection device is required and should be installed
near the equipment.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
1.2.2 Batteries
Minimum Operating Voltage: 21.5V
Maximum Charging Current: 400mA
Maximum Charging Voltage: 27.6V
Battery Type: Sealed lead-acid battery
Minimum Batteries: 2 batteries, 7Ah/12VDC
Recommended Battery and Model: Yuasa NP7-12
Standby battery maximum operating current: 2.5A
Standby battery current with full-loaded: 0.1A
Maximum Internal Resistance: 1.0Ω
1.2.3 Load of Power Supply
The maximum output current in standby condition is 550mA (Max. a as described in Table
1 of EN 54-4 Clause 9.2.1.)
The maximum output current in alarm condition is 2.35A (Max. b as described in Table 1
of EN 54-4 Clause 9.2.1).
The Minimum output current in fully charged condition is show in Table1-3 (I Min. as
described in Table 1 of WN54-4 Clause, 9.2.1)
Table 1-3
FACP
GST102A
GST104A
GST108A
GST116A
I min(mA)
40
50
70
110
1.2.4 Detection Zone
The controlpanel supports up to 16 detection zones, and the number of external conventional
detectors in each zone reaches 32, with the following parameters:
Loop Voltage: 15VDC~28VDC
Maximum output current per zone: 170mA.
Dynamic Current: Resistance range for fire alarm is 150Ω~1.5kΩ(normally 470Ω), using
a 4.7kΩend of line resistor or AEOL (active end of line unit). The alarm current for a zone
depends on the number of conventional devices in the zone. The alarm current for a
conventional detector is about 25mA.
Maximum output current for the 16 detection zones is 400mA.
Recommended Wiring: 1.0mm2or above 2 core cable, complying with local installation
codes.
Recommended Cable Length: no more than 1000m
1.2.5 Output Interface
Fault Output
➢Type: normally open/close contact output

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 5
➢Contact capacity: 1A/24VDC
Disable/Supervisory Output (defaulted disable output)
➢Type: normally open/close contact output
➢Contact capacity: 1A/24VDC
Alarm output
➢Type: voltage contact output, normally open/close contact output are available,
(defaulted normally open contact output)
➢Contact capacity: 1A/24VDC
➢Output voltage: 18VDC~28VDC
➢Output current: 300mA in alarm
➢End-of-line-resistor: 4.7kΩ
Sounder output 1
➢Type: voltage contact output, normally open/close contact output (defaulted voltage
contact output)
➢Contact capacity: 1A/24VDC
➢Output voltage: 18VDC~28VDC
➢Output current: 300mA in alarm
➢End-of-line-resistor: 4.7kΩ
Sounder 2/3 output
➢Type: voltage contact output
➢Output voltage: 18VDC~28VDC
➢Output current: 300mA in alarm
➢End-of-line-resistor: 4.7kΩ
Auxiliary Power Output
➢Output Voltage: 18VDC~28VDC
➢Output current: 450mA in standby mode and Maximum 1000mA in alarm mode when
the Alarm Output has been set to a normally open/close contact type. (Refer 3.2)
Repeater output
➢Type: open-collector output
➢Output Voltage: 18VDC~28VDC
Recommended Wiring: 1.0mm2or above 2-core cable, complying with local installation
codes. Please refer to repeater panel instruction manual for installation and wiring
requirements.
Recommended Cable Length: no longer than 1000m
1.2.6 Input Interface
RESET/EVAC/SILENCE input
➢Type: normally open contact input
Recommended Wiring: 1.0mm2 or above 2-core cable, complying with local installation
codes.
Recommended Cable Length: no longer than 1000m

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 6
1.2.7 Installation and Storage
The control panel is applicable for indoor use below the elevation of 2000m. Overvoltage level is
Class II and pollution degree is 2. Ingress protection level is IP30.
Installation Environment
Temperature: 0℃~40℃
Relative humidity≤95%, non-condensing
Storage Environment:
Temperature: -5℃~50℃
Relative humidity≤95%, non-condensing
1.3 Controls and Indications
The fascia of the GST-116A is shown below in Fig. 1-1.
There is no Control Enable 003 key-switch used on the large cabinet version panels as Access
Level 2 is achieved when opening the front door (with glass window) which has a 003 lock.
Fig. 1-1
1.3.1 Common Status Indicators
FIRE: Red. It flashes when there is fire alarm and illuminates steadily when the fire sound
is silenced.
ALARM ROUTING ACTIVATED: Red. It illuminates steadily when the alarm output is
activated.
POWER: Green. It illuminates steadily when the CIE is powered up.
FAULT: Yellow. It flashes when there is a fault and illuminates steadily when the fault
sound is silenced or the CIE enters safe state.
DISABLE: Yellow. It illuminates steadily if any zone, sounder output or alarm routing
output is disabled.
SUPERVISED: Yellow. It flashes when any zone defined as supervisory is activated. It
illuminates steadily when the supervisory sound is silenced.
IN TEST: Yellow. It illuminates steadily when any zone is in test condition.
MAINS FAULT: Yellow. It flashes when there is mains fault and illuminates steadily when
the fault sound is silenced.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 7
BATTERY FAULT: Yellow. It flashes when there is battery fault and illuminates steadily
when the fault sound is silenced.
CHARGER FAULT: Yellow. It flashes when there is charger fault and illuminates steadily
after the fault sound is silenced.
EARTH FAULT: Yellow. It flashes when any cable of sounder output (voltage contact),
alarm routing output, auxiliary power output or zone input, connects with the enclosure of
the panel. It illuminates steadily when the fault sound is silenced.
SYSTEM FAULT: Yellow. It illuminates steadily when the CPU is in fault condition or CPU
communication is abnormal.
DELAY MODE: Yellow. It flashes when there is an alarm output or sounder output in
delayed condition.
BUZZER MUTE: Yellow. It illuminates steadily when the buzzer is silenced.
SILENCE: Yellow. It illuminates steadily when the sounders are silenced.
SOUNDER 1 FLT/DIS: Yellow. It flashes when Sounder 1 output is in fault condition, and
it illuminates steadily when Sounder 1 output is disabled.
SOUNDER 2 FLT/DIS: Yellow. It flashes when Sounder 2 output is in fault condition, and
it illuminates steadily when Sounder 2 output is disabled.
SOUNDER 3 FLT/DIS: Yellow. It flashes when Sounder 3 output is in fault condition, and
it illuminates steadily when Sounder 3 output is disabled.
ALARM OUTPUT FAULT: Yellow. It flashes when alarm output is in fault condition, and it
illuminates steadily when Alarm output is disabled.
1.3.2 Zone Status Indicators
ZONE RED LED: Red. It flashes when a zone is in fire condition(0.5:0.5). And it
illuminates steadily after Mute/ACK is pressed.
ZONE AMBER LED: Yellow. It flashes when the zone is in fault condition(0.5:0.5). And
it illuminates steadily when the zone is disabled or in test mode.
ZONE SUPERVISED LED
(
Z1~Z16
)
: It illuminates GREEN when the zone is defined
as a supervisory type. (Factory Default, refer to Chapter 3.6.2 for programming
instructions). This feature is typically used for pump running and pump stopped
indications.
1.3.3 Operating Indicators and Keys
Keys
➢SILENCE BUZZER: In Access Level I and access level II, fault sound, supervisory
sound, and an alarm sound can be silenced.
➢SILENCE/RESOUND ALARM: Pressing this key can silence all the sounders outputs;
pressing it again in fire condition, the silenced sounders output will be activated again.
The LED illuminates yellow steadily when the sounders are silenced.
➢RESET: It is available in Access Level II for resetting the control panel.
➢DISABLE: It is available in Access Level II. Pressing this key can disable all zones
with a fire condition. Note: The warning system must first be silenced in order for this
button to operate.
➢DIS/ENABLE WARNING SYSTEM: It is available in Access Level II. Pressing this
key can disable/enable all sounder outputs.
➢SCROLL: It is available in Access Level II for scrolling to choose.
➢CANCEL: It is available in Access Level II for cancellation.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 8
➢ENTER: It is available in Access Level II for confirmation.
Keys with LEDs
➢EVAC: It is available in Access Level II. Pressing this key can start all sounders for
evacuation and the LED illuminates yellow steadily. Press key again to cancel.
➢DISABLE/ENABLE: It is available in Access Level II. Pressing this key can disable
or enable an output or a zone and the LED illuminates yellow steadily.
➢OUTPUT PROGRAM: It is available in Access Level III. Pressing this key can set
output program and the LED illuminates yellow steadily.
➢TEST: It is available in Access Level II. Pressing this key can set test status and the
LED illuminates yellow steadily.
Control Lock
➢CONTROL ENABLE: If it’s switched to the “OFF” position, the CIE is at the access
level 1. If it’s switched to the “ON” position, the CIE is at the access level 2. The 003
key is not removable in access level 2
1.4 Configuration and Functions
1.4.1 Internal Components
The internal construction of the CIE cabinets is shown in Fig. 1-2.
Fig. 1-2
○
1 Display board ○
2 Optional relay board or zone extension board for 16 zone panel
○
3 Control board ○
4 Batteries
1.4.2 Configuration and Functions of GST-116A .
GST-116A control panels have the following configuration and functions.
Batteries: Standby power source for the CIE.
Control board: For controlling power supply, charger, and all outputs such as
fault/disable/supervisory relay output, alarm output, sounder outputs and repeater panel
for zone 1 to 8, and monitoring the state of zone 1 to 8.
Extension board: Providing detection input and repeater output for zone 9 to 16.
4 3 2 1

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 9
Display board: For information display and key operation.
Relay board (optional): Providing detection input and repeater output for zone 9 to 16.
Controlling outputs of alarm relay and fault relay for zone 1 to 16.
1.4.3 Configuration and Functions of GST-108A
GST-108A control panels have the following configuration and functions.
Batteries: Standby power source for the CIE.
Control board: For controlling power supply, charger, and all outputs such as
fault/disable/supervisory relay output, alarm output, sounder outputs and repeater panel
for zone 1 to 8, and monitoring the state of zone 1 to 8.
Display board: For information display and key operation.
Relay board (optional): Controlling outputs of alarm relay and fault relay for zone 1 to 8.
1.4.4 Configuration and Functions of GST-104A.
GST-104A control panels have the following configuration and functions.
Batteries: Standby power source for the CIE.
Control board: For controlling power supply, charger, and all outputs such as
fault/disable/supervisory relay output, alarm output, sounder output and repeater panel for
zone 1 to 4, and monitoring the state of zone 1 to 4.
Display board: For information display and key operation.
Relay board (optional): Controlling outputs of alarm relay and fault relay for zone 1 to 4.
1.4.5 Configuration and Functions of GST-102A
GST-102A control panels have the following configuration and functions.
Batteries: Standby power source for the CIE.
Control board: For controlling power supply, charger, and all outputs such as
fault/disable/supervisory relay output, alarm output, sounder outputs and repeater panel
for zone 1 to 2, and monitoring the state of zone 1 to 2.
Display board: For information display and key operation.
Relay board (optional): Controlling outputs of alarm relay and fault relay for zone 1 to 2.
1.5 Terminal Description
1.5.1 Terminals on the Control Board
Note: The contents of italics are not covered in EN54-2/4.
Terminals for batteries are shown in Fig. 1-3.
BATTERY
Fig. 1-3
BATTERY (+, -): Battery input terminals.
Other terminals on the control board are shown in Fig. 1-4.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 10
REPEATER OUTPUT
Z8Z7Z6Z5Z4Z3Z2Z1
FLT
FIRE
MUTE
0V
PW
RESET
INPUT
EVAC
INPUT
SILECE
INPUT
FAULT
NC COM NO 1
DIS./SUP
NC COM NO ALARM SOUNDER OUTPUT AUX
2 3
Z1
ZONE
INPUT
Z2 Z5
Z4 Z7
Z8Z6
Z3
Fig. 1-4
FAULT (NC, COM, NO): Fault output terminal.
DIS. / SUP. (NC, COM, NO): Disable/supervisory terminal.
ALARM OUTPUT (-, +): Alarm output terminal.
SOUNDER OUTPUT (1~3) (-, +): Sounder output terminals.
AUX SUPPLY (-, +): Auxiliary power terminal.
REPEATER OUTPUT (Z1~Z8): Output terminals of repeater panel for zone 1 to 8.
FLT: Fault terminal for repeater panel connection.
FIRE: Fire alarm terminal for repeater panel connection.
MUTE: Mute terminal for repeater panel connection.
0V: Power supply negative terminal for repeater panel connection.
PW ON: Reserve terminal for repeater panel connection.
RESET INPUT: For remote operation of reset.
EVAC INPUT: For remote operation of EVAC.
SILENCE INPUT: For remote operation of silence.
ZONE INPUT (1~8): Zone 1 to 8 input terminals.
1.5.2 Terminals on Extension Board
Note: The contents of italics are not covered in EN54-2/4.
Terminals on the extension board are shown in Fig. 1-5 and Fig. 1-6.
9ZONE INPUT
11 1210 13 14 15 16
Fig. 1-5
REPEATER OUTPUT
Z11
Z10
Z9
Z12
Z13
Z14
Z15
Z16
0V

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 11
Fig. 1-6
ZONE INPUT (9~16): Zone 9 to 16 input terminals.
Z9~Z16: Output terminals of repeater panel for zone 9 to 16.
0V: Power supply negative terminal for repeater panel connection.
1.5.3 Terminals on Relay Board of RB116A
Note: The contents of italics are not covered in EN54-2/4.
Terminals on relay board of RB116 are shown in Fig. 1-7 and Fig. 1-8.
REPEATER OUTPUT
Z11
Z10
Z9
Z12
Z13
Z14
Z15
Z16
0V
9
ZONE
INPUT
10 13
12 15
1614
11
Fig. 1-7
ALARM6 ALARM7
FAULT11
FAULT1
FAULT12
FAULT2
ALARM8 ALARM9
FAULT13
FAULT3
FAULT14
FAULT4
ALARM10 ALARM11
FAULT15
FAULT5
FAULT16
FAULT6
ALARM12 ALARM13
ALARM1
FAULT7
ALARM2
FAULT8
ALARM14
ALARM3
FAULT9
ALARM15 ALARM16
ALARM4
FAULT10
ALARM5
Fig. 1-8
ZONE INPUT 9~16: Zone 9 to 16 input terminals.
Z9~Z16: Output terminals of repeater panel for zone 9 to 16.
0V: Power supply negative terminal for repeater panel connection.
FAULT1~FAULT16: Fault output terminals for zone 1 to 16.
ALARM1~ALARM16: Alarm output terminals for zone 1 to 16.
1.5.4 Terminals on Relay Board of RB108A
Terminals on relay board of RB108A are shown in Fig. 1-9. Relay board of RB104A/RB102A is
similar to RB108A with fewer terminals.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 12
FAULT1 FAULT2 FAULT3 FAULT4 FAULT5 FAULT6 FAULT7 FAULT8
ALARM1 ALARM2 ALARM3 ALARM4 ALARM5 ALARM6 ALARM7 ALARM8
Fig. 1-9
FAULT1~FAULT8: Fault output terminals for zone 1 to 8.
ALARM1~ALARM8: Alarm output terminals for zone 1 to 8.

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 13
1.6 Appearance and Dimensions
The appearance of control panel is shown in Fig. 1-10. Its dimensions are 430mm×98mm×
320mm (L×D×H).
Fig. 1-10

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 14
Chapter 2 Installation and Wiring
2.1 Installing the Cabinet
The FACP is wall-mounted as in Fig 2-1A.
Note: Cable connector should be installed in the knock-out hole to avoid cable abrasion
and foreign objects.
The below diagrams show the mounting holes for both the small version cabinets (Fig 2-1B).
Fig. 2-1A
Conduit
Expansion
Bolt M5x50
(Unit: mm)

GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 15
Fig. 2-1B
Other manuals for GST102A
1
This manual suits for next models
3
Table of contents
Other GST Control Panel manuals