© 2017 United Technologies Corporation 1 / 2 P/N 30310838-EN • REV 001 • ISS 27MAR17
DC-M9414 Series Wall Mount
Sounder Installation Sheet
Description
The DC-M9414 Series Wall Mount Sounder is an audible fire alarm
notification appliance that is designed for mounting on indoor walls.
See Table 1 for a list of model numbers.
Table
1: Models
Description
Model number
Sounder,
white DC-M9414W
Sounder, red
DC-M9414R
The DC-M9414 Series Wall Mount Sounder includes field-configurable
jumper options for selecting:
• Temporal or steady sounder output (see Figure 1 item 1)
• High dB or low dB output (see Figure 1 item 2)
Installation
Install and wire this device in accordance with applicable national and
local codes, ordinances, and regulations.
Caution: Electrical supervision requires breaking the wire run at each
terminal. Do not loop the signaling circuit field wires around the
terminals.
To install the sounder:
1. Remove the cover by depressing both tabs on the top of the unit
with a small screwdriver and twisting slightly.
2. Set the sounder signal and sound output level to desired settings.
See Figure 1.
3. Connect the sounder terminals to the signal circuit field wiring.
Observe polarity for the unit to function properly. See Figure 2.
4. Mount the unit onto a compatible electrical box, making sure not to
overtighten the mounting screws.
5. Replace the cover by aligning at the bottom, then snapping in at
the top.
6. Test the unit for proper operation.
Figure 1: Sounder settings
(1) To change the sounder signal from temporal to steady, cut from
circle J2 to edge of circuit board
(2) To change the sounder sound output level from high dB to low
dB cut J3 by snipping the board trace between holes
Figure 2: Wiring diagram
(1) From NAC output
(2) To next appliance, EOLR, or return to source
Note: Polarity is shown in the alarm condition.
Maintenance
Caution: To maintain the required agency listings, do not change
factory applied finishes.
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a year or as
directed by the local authority having jurisdiction.
Specifications
Operating Voltage
Regulated 16 to 33 VDC, 16 to 33 VFWR
Current
Alarm
Operating
40 mA at 24 VDC
See Table 3
Sound level output
See Table 2
Audible directional
characteristics
See Table 4 and Table 5
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical
boxes
Single-gang box, 2-1/2 in. (64 mm) deep
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
J2 J3
J1
(1) (2)
(1) (2)
2 / 2 P/N 30310838-EN • REV 001 • ISS 27MAR17
Table 2: Sound level output (dBA)
Signal and voltage
Low High
Temporal
16 VDC 76.0 81.4
24 VDC 79.4 84.4
33 VDC 82.1 86.3
Continuous
16 VDC 80.1 85.5
24 VDC 83.5 88.6
33 VDC 86.5 90.4
UL 464: Sound level output
at 10 ft. (3.05 m) measured in a
reverberant room.
Table 3: Operating current in RMS (A)
Voltage
High
Low
16 VDC
0.026 0.019
24
VDC 0.036 0.027
33 VDC
0.041 0.033
16 VFWR
0.051 0.037
24 VFWR
0.069 0.052
33 VFWR
0.076 0.070
VDC = Volts direct current, regulated and filtered
VFWR = Volts full wave rectified
Table 4: Audible directional characteristics (horizontal pattern)
Angle (°) [1]
Sound output (dBA) [2]
−
90 94
−
45 97 (−6)
−
30 100 (−3)
90
103
30
100 (3)
45
97 (6)
90
96
[1] Angles are measured from a perpendicular axis; positive angles to
the right
[2] Peak output at 24 VDC, set for temporal tone.
Table 5: Audible directional characteristics (vertical pattern)
Angle (°) [1]
Sound output (dBA) [2]
−
90 94
−
40 97 (−6)
−
25 100 (−3)
90
103 dBA
35
100 (3)
45
97 (6)
90
96
[1] Angles are measured from a perpendicular axis; positive angles are
up.
[2] Peak output at 24 VDC, set for temporal tone.
Certification and compliance
UL rating
Regulated 24 DC and Regulated 24 FWR [1]
Environmental
class
UL: Indoor, Dry
North American
standards
UL 464
[1] This device was tested to the regulated 24 DC/FWR operating
voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these
values for system operation.
Contact information
For information or questions, please contact:
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel +86 (0) 335 8502434
Fax +86 (0) 335 8502532
[email protected]
www.gst.com.cn

This manual suits for next models

2

Other GST Security System manuals

GST DI-9204E User manual

GST

GST DI-9204E User manual

GST GST116 User manual

GST

GST GST116 User manual

GST DC-M9204F User manual

GST

GST DC-M9204F User manual

GST 8903 User manual

GST

GST 8903 User manual

GST I-9407 User manual

GST

GST I-9407 User manual

GST GST200N User manual

GST

GST GST200N User manual

GST DI-9204E User manual

GST

GST DI-9204E User manual

GST I-9405 User manual

GST

GST I-9405 User manual

GST I-9403 User manual

GST

GST I-9403 User manual

GST DI-9204E Owner's manual

GST

GST DI-9204E Owner's manual

GST DC-9204 User manual

GST

GST DC-9204 User manual

GST C-9403 User manual

GST

GST C-9403 User manual

Popular Security System manuals by other brands

Smanos KP-20 user manual

Smanos

Smanos KP-20 user manual

Eldes EWS1 manual

Eldes

Eldes EWS1 manual

Furuno BR-500 Product guide

Furuno

Furuno BR-500 Product guide

FIRETRACE FTILPINTHTBI operating manual

FIRETRACE

FIRETRACE FTILPINTHTBI operating manual

Vicon NOVA VI 422 Programming manual

Vicon

Vicon NOVA VI 422 Programming manual

Vpon VP-8000 user manual

Vpon

Vpon VP-8000 user manual

Velleman CAMSET13 manual

Velleman

Velleman CAMSET13 manual

Samsung SME-2220N Quick user manual

Samsung

Samsung SME-2220N Quick user manual

ADVANCED Network Devices Smart IP Strobe Installations

ADVANCED Network Devices

ADVANCED Network Devices Smart IP Strobe Installations

ADEMCO Vista-10SEa user guide

ADEMCO

ADEMCO Vista-10SEa user guide

Adtech DCA 114 instruction manual

Adtech

Adtech DCA 114 instruction manual

Klaxon Nexus 120 AC installation instructions

Klaxon

Klaxon Nexus 120 AC installation instructions

RCF MU 7100EN owner's manual

RCF

RCF MU 7100EN owner's manual

stabo multifon security II user manual

stabo

stabo multifon security II user manual

ETS STWI5-SE2 instructions

ETS

ETS STWI5-SE2 instructions

FireAngel Wi-Safe 2 P-LINE Series Installation & user guide

FireAngel

FireAngel Wi-Safe 2 P-LINE Series Installation & user guide

Marmitek SAFEGUARD user guide

Marmitek

Marmitek SAFEGUARD user guide

iSmartAlarm iCamera Quick installation manual

iSmartAlarm

iSmartAlarm iCamera Quick installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.