7. Wiring Diagram
【High Voltage Warning】
【Precautions Before Operation】
The control box is equipped with high-voltage components
Please turn off the power and keep the unit shut down for more than 10 minutes and ensure that voltage
between P and N on the frequency conversion board is reduced to DC 20V or less before checking the
inside of the control box.
·It is not allowed to connect the power line to the P and Q terminals. These terminals are used to connect the
control signal lines.After connection, the printed circuit board will be burned.
·After the initial installation, please confirm that the power supply voltage of the indoor unit and outdoor unit is
normal.
Before trial operation, ensure that the outdoor unit is powered on for more than 12 hours to fully warm up the
compressor.
·When the outdoor unit leaves the factory, the dial code BM1_1 is set to the OFF state by default.
The commissioning personnel shall confirm that the number of indoor unit displayed on the display board is
consistent with the number of indoor unit actually connected and the type of power supply and outdoor unit capacity
are consistent with the parameters marked on the outdoor unit nameplate, then this dial is set to the ON state;If it is
inconsistent, the outdoor unit cannot detect some indoor unit or the dial setting of the outdoor unit is wrong.
At this time, do not force the dial to ON, which will cause the unit to malfunction or damage.
L N
P Q
【
Wiring Diagram
】
Control
Board
P
ACL
HPS
P
LPS TD TE
(1)
TC TS TA
ACN
BM1BM2
CN1
CN19
PTC
CN2 CN3 CN4 CN5 CN6 CN7
LED4
LED3
LED1
LED2 PC
CN29 CN28
CN21
CN24
CN10
CN9
CN8
PMV
CN30
6.3A 250VAC
FUSE1
CN18
CN17
CN16
CN25
CN15
CN12
ACFAN2
SW1SW3
SW4
DCFAN1
SW2
HEATER
4WV
SV1
NO
12345678
NO
12345678
M
【
High Voltage Warning
】
red
indoor communication
white
green
green
green
red
red
red
red
red
red blue
blue white
white
white
CN20
white
white
CN11
white
black yellow blue red
red
red
red
white
white
CN14
ACFAN1
white
CN13 DCFAN2
yellow
white
ACL
DK2
DK1
black
U
V
W
COMP
compressor
red
black
white
frequency conversion board
Tfin
CN11
CN1
E
reactor
white
Display
Board
CN31 CN32
CN30
SW01
LD1 LD2 LD3
SW02
white
white
red
0150541652
CN13
ACL’
ACN’
M
DC FAN
ACN
JP3
CN12
white
white
yellow/green
【Precautions Before Operation】
·After the initial installation, please confirm that the power supply voltage of the indoor unit and outdoor unit is normal.
Before trial operation, ensure that the outdoor unit is powered on for more than 12 hours to fully warm up the compressor.
·When the outdoor unit leaves the factory, the dial code BM1_1 is set to the OFF state by default.
·It is not allowed to connect the power line to the P and Q terminals. These terminals are used to connect the control
signal lines.After connection, the printed circuit board will be burned
The commissioning personnel shall confirm that the number of indoor unit displayed on the display board is consistent with
the number of indoor unit actually connected and the type of power supply and outdoor unit capacity are consistent with
the parameters marked on the outdoor unit nameplate, then this dial is set to the ON state;If it is inconsistent,
the outdoor unit cannot detect some indoor unit or the dial setting of the outdoor unit is wrong.
At this time, do not force the dial to ON, which will cause the unit to malfunction or damage.
[1][2][3][4][5][6][7][8]
-1 1 0 0 0 0 0
0
4.0
01 0 0 5.0
0 0 0 0
BM1
BM2
dial
model
【
Dial Code Description
】
1
O represent OFF
1 represent ON
-
represent need to be setting when installing
ACL
ACN
HEATER
SV1
SV2
4WV
CA
DCFAN1
DCFAN2
LED1-4
SW1-4
symbol description
Live line
Neutral line
Compressor heating belt
Unloading solenoid valve
Jet solenoid valve
Four-way valve
AC fan capacitor
DC fan above
DC fan below
Indicator light
button
BM1,2
Dip switch
【Symbol Description】
HPS
TD
TE(1)
TS
TA
PMV
LD1-3
SW01,02
symbol description
High pressure switch
LPS
Low pressure switch
Exhaust temperature sensor
Defrost temperature sensor
Intake temperature sensor
TC
Tube temperature sensor
outdoor temperature sensor
Electronic expansion valve
Digital display tube
Rotary dial
PC
PC connection tooling
Tfin
Module temperature sensor
1
The control box is equipped with high-voltage components
Please turn off the power and keep the unit shut down for more than 10 minutes and ensure that voltage between P and N
on the frequency conversion board is reduced to DC 20V or less before checking the inside of the control box.