5
Installing and removing a fan tray 风扇模块的安装与拆卸
Using the LSWM1BFANSC fan tray
采用LSWM1BFANSC风扇模块
Using the LSWM1BFANSCB fan tray
采用LSWM1BFANSCB风扇模块
6
Install a fan tray安装风扇 Remove a fan tray拆卸风扇
Installing and removing a power module 电源模块的安装与拆卸
Remove a power module拆卸电源模块
Install a power module安装电源模块
Remove a filler panel 拆卸假面板
Install a filler panel 安装假面板
Connecting the power cord 连接电源线
1
2
1
2
1
The LSWM1BFANSC fan tray provides forward airflow from the power module side to the port
side. The fan tray handles are blue. The LSWM1BFANSCB fan tray provides reverse airflow
from the port side to the power module side. The fan tray handles are red.
LSWM1BFANSC为吹风风扇,风向为电源侧进风,端口侧出风,风扇把手为蓝色LSWM1BFAN
SCB为抽风风扇,风向为端口侧进风,电源侧出风,风扇把手为红色。
Before installing a fan tray, make sure the airflow direction marked on the fan tray meets the
ventilation requirements at the installation site.
安装风扇模块前,请根据风扇模块的风向指示,确认气流方向和安装环境的通风要求一致。
When you install a fan tray, make sure the "TOP" mark is on the top surface of the fan tray.
安装风扇模块时,请确保“TOP”丝印朝上。
The switch comes with the fan tray slots empty. You must install two fan Trays of the same model
for the switch for adequate heat dissipation. Do not power on the switch when no fan tray is
installed.交换机出厂时两个风扇插槽均为空,为保证设备的正常散热,用户必须安装两个相同型号
的风扇模块,否则禁止交换机上电运行。
If both fan trays fail when the switch is operating, finish replacing the fan trays within 1 minute.
设备运行过程中,如果两个风扇模块均出现故障,则必须在1分钟内完成故障风扇模块的更换。
If one fan tray fails when the switch is operating and the ambient temperature is not higher than
27°C (80.6°F), replace the fan tray within 24 hours, and make sure the faulty fan tray is in position
before replacing it. If the ambient temperature is higher than 27°C (80.6°F), replace the fan tray
immediately. 设备运行过程中,如果一个风扇模块出现故障,则当环境温度不高于27℃时,必须在
24小时内完成故障风扇模块的更换,且更换前需保持故障风扇模块在位;当环境温度高于27℃时,
请立即进行更换。
Make sure each hot swappable module slot is installed with a module or filler panel when the
switch is operating.
设备运行过程中,必须确保所有可插拔模块插槽不能为空,请务必安装相应的模块或假面板。
!
Install a filler panel in an Empty power module slot to prevent dust from entering the chassis and
ensure good ventilation.若电源模块插槽没有安装电源模块,请及时安装假面板,以保证设备的良好
通风散热并防止灰尘进入交换机。
Before connecting the power cord, connect the grounding cable and make sure the switch is
reliably grounded. 在连接电源线前,需先连接保护地线,保证交换机正确接地。
Connect the power cord to the switch first and then to the power source to avoid bodily injury.
连接电源线时,请先完成电源线与交换机侧的连接,再进行电源线与供电系统的连接,以免造成人
身伤害。
!
Airflow through the switch 交换机的风向设计
The switch provides front-to-back and back-to-front air aisles. Select fan trays to provide airflow
from the power module side to the port side, or from the port side to the power module side based
on the ventilation requirements at the installation site.
交换机采用前后风道设计,通过安装不同的风扇模块,可提供“电源侧到端口侧”和“端口侧到电源侧”
两种气流方向,满足不同环境下的散热要求。