HID EDGE EVO EH400-K User manual

INSTALLATION GUIDE
An ASSA ABLOY Group brand
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output
are fictitious. Specifications are subject to change without notice.
© 2014 - 2017 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID Brick logo, the Chain Design, iCLASS, EDGE EVO, and Hi-O are trademarks or registered
trademarks of HID Global, ASSA ABLOY AB, or its aliate(s) in the US and other countries and may not be used without permission. All other trademarks, service marks, and product
or service names are trademarks or registered trademarks of their respective owners.
EDGE EVO®
Standard Networked Controller
EH400-K/ESH400-K 82000-921, Rev. D.3
EDGE EVO is the next evolution in access control hardware solutions. A true IP solution that meets the demands of
open architecture, IP-centric environments, EDGE EVO provides fully distributed intelligence and decision making right
to the door, leveraging the IT infrastructure to the maximum extent possible. Leveraging Power-over-Ethernet (PoE),
EDGE EVO reduces door installation costs by not requiring a separate local power supply under many circumstances.
The Standard Networked Controller is a fully integrated single-door controller offering discrete I/O and Wiegand/
Clock-and-Data interfaces to readers. Additionally, connect native Hi-O™ devices (readers, locks, pushbuttons) and
EDGE EVO Hi-O Modules to the Hi-O bus, providing secure communication around the door. Hi-O involves devices with
built-in intelligence and a CANbus that links all the devices together. Password protect or encrypt Hi-O CANbus data
traffic. Each Hi-O device (such as the push plate, electric strike, card reader and door operator) is connected to the
CANbus by a single, four-wire cable. Two wires supply power and the other two are used for data communication.
Specifications
CONDITIONS VOLTAGE DC CURRENT POWER OPERATING
TEMPERATURE CABLE LENGTH REGULATORY
REF NUMBER
INPUT
DC Input (NSC)
+12 VDC 0.18 Amp 2.16 W
32° - 122°F
(0° - 50° C)
Hi-O CANbus
Total Length:
100 ft (30 m)
22 AWG
0.65 mm
0.33 mm2
Maximum between drops:
30 ft (10 m)
22 AWG
0.65 mm
0.33 mm2
RJ-45
328 ft (100 m)
Category 5 K
KE400CX1X2N
+24 VDC 0.14 Amp 3.36 W
PoE (+48 VDC NOM) 0.085 Amp 4.08 W
DC Input (MAX)
+12 VDC 1 .50 Amp 18.00 W
+24 VDC 36.00 W
PoE (+48 VDC NOM) 0.30 Amp 14.40 W
Supervised inputs
(AC, Batt, REX, Door Mon) (MAX)
0-+5VDC Reference
0.005 Amp
(sink) 0.025 W
Data 1/CLK , Data 0 / Data (MAX) N/A N/A
OUTPUT
GRN LED, RED LED, Beep, Hold (MAX) 0.005 Amp
(sink) 0.025 W
External Tamper (MAX) +5VDC (NOM) 0.02 Amp 0.100 W
CAN DC
PWR Output
(MAX)
AUX 12/24 VDC Input +10.8 to +24 VDC 1 .2 Amp* 28.80 W
PoE Input + 24 VDC (NOM) 0.4 Amp* 9.60 W
Reader DC
PWR Output
(MAX)
AUX 12 VDC
+9.8 to +12.25 VDC
0.32 Amp* 3.92 W
AUX 24 VDC 0.60 Amp* 7.35 W
PoE Input 0.58 Amp* 7.11 W
Strike***/
AUX Relays
NC or NO
DC Output
(MAX)
AUX 12 VDC
Input Unregulated
(Wet) Jumpers
+10 to +12 VDC
0.70 Amp*
8.40 W
AUX 24 VDC
Input
+23 to +24 VDC 16.80 W
Regulated (Wet)
Jumpers - 12 VDC +10 to +12 VDC 8.40 W
PoE Input
Unregulated
(Wet) Jumpers +16.5 to +24 VDC 0.36 Amp* 8.64 W
Regulated (Wet)
Jumpers - 12 VDC +10 to +12 VDC 0.58 Amp* 6.96 W
AUX/PoE
Input Jumpers Set to
Dry +12 to +24 VDC
External 2 .00 Amp ** 48.00 W
Legend
AUX = Auxillary input or output
CAN = CANbus
NSC = Normal Standby Condition
Regulatory Reference
Number Deciphering
X1= K for Black
G for Gray
X2= N for non-Solo
S for Solo
*Combined output ratings not to exceed V*I = W:
• 1.2 Amp (+ 24 VDC Aux Input, 28.8 W)
• 1.2 Amp (+ 12 VDC Aux Input, 12.96 W)
** Each relay
*** Shared between each relay
PoE = Power over Ethernet
NC = Normally Closed
NO = Normally Open

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 2
Installation
1 Power Analysis
Before starting installation, determine which components will be used in the system and analyze
the power requirements to avoid over-loading the EDGE EVO Hi-O Networked Controller & Reader
(EH400-K).
The following steps illustrate sizing power requirements for the system.
Step 1 Identify System Components
Identify the components that will be used in the system. A typical installation may include the following
components:
• Door Position Switch – Detects when the door is open or closed.
• Magnetic Lock – Holds the door locked.
• Request to Exit (REX) Switch – Unlocks the door when exiting the secured area.
• EDGE EVO Hi-O Standard Networked Controller (EH400-K) – Provides access control and manages
all peripherals around the door.
• iCLASS® Wiegand Reader – Provides entry into the secured area.
Step 2 Create System Layout
Using the components identified in Step 1 Identify System Componentscreate the system layout.
In this example, the EH400-K is connected to the remote server through an Ethernet connection and
manages door peripherals over the Hi-O bus. Controlling downstream door peripherals, the EH400-K is
a fully integrated single-door controller offering discrete I/O and Wiegand/Clock-and-Data interfaces
to external readers. The EH400-K receives inputs from the Door Position Switch and REX Switch to
drive the Magnetic Lock output.
Unprotected
Area Protected Area
Physical Access
Control Server
(real-time functions
not required )
Remote Area
Wiegand Ethernet Swit
ch
Ethernet Data
Door Position
Switch
Magnetic Lock
REX Switch
Wi
ega
n
D
o
o
r
P
S
w
i
M
a
g
c
t
e
d
n
e
Wiegand
Reader
EH400-K

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 3
Step 3 Analyze Power Requirements
A - Door Peripheral Operational Currents
For the door peripherals identified in Step 1 Identify System Components, consult the vendor
data sheets to determine the operational current draw. Typical operational current draw is
provided below.
Note: See individual peripheral data sheets for actual operational current draw.
Device Conditions Typical Operational Current
Door Position Switch Vin = 12VDC 15mA
(For example, Securitron MSS) Vin = 24VDC 15mA
Mag Lock Vin = 12VDC 300mA
(For example, Securitron M32) Vin = 24VDC 150mA
REX Switch Vin = 12VDC 28mA
(For example, Securitron EEB) Vin = 24VDC 38mA
iCLASS Wiegand Reader Vin = 12VDC 150mA
B - Match I/O Requirements to the Hi-O Interface Device
For the door peripherals identified in Step 1 Identify System Components, the system requires
direct connection to I/O interface and Wiegand/Clock-and-Data ports of the EH400-K. A
separate Hi-O Interface Device is not required.
C - Compute and Compare Overall Current Draw
Calculate the total current draw for all door peripherals, all Hi-O interface devices, and all Hi-O
enabled readers with the following equation, adding terms as required.
I total = I dps + I mag + I rex + … + I EDM-M
For this example, the total current draw equals the following:
I total @ +12VDC = 15mA + 300mA + 28mA + 150mA* = 493mA
I total @ +24VDC = 15mA + 150mA + 38mA + 150mA* = 353mA
Compare the required current draw (I total) to the output current capacity of the EH400-K to
select the EH400-K power scheme. See Specifications. The CAN DC PWR Output represents
the entire power output capacity of the EH400-K.
Device Port Conditions V out I out
Standard Networked Controller
(EH400-K)
CAN DC PWR Output (MAX) AUX +12/24 VDC Input +10.8 to +24VDC 1.2 Amp
PoE Input +24VDC (NOM) 0.4 Amp
In this example, the EH400-K provides sufficient power when operated with a PoE injector or
+12/24VDC auxiliary power supplies.
Directly connect the door peripherals identified in Step 1 Identify System Componentsto the
EH400-K I/O ports per the Specificationsfor the selected input power scheme.
Ensure all door peripherals connected to the Strike/AUX relays or the Reader DC PWR
Output, or both, do not exceed 1.2 Amps (AUX Input) or 0.4 Amps (PoE Input) combined.
Alternatively, the door peripherals may be connected to the Strike/AUX relays configured for
Dry contact up to 2 Amps per relay.

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 4
Step 4 Select Power Scheme
Select the appropriate power scheme to meet overall current draw. Using the analysis from
the previous sections equates to the following two power scheme options.
Power Scheme 1
Standard Networked Controller power is derived from PoE. Insert a UL294 Listed PoE Injector
in the Ethernet line to power the Standard Networked Controller.
Protected Area Remote Area
Wiegand
Ethernet Data
Door Position
Switch
Magnetic Lock
REX Switch
Wiegand Reader
EH400-K
Unprotected
Area
Reader Power
Ethernet Power
Wie
ga
D
o
o
r
P
o
S
w
i
M
a
g
n
e
a
der
c
t
e
d
Re
ad
e
Physical Access
Control Server
(real-time functi
ons
not required)
Ethernet Swit
ch
UL 294 PoE
Injector
e
r
Power Scheme 2
Standard Networked Controller power derived from an external +12VDC or +24VDC power
supply. Standard Networked Controller is connected directly to the Ethernet switch without a
PoE Injector.
Protected Area
Physical Access
Control Server
(real-time functi
ons
not required)
Remote Area
Wiegand Ethernet Switch
Ethernet Data
Door Position
Switch
Magnetic Lock
REX Switch
Wiegand Reader
EH400-K
Unprotected Area
+/24VDC12
Power Supply
Power
Wiega
n
D
o
o
r
P
S
w
i
M
a
g
n
a
de
r
d
A
r
e
a
Po
w
e
r

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 5
2 Mounting
3 Wiring
Hi-O Group Select Jumper
Short = Group 1, Open = Group 2
Outside Door Inside Door
(
)
1 P2 12 1 P1 4
CAN V+
GND
CAN_H
CAN_L
RDR PWR
GND
Data0 / Data
Data1 / CLK
*
GRN LED
RED LED
Hold
*
Beep
GRP SEL
+
-
10 P3 14P1 1
+
-
Hi-O Group Select Jumper
Short = Group 1, Open = Group 2
Outside Door Inside Door
( )
+
-
*
NC
NO
COM
NC
NO
COM
Relay Jumpers
6 P10 1
AUX
+DC
AUX
GND
+
-
Reader Tamper +
Door Strike
AUX
AC FAIL
INPUT SENSE
REX
Door Mon
* = Built-In Module Internal Optical Tamper Disable
BATT FAIL
INPUT SENSE
Note: Connect the Door Monitor to avoid a Force Door Alarm.
P9
P5
P8
P6
P4
P7
Ethernet / PoE
Auto-Detected
Activity LED
Link LED
Hi-O CANbus
Reader Tamper -
CAP
Restore Network
Defaults Jumper
CAUTION: Some magnetic locks exhibit both high inrush current when activated and a high
instantaneous break voltage when de-energized due to magnetic field collapse. It is recommended
you use of a snubber circuit across the controlling relay terminals to protect the controlling relay
contacts. Go to www.hidglobal.com > Support and search for "Edge Solution 891" to access How do I
wire a High In-Rush Current locking device to VertX/EDGE EVO. Not evaluated by UL.
Optional
Supervised Inputs
1-6K N/O
1-6K
N/C
1-6K
1-6K
N/O
Legend
CAN_H = Hi-O CANbus High
CAN_L = Hi-O CANbus Low
GND = Ground
CAN V+ = Hi-O CANbus Positive
Supply
ATTENTION
Observe precautions for handling
ELECTROSTATIC SENSITIVE DEVICES
Junction box not included.

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 6
4 Install to Backplate
Contact EDGE EVO with the information provided in the next section.
5 Contact
Contact EDGE EVO through one of the following methods:
Direct Connect
If connecting EDGE EVO to a network using static IP addressing or if the Discovery GUI is not installed
on the PC, use this method.
Note: The computer must be running Windows 2000 or XP and be configured for DHCP.
1. Disconnect the computer from the network and directly connect EDGE EVO to the computer with
an Ethernet cable.
2. Select Start > Run and enter ipconfig /renew.
3. Open a web browser and enter 169.254.242.121 into the Address field.
Discovery GUI (for DHCP Networks)
With a DHCP network, use the HID Discovery GUI on the PC to locate and connect the Controller.
Note: The Controller must be connected to the network before power is applied for DHCP to function.
Java is required for the Discovery GUI.
1. With the PC connected to the same network as the Controller, double-click hid-discovery.exe.
Note: If the HID Discovery Application is not on the PC, download the application from
www.hidglobal.com/drivers. Search for “Discovery” and the DISCOVERY GUI download window
will appear.
2. Select the device from the list and click the Launch Browser button.

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 7
6 Configure
The web browser will prompt for login information.
Note: To correct errors in the controller Network Configuration or if the admin password is not
available, see Appendix B: Troubleshooting.
1. From the Login screen enter admin, leaving the Password field empty.
2. Follow the instructions on the web browser screen to configure EDGE EVO.
Note: On subsequent sessions, the password may be changed by the user. The password must
be between 6 to 10 characters long and can include all printable ASCII characters from 32 to 126
(decimal). Reference: http://www.asciitable.com.
For EDGE EVO Solo, see the EDGE EVO Solo User Guide, 83000-902, rev B.x.
7 Power & Testing
Test the system once per year using the web Graphical User Interface to ensure all wiring and
configuration is correct.
For additional installation information, such as Passive Infrared Device (PIR) and other active REX
devices, as well as connecting fire relays, see http://www.hidglobal.com > Support and search for
"EDGE EVO."

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 8
Appendix A Hi-O Interface Modules
Hi-O interface modules are used to interface the EDGE EVO Networked Controller. Hi-O interface
modules connect the native Hi-O bus with additional components around and behind doors and other
access points.
For Hi-O interface module wiring, see their respective Installation Guides:
go to www.hidglobal.com > Support > Document Library and search the document type
InstallationGuide.
Model Description Part Number
EDM-M EDGE EVO Door Module 82342
EIM-M EDGE EVO Input Module 82340
EWM-M EDGE EVO Reader Module 82360
EDWM-M EDGE EVO Door & Reader Module 82363AM
ELM EDGE EVO Lock Module 82301
EVM EDGE EVO Voltage Module 82365

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 9
Appendix B Troubleshooting
See Section 3: Wiring to clarify the procedures in this appendix.
B.1 Network Defaults Jumper Procedures
Use the applicable Network Defaults Jumper procedure to correct potential errors in an EDGE EVO and
EDGE EVO Solo controller Network Configuration or if the admin password is not available.
EDGE EVO (EH400-K)
This Network Defaults Jumper procedure requires physical access to the EDGE EVO controller. Physical
access provides the necessity to place a jumper over the debug port prior to the controller rebooting.
The controller reconfigures the network settings to the factory defaults when the jumper is on the
debug port during a reboot. From this point, configuration (or re-configuration) proceeds normally.
A jumper is supplied with the EDGE EVO for the Hi-O termination; borrow this jumper to perform this
process. Replace the jumper to the Hi-O termination after restoring network defaults.
1. Remove the back plate on the EDGE EVO.
2. Loosen the Mylar cover.
Note: For the jumper location, see the diagram in Section 3: Wiring.
3. Reboot the controller and place the supplied jumper over pins 3 and 5 of the Debug port after
the beep. The Debug port is an eight pin header, located above and to the right of the Ethernet
connector, underneath the Mylar.
Note: The network reset opportunity occurs for 30 seconds, while rebooting the controller. On an
EDGE EVO, a second beep occurs to signal the end of the 30 second period.
4. After 30 seconds, the beeper stays on constantly to indicate success. When an error occurs, you
receive a single beep.
5. Remove the jumper; return it to the Hi-O termination header and cycle power. The controller
resets in approximately 60-seconds. Once the reset is complete, you hear the single beep. After
the 30-second window, you hear the second beep. The controller is fully functional during this
time.
CAUTION: During the controller rebooting process, all network configuration information is
overwritten and returned to the original defaults.
6. Configure the controller for your installation parameters.
7. Reinstall the back plate of the EDGE EVO.

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 10
EDGE EVO Solo (ESH400-K)
This procedure will reset the password for the admin user, the admin user can reset the user password
if installer lock is enabled. This process requires:
• 5-10 minutes to complete.
• Contacting HID Global technical support by e-mail or phone with the unit's MAC Address to obtain
the new generated password that is required in the following procedure.
• Physical access to the EDGE EVO Solo device.
• A pair of needle-nose pliers to work with a small jumper.
Note: This procedure works for all released versions of EDGE EVO Solo but must be followed very
carefully for the process to work.
1. Remove the jumper from the HiO Termination pins. This is located to left of the HiO four-pin
connector. This jumper will be used through the remainder of the procedure.
2. Power Cycle the EDGE EVO Solo unit.
3. Between 10 and 25 seconds after power is applied, place a jumper over pins 3 and 5 of the Debug
Port (eight pin header located above and to the right of the Ethernet connector, underneath the
Mylar - see graphic below). If no jumper is applied during this period the unit will continue to
operate as normal and no reset will occur.
Note: If the jumper is applied before power is applied to the unit, no reset procedure is
completed, and the unit will fail to boot correctly.
4. Provided the jumper is correctly fitted within the specified time, the unit will beep with 2 short
beeps, then a pause. This beep/pause cycle will continue indefinitely until the jumper is removed.
5. Remove the jumper. The beeps will cease.
6. Wait a minimum of 1 second then reapply the jumper. The jumper must be reapplied within 15
seconds of removing it. If the jumper is not reapplied within this time, the device will emit 10 short
beeps and the unit will automatically reboot. In this case the password will not have been reset.
7. The unit will beep with 2 short beeps, then a pause. This beep/pause cycle will repeat indefinitely
until the jumper is removed.
8. Remove the jumper to complete the process.
9. The beeps will cease. The admin password is now reset to the value provided by HID Global
Technical Support. The unit will beep quickly 10 times and then automatically reboot.
The password reset process is now complete.
10. Reinstall the jumper borrowed from the HiO Termination pins. This is located to left of the HiO
four-pin connector.
11. Connect to the unit via the JumpStart application, configured IP Address, or Alias IP Address.
12. The web browser will prompt for a username and password.
13. Login with username: admin and the password will be the 8-digit alphanumeric value you
obtained from HID Global Technical Support.
14. It is recommend you immediately go and modify the password(s) using the Password option
within the Preferences link.

INSTALLATION GUIDE
An ASSA ABLOY Group brand
EDGE EVO 82000-921, Rev. D.3
Page 11
B.2 Internal Optical Tamper
The Controller Optical Tamper can not be disabled. The Optical Tamper is suppressed by properly
installing the back plate which contains a post with white paint on it and securing it to the unit. To
disable the internal module optical tamper sensors:
• Right side of PCB (reader interface board): attach a jumper wire from P2 pin 10 to P2 pin 5.
• Left side PCB (door interface board): attach a jumper wire from P3 pin 1 to P3 pin 2.
CAUTION: The EH400-K ships from HID Global with these jumpers pre-installed on the connectors.
Removing these jumpers causes false tampers to trigger.
Note: If desiring an external tamper, wire an unsupervised Normally Closed contact, replacing one of
the pre-installed jumpers.
B.3 Relay Jumpers
AUX Wet
CAN V+
AUX Wet
+12VDC AUX Dry DS Wet
CAN V+
DS Wet
+12VDC DS Dry
31
P9
P5
P8
313 1 3 1
P6
P4
P7
313 1
JUMPER =
B.4 Tamper (Reader Interface Board)
The Reader Tamper + and - are implemented allowing a connection for an open collector external
tamper from a reader, such as iCLASS.
Note: Connect P2, Pin 2 (GND) from the Reader Interface Board to the same ground as the reader
power if the reader is not powered by the unit's 12 VDC output port.
B.5 Door Interface Board Groups 1 and 2
Following are the inputs for Group 1 and Group 2 configurations.
Group 1 Group 2
Input Port Pin Input Port Pin
AC - P3 Pin3 Input 4 - P3 Pin3
AC + P3 Pin 4 Input 4 + P3 Pin 4
BATT - P3 Pin 5 Input 3 - P3 Pin 5
BATT + P3 Pin 6 Input 3 + P3 Pin 6
REX - P3 Pin 7 Input 2 - P3 Pin 7
REX + P3 Pin 8 Input 2 + P3 Pin 8
Door Mon - P3 Pin 9 Input 1 - P3 Pin 9
Door Mon + P3 Pin 10 Input 1 + P3 Pin 10

An ASSA ABLOY Group brand
INSTALLATION GUIDE
Page 12
EDGE EVO 82000-921, Rev. D.3
HID Global
Americas & Corporate
611 Center Ridge Drive
Austin, TX 78753
USA
Support: 866-607-7339
Fax: 949-732-2120
Asia Pacific
19/F 625 King's Road
North Point, Island East
Hong Kong
Support: 852-3160-9833
Fax: 852-3160-4809
Europe, Middle East & Africa
Haverhill Business Park Phoenix Road
Haverhill, Suolk CB9 7AE
England
Support: 44 (0) 1440 711 822
Fax: 44 (0) 1440 714 840
Patent Pending
Check reader label for current regulatory approvals.
For additional oces around the world, see www.hidglobal.com corporate oces.
HID Global Customer Support: support.hidglobal.com
Regulatory
UL
Connect only to a Listed Access Control / Burglary power-limited power supply, or Listed Access Control / Burglary PoE (Power-over-Ethernet) adapter.
All National and local Electrical codes apply. Install in accordance with NFPA70 (NEC), Local Codes, and authorities having jurisdiction. Host-based security, Ethernet / Host
Communication, has not been evaluated by UL. Ethernet port has been evaluated for supplemental use only.
Indoor use only.
The EDGE EVO family has been evaluated for standalone Access Control.
Mount onto UL Listed Single-Gang electrical box.
Hi-O Networked Controller and EDGE EVO Modules are UL Listed for installation within the protected area.
All panic and alarm hardware and equipment shall be UL Listed.
All cabling and wire shall be UL Listed or Recognized and suitable for the application.
All splices and connections shall be mechanically secure and bonded electrically.
EDGE EVO was evaluated for use with all Listed HID Global Wiegand models: iCLASS, Indala Prox, HID Prox, bioCLASS, SmartID, SmartTRANS, and Mag Stripe series (with
and without keypad), up to 128-bit formats. EDGE EVO was evaluated for use with all HID Global Hi-O iCLASS readers.
Hi-O Networked Controller is UL Listed for installation in the unprotected area, as well as within the protected area.
CAUTION: Any changes or modifications to this devise not explicitly approved by the manufacturer could void your authority to operate this equipment.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Canada Radio Certification
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference,
and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
(1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en
compromettre le fonctionnement.
CE MARKING
HID Global hereby declares that these proximity readers are in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
Por el presente, HID Global declara que estos lectores de proximidad cumplen con los requisitos esenciales y otras disposiciones relevantes de la Directiva 1999/5/EC.
HID Global déclare par la présente que ces lecteurs à proximité sont conformes aux exigences essentielles et aux autres stipulations pertinentes de la Directive
1999/5/CE.
A HID Global, por meio deste, declara que estes leitores de proximidade estão em conformidade com as exigências essenciais e outras condições da diretiva 1999/5/EC.
HID Global bestätigt hiermit, dass die Leser die wesentlichen Anforderungen und anderen relevanten Bestimmungen der Richtlinie 1999/5/EG erfüllen.
HID Global dichiara che i lettori di prossimità sono conformi ai requisiti essenziali e ad altre misure rilevanti come previsto dalla Direttiva europea 1999/5/EC.
Download copies of the R&TTE Declaration of Conformity (DoC) at http://www.hidglobal.com/certifications.
JAPAN MIC
この装置は認証済みです。
TAIWAN NCC
經型式認證合格之低功率射頻電機,非經許可,公司、商號或使用者均不得擅自變更頻率、加大功率或變更原設計之特性及功能。低功率射頻電機之使用
不得影響飛航安全及干擾合法通信;經發現有干擾現象時,應立即停用,並改善至無干擾時方得繼續使用。前項合法通信,指依電信法規定作業之無線電
通信。低功率射頻電機須忍受合法通信或工業、科學及醫療用電波輻射性電機設備之干擾。
According to «Administrative Regulations on Low Power Radio Waves Radiated Devices» without permission granted by the NCC, any company, enterprise, or user is not
allowed to change frequency, enhance transmitting power or alter original characteristic as well as performance to an approved low power radio-frequency devices. The
low power radio-frequency devices shall not influence aircraft security and interfere legal communications; If found, the user shall cease operating immediately until no
interference is achieved. The said legal communications means radio communications is operated in compliance with the Telecommunications Act.
The low power radio-frequency devices must be susceptible with the interference from legal communications or ISM radio wave radiated devices.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit (http://www.openssl.org).
This manual suits for next models
1
Table of contents
Other HID Controllers manuals

HID
HID VertX EVO V1000 User manual

HID
HID Signo 25B User manual

HID
HID Mercury LP1502 User manual

HID
HID Vertx CS V100 User manual

HID
HID Aero X1100 User manual

HID
HID VertX EVO Series User manual

HID
HID Signo 25B User manual

HID
HID VertX EVO V2000 User manual

HID
HID iCLASS SE RB25F User manual

HID
HID Mercury LP4502 User manual
Popular Controllers manuals by other brands

Kromschroeder
Kromschroeder Lago Basic 0101/1001 Operating and installation instructions

Timeguard
Timeguard SLW360L Installation & operating instructions

BOSSCO
BOSSCO 356 manual

AutomationDirect
AutomationDirect DirectLogic Series Application note

Tolomatic
Tolomatic Axidyne AXIOM PLUS PV Series user manual

dewert okin
dewert okin RF61 instructions