When Tr>Ts+2℃, the compressor run continuously with indoor fan motor running in
accordance with the wind speed setting.
When Ts-1 ≤Tr ≤Ts + 2 ℃, the compressor will cycle for 10 minutes on and 6 minutes off,
When Tr < Ts-1, the compressor will shut off, and the fan motor runs at low speed.
Timer on, Timer off control are available.
5.1.3 Fan mode:
The temperature set unavailable.
Fan motor running in accordance with the speed setting.
The compressor shut off.
Timer on, Timer off control are available.
5.2 Control function:
5.2.1 Self-checking function: All indicators come on and the nixie tube displays no other than
"8" at the first power-on. The unit turns to the waiting state 3 seconds later.
5.2.2 Timer function:
You can set 24-hour timer on or timer off as required, and the minum time unit is 1 hour.
After setting, the indicator of indoor unit is on , and it is off when timer setting is completed.
There are several timer mode as follows.
⑴Timer on: The LED of “timer on” lights up, and unit behaves with halt status. Timer on
is completed, and then unit starts running with the LED of “timer on” off. The unit starts with
the the last setting receiving timer signals, and sleep setting is not allowed.
⑵Timer off: Unit starts, timer indicator lights up; When reaching time setting, the
indicator goes out, unit enters shut down mode, and sleep function can be set. If timer off and
sleep are set synchronously, the one which time is short run first. Executing shutdown
instruction clear timer and sleep function.
⑶Timer on and timer off can be set only one mode at the same time.
5.2.3 Abnormity Diagnose
1. Sensor diagnose: 2 seconds after the sensors open circuit or short circuit, the unit will
turn off automatically and the LED will show E0 until the sensors resume.
2. Keystroke circuit error diagnose: When power on for the first time, the PCB will check
the keystroke circuit, if the sampling value is different with the theory value, the LED will show
E1, which means failed keystroke circuit. The keyboard is locked and so invalid, but the
remote control is working normally.
5.2.4 Power failure resume(please set and apply as necessary)
If sudden power failure occurs, the unit will resume original operation when power is
supplied again.
Note:
When sudden power failure happens during unit operation in power failure resume mode,
if the air conditioner is not desired for use in a long period, please shut off the power supply in
case that the unit automatically resume operation when power is re-supplied, or press
POWER to turn off the unit when power resumes.