IMPORTANT INFORMATION ABOUT LOW VOLTAGE WIRE
The only wire acceptable for use with GTO products is 16 gauge multi-stranded, low voltage, PVC
sheathed wire. This particular gauge enables the transformer to provide an adequate charge through the
control board to the battery at distances up to 1000 ft.
DO NOT use telephone wire or solid core wire. Unlike multi-stranded wire, these types of wire are
inadequate for use with your gate opener system. Telephone wire and solid core wire do not deliver
enough voltage for your gate opener to function and will cause the system to go into a condition known
as "low voltage lockout."
NEVER splice wires together. Splicing permits corrosion and seriously degrades the wire's ability to
carry an adequate current.
Step 5
Strip 3/16" off the ends of the low voltage wire and
twist tightly. Attach these ends to the GTO TRANSF
(GTOTransformer)terminalslocatedonthePOWER
INPUTS (GTOTransformer)terminalblock(see
illustration at right). Be certain not to let the
exposed wires touch each other!
Insert one transformer wire into an GTO TRANSF
terminal. Insert the other transformer wire into the
remaining GTO TRANSF terminal. The transformer
wires can be connected to the GTO TRANSF
terminals regardless of color or polarity.
Tighten set screws against exposed end of wires. A
dab of household petroleum jelly on each terminal will
help prevent corrosion.
~~
ORGBLUEWHTGRN BRN RED
MASTER INPUTS
BLK
SOLAR
or
18 VAC
ORGBLUEWHTGRN BRN RED
SLAVE INPUTS
BLK
LOCK
GTO AUX
GTO
TRANSF
LOCK
PWR
AUX
RLY
POWER
INPUTS
CONTROL
OUTPUTS
MASTER CABLESLAVE CABLE
Power Cable
from Master Arm
RED
BLACK
RED
BLACK
Low Voltage Wire
from AC Transformer
or Solar Panel
Low Voltage Wire
from Transformer
or Solar Panel
PVC Pipe
Power Cable
from Master Arm
12 V Battery
RECEIVER
25
FUSE
BATT+
BATT-
1 2 3 4
ON DIP
RECEIVER
LEARN
MAST LIMIT
LEARN
SLV LIMIT
S3
S4
ALM
S2
MASTER INPUTS
SOLAR
or
18VA C
SLAVEINPUTS
LOCK
GTOAUX
GTO
LOCK
PWR
AUX
RLY
POWER
INPUTS
CONTROL
OUTPUTS
MASTER CABLESLAVE CABLECONTROLINPUTS
AUTO CLOSE TIME STALL FORCE
WARNING! DO NOT PLUG THE TRANSFORMER
INTO AN OUTLET DURING THIS STEP! THE
TRANSFORMER MUST ONLY BE PLUGGED INTO
AN OUTLET DURING STEP 7!
Step 3
Lay the measured length of low voltage wire in a trench following a path
from the selected electrical outlet to the control box. Wires coming up
fromthegroundshouldberunthroughPVCconduittoprotectthemfrom
lawn mower blades, weed eaters, and grazing animals. Be sure to bury the
wire laid in the trench.
Step 4
Feed the low voltage wires upward through the strain relief opening on the
lowerleftofthecontrolbox.Pull6"to8"ofwireintothecontrolboxand
tighten the strain relief screw to secure the wires.