manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GST
  6. •
  7. Control Unit
  8. •
  9. GST I-9319 User manual

GST I-9319 User manual

Other GST Control Unit manuals

GST C-9302C User manual

GST

GST C-9302C User manual

GST I-9308 User manual

GST

GST I-9308 User manual

GST I-9305 User manual

GST

GST I-9305 User manual

GST I-9300 User manual

GST

GST I-9300 User manual

GST DI-M9300 User manual

GST

GST DI-M9300 User manual

GST P-9903 User manual

GST

GST P-9903 User manual

GST DC-9503E User manual

GST

GST DC-9503E User manual

GST DI-9300E User manual

GST

GST DI-9300E User manual

GST I-9300 User manual

GST

GST I-9300 User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

HTTP://WWW.HOMBI.RU
30303457 Issue 4.01
Features
Cable checking.
Occupying one address, this can be modified
through P-9910B programmer or fire alarm control
panel.
Power cut checking.
Two LEDs indicate fire and fault condition
separately.
Plug-in structure.
Description
I-9319 Addressable Zone Monitor Unit (the unit) is
designed to connect with conventional detectors,
occupying one address. When any device in the loop
reports fire signal, the unit will transmit the signal to the
fire alarm control panel which generates fire alarm and
displays the address of the unit.
The end of the unit is connected with P-9907 Active
End of Line Unit, if the output circuit is broken, the fault
signal will be transmitted to the fire alarm control panel
and then the address of the unit will be displayed on the
fire alarm control panel. When a field device is removed,
the unit will report fault without affecting normal
operation of other field devices.
Connection and Wiring
Terminals of the unit are shown in Fig. 1.
910 15 16
8721
Z2D2 Z1D1
O- O+
Mounting
Hole Mounting
Hole
Mounting
Direction
Fig. 1
Z1, Z2: Connecting with control panel loop cable,
polarity insensitive.
D1, D2: Connecting with 24VDC, polarity insensitive.
O-, O+: Polarity sensitive output.
Recommended Wiring
1.0mm2or above fire cable for each terminal, subject to
local codes. The color of cables for O-and O+ should
be different.
Installation
The unit is simply plugged onto the base after
corresponding terminals are connected.
If the cable conduit is inside the wall, the base is
installed onto the electric box (Fig. 2). If the cable
conduit is on the surface of the wall, B-9310 Back Box
is available (Fig. 3).
Conduit Electric
Box
B-9310
Back Box
Conduit
the Unit the Unit
Fig.2 Fig.3
Please note the upward arrow for mounting direction
(Fig. 1).
Application
Address can be set in field through P-9910B
programmer. The output loop can connect up to 15
conventional devices. Detectors, such as C-9102
Photoelectric Smoke Detector, C-9103 Rate of Rise and
Fixed Temperature detector can be used together.
1. When the unit connects with conventional detector
in series, the detector base should connect with an
1N5819 diode, and P-9907 must be connected to the
output end. P-9907 can also be used as the base of a
conventional detector. System composition is shown in
Fig. 4.
O-
O+
Diode Diode
Conventional Detector Conventional Detector P-9907 Active End of Line Unit
AddessableZoneMornitorUnit
I-9319
Fig. 4
2. When P-9907 Active End of Line Unit is not used as
detector base, a cover should be added, the system
composition is shown as Fig. 5.
The Intelli
g
ent Solution
I-9319
Addressable Zone Monitor Unit
HTTP://GSTRU.RUE-MAIL: [email protected]
HTTP://WWW.HOMBI.RU
30303457 Issue 4.01
O-
O+
AddressableZoneMonitorUnit
Diode Diode
Conventional Detector Conventional Detector P-9907 Active End of Line Unit
I-9319
Fig. 5
3. If the output end connects with terminal resistor, the
diode will not be added to the detector base, system
composition is shown in Fig. 6.
O-
O+
Conventional Detector Conventional Detector
AddressableZoneMonitorUnit
I-9319
4.7kΩ Terminal Resistor
Fig. 6
Specification
Operating Voltage Loop: 24V
Power:24VDC
Quiescent Current Loop≤0.5mA Power≤10mA
Action Current Loop ≤5mA Power≤60mA
Addressing Electronic addressing within
1~242.
LED Alarm LED: Red, illuminates in
alarm condition.
Fault LED: Yellow, illuminates
in fault condition.
Ingress Protection
Rating IP30
Operating
Temperature -10℃~+50℃
Relative Humidity ≤95%, non condensing
Material and Color
of Enclosure ABS, Traffic white (RAL9016)
Dimension
(L×W×H) 120mm×80mm×43mm
Weight About 191g (with base)
Accessories and Tools
Model Name Remark
P-9910B Hand Held
Programmer Supplied separately
B-9310 Back Box Supplied separately
Limited Warranty
GST warrants that the product will be free from defects
in design, materials and workmanship during the
warranty period. This warranty shall not apply to any
product that is found to have been improperly installed
or used in any way not in accordance with the
instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not in
the position to amend the contents of this warranty.
Please contact your local distributor for products not
covered by this warranty.
GST China
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
Fax: +86 (0) 335 8508942
[email protected]
www.gst.com.cn
GST UK
Global System Technology PLC
Lion Court, Staunton Harold Hall,
Melbourne Road, Ashby de la Zouch,
Leicestershire, England LE65 1RT
Tel: +44 1283 225 478
Fax: +44 1283 220 690
[email protected]
www.gst.uk.com
GST Dubai
Global System Technology PLC
PO Box 17998 Unit ZA04
JEBELALI Free Zone,
Dubai, UAE
Tel: +971 (0) 4 8833050
Fax: +971 (0) 4 8833053
[email protected]
www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.