Heyuan Intelligence IOT-L2S-C1 User manual

LoRaWAN Data
Transmission Terminals
Model IOT-L2S-C1
User Manual
(V1.0)
Heyuan Intelligence Technology Co., Ltd

Copyright © 2018 Heyuan Intelligence Technology Co.,Ltd All Rights Reserved
This manual may not be reproduced, copied, transmitted or transcribed in whole or in part
by any means without the expressed written permission of Heyuan.
IMPORTANT DECLARATIONS
1. This document is an instruction manual. Its content will change as product is upgraded
without notice. Please contact with Heyuan Intelligence Technology Co., Ltd to get the latest
product specifications if it is needed.
2. Heyuan shall not be responsible or liable for any damages or injuries caused by imp roper
meter installation and/or operation.
3. Please read this manual carefully before the product is operated, and once you start,
you’ll be considered to have read this manual and accept all our terms.
Contents
Chapter 1 Product Introduction …………………………………………..……………………………...1
Chapter 2 Features and Function …………………………………………..……………………………1
2.1 Function Introduction ………………………………………………………….……………...1
2.2 Technical Parameter…………………………………………………………………………..2
2.3 Selection Table …………………………………………………………..……………………2
2.4 Parameters Configuration ……………………………………………….…….…..………...2
Chapter 3 Installation Introduction……………………..………………………………………………..4
3.1 Dimension ………………………………………………………….…………………………4
3.2 Terminal Definition ………………………………………………………….………………5
Chapter 4 Typical Application ………………………………….………………………….……..………5
4.1 Application System Examples……………………………………………..…….…………..5
4.2 Application Areas………………………………………………………………….…………..5
Chapter 5 After-sales Service ……………………..……………………………………………………..6
Chapter 6 Contact Us ……………………..……………………………………………………………….6

1
Chapter 1 Product Introduction
The LoRa Data Transmission Terminal, Model No.IOT-L2S-C1 is universal communication
interactive equipment which is designed and manufactured by our company based on the
LoRa RF chip. It integrates two interfaces of industrial standard RS485 and supports a
variety of protocols to realize data transmission between wired and wireless devices. It
transmits the data of the wired device to the product and then transmits the data wirelessly
through RS485 communication lines.
The product can be widely applied in the IOT, centralized metering and industrial control
etc.
Product picture
Chapter 2 Features and Function
2.1 Function Introduction
◆ 2 standard interfaces of RS485, supporting a variety of protocols and communicating
with various automatic devices with RS485 interfaces
◆ Equipped with LoRa chips SX1276 from Semtech for RF part
◆ Supporting LoRaWAN Class C protocol
◆ Small size, easy to install

2
◆ Working temperature range: -20℃~70℃, suitable in all kinds of harsh environment
◆ Wide operating voltage range with optional multi specification models
2.2 Technical Parameter
Product Parameter
Power Supply
AC85-265V,50/60Hz
Power Consumption
<1W
Protocols Supported by RS485
Modbus RTU, DL/T 645
RS485 Communication Baud Rates
1200-115200bps,8N1, 8E1, 8O1
Installation
Din rail mounted installation
RF Parameter
Working Frequency Range
868MHz
ISM Band
868MHz
Antenna Impedance
50Ω
Output Power
18dBm100mA
Sensitivity
-139dbm (SF12, Broadband 125KHz)
Transmission Data Length
51 bytes every frame, total 32 frames
Protocol
LoRaWAN Class A/C
2.3 Selection Table
Model
RS485
Power Supply
Wireless parameters
Working
Frequency
Network Mode
IOT-L2S-C1
2
AC85~265V
868MHz
LoRaWAN
2.4 Parameter Configuration
All the parameters of LoRaWAN series products developed by our company can be set by
the user. The setting steps are as follows:
2.4.1 Wiring
The power ports are connected into power supply of AC85-265V. Connect the RS485-1 port
of the device to the PC terminal through a RS485 converter.
The Link/ACT indicator light will flash quickly after power on, if the module acces ses the
Net successfully, it will flash every two seconds.

3
2.4.2 Enter Configuration Mode
Method 1:
After wiring, power on and press button “Deploy” longer than 5S to make LoRa device enter
the configuration mode. After that, the LINK/ACT indicator lights flash at a fixed frequency
(flashing once per second) and release the button.
Method 2:
Press the button “Deploy” to power up the module, it will enter the configuration mode
directly. And then release the button. The Link/ACT indicator light will flash at a fixed
frequency (flashing once per second).
2.4.3 Open the Software
Open the software of LoRaWAN series products. Select the corresponding COM port in the
“Communication Connection” part, and then click “Open the Port”, like the following picture.
2.4.4 Parameters Configuration
There are six parts in the parameters configuration: internet access, serial port parameters
configuration, devices definition, register definition, upload/download data definition. Now
we need to configure the parameters of internet access & serial port.
(1)Internet Access: the unique code of LoraWAN device and Appkey cannot be modified.
(2)Serial Port Parameters Configuration: Close RS485-1 and RS485-2
Parameter Configuration Process:
After opening the serial ports, click “Read”. Then it will indicate “Completed”. If it indicates
“Time Out”, please check whether the LoRa device enters the configuration mode.
After completing operation, the host computer will read out the current configured
parameters.
If you need to modify corresponding parameters, click “Write” then it will indicate
“Completed”.
Click “Read” again to check whether configuration is correct. Click “Restart” to exit
configuration mode.

4
Chapter 3 Installation Introduction
3.1 Dimension

5
3.2 Terminal Definition
Name
Definition
L
Line L of Power Input
N
Line N of Power Input
NC
Not Connection
A1
RS485-1 Communication Interface A1
B1
RS485-1 Communication Interface B1
A2
RS485-2 Communication Interface A2
B2
RS485-2 Communication Interface B2
G
GND (Grounding)
Chapter 4 Typical Application
4.1 Application System Example
4.2 Application Areas

6
Chapter 5 After-sales Service
Product Warranty
1. The product warranty period is one year.
2. The company is responsible for free maintenance or exchange within one-year
warranty period.
3. The cost of the components and freight shall be charged for improper meter installation
and/or operation.
4. Over the warranty period, part of the maintenance cost according to actual situation
will be charged.
Service Guarantee
1. Product technical consulting and quality complaints will be replied within 12 hours.
2. Solutions for quality complaints will be provided within 24 hours.
3. Except statutory holidays and force majeure.
Chapter 6 Contact Us
Headquarter Add.: 7F No.1 Aosheng Building, 1166 Xinluo Street, High-tech Development
Zone, Jinan, P.R. China 250101
Factory Add.: 2F Innovation Factory, Feiyue Road, High-tech Development Zone, Jinan,
P.R. China 250101
Tel: +86 0531 68621770-863
E-mail: info@heyuanintel.com
Website: www.heyuanintel.com
Table of contents
Other Heyuan Intelligence Touch Terminal manuals
Popular Touch Terminal manuals by other brands

Advanced Kiosks
Advanced Kiosks Multipurpose Kiosk Assembly and operation instructions

Sagem
Sagem EFT930 Quick reference guide

VeriFone
VeriFone T650m installation guide

Anker
Anker till.one mobile operating manual

Uniwell
Uniwell AX-3000 series user manual

ABB
ABB SPAC 315 C User manual and technical description