FOR SERVICE PERSONNEL ONLY
INDOOR UNIT
1 Installation of Hanger, Wall Penetration and Installation of Protection Pipe
CAUTION
The draining of the water container inside the Indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side of
drain hose. Otherwise, condensed water may overflow the water container.
Direct Mounting On The Wall
Please use hidden beams in the wall to hold the hanger.
Procedures of Installation and Precautions
Procedures to fix the hanger.
1.Drill holes on wall.
(As shown below)
2.Push plug into the holes.
(As shown below)
3.Fix the hanger on wall with
4.1 x 32 screw.
(As shown in figure below)
Wall Penetration and Installation of Protection Pipe
Drill a ø65mm hole on wall which is
slightly tilted towards the outdoor side.
Drill the wall at a small angle.
Cut the protection pipe according to the
wall thickness.
Empty gap in the sleeve of protection
pipe should be completely sealed with
putty to avoid dripping of rain water into
the room.
Please ensure smooth flow of water
when installing the drain hose. Improper
installing may wet your funiture.
An IEC approved power cord should be
used. Power cord type: NYM.
WARNING
Be sure that the wire is not
in contact with any metal in
the wall. Please use the
protection pipe as wire
passing through the hollow
part of the wall so as to
prevent the possibility of
damaged by mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and any
dew may drop.
Seal with
putty
Protection
pipe Sleeve of
protection
pipe
Seal with
putty
Outdoor
Indoor
2-5mm
2 Installation Of The Indoor Unit
WALL
32mm
Wall
ø4.8mm
Hanger
Screw
Wall
Plug
(Procure
locally)
Screw the hanger at the
positions possibly near the
upper and lower hooks where
the indoor unit is hung. Use 4 or
more screws to fix the hanger.
PIPING FROM THE RIGHT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Connect connecting cord.
Pull out the pipe, connecting cord and drain hose.
Installation
Insert the pipe through the wall hole.
The upper part of the Indoor unit is hanged on the
hanger.
The projection at the lower part of the Indoor unit is
hooked onto the hanger.
Connecting cords, pipe and
drain hose must be laid
together with Vinyl tape.
Lift the body
of the unit
upwards and
then force it
downwards.
Hanger
Refrigerating
Pipe
Protection
Pipe Drain Hose Connecting Cord
Projection
PIPING FROM THE LEFT SIDE (BACKWARD, DOWNWARD, HORIZONTAL)
Preparation
Changed of Drain Hose and Installation Procedures.
Exchange the location of drain hose and drain cap while installing the pipe from the left side as
shown in below. Be sure to plug in the drain hose until the insulating material folds upon itself.
Please use pliers to pull out the drain cap.
(This is an easier way to remove the drain
cap).
CAUTION
Insufficient insert may
result in water leakage.
Cutting Low Cover bush
While installing the pipe from the right, left or
bottom side, use a knife to cut openings as
shown in figure. Then smoothen the edges of
openings with a file.
Openings
Openings
CAUTION
The rubber strap used for fixing the insulator
should not be tied with great force. Otherwise,
this will damage heat insulation and causes
water condensation.
Please pull the lower part of the Indoor unit
outwards to check if the unit is hooked onto
the hanger. Improper installation may cause
vibration and noise.
Transform the piping while holding down the
lower portion of pipe-support by hand.
Pipe Rubber strap tied
with great force
INSTALLATION AFTER CONNECTION OF REFRIGERATING PIPES
The refrigerating pipe should be adjusted to fit into
the hole on the wall and then ready for further
connection.
The terminals of 2 connected pipes must be covered
with insulator used for terminal connection. Then the
pipes are wrapped with insulation pipe.
Connect the connecting cord after removing low
cover.
(Refer to "CONNECTION OF POWER CORD")
After adjustment, fit the connecting cord and pipes
into the space available under the unit. Use holder to
hold them tight.
THE CONNECTION OF REFRIGERATING PIPE DURING
THE INSTALLATION OF INDOOR UNIT
Preparation To Install Refrigerating Pipes
The refrigerating pipes and connecting cord
transform and are attached.
below
5mm
Please bend at a small
radius to form an arc
Installation
Hang the indoor unit onto the hanger. Use the temporary stand
at the back of the Indoor unit to push its lower part 15cm
forwards.
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing low cover.
(Refer to "Connection of Power Cord")
After adjustment, the connecting cord and refrigerating pipes
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.
about 15cm
Hook
Projection
4 Installation of Drain Hose
CAUTION
Be sure that the drain hose is
not loosely connected bend or
proper condition like left figure.
CAUTION
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
unit during installation. (Careless may result in water leakage.)
Condensed
water pond
Bending upwards Condensed water
pond
Ditch
The connected terminals should be completed sealed
with heat insulator and then tied up with rubber strap.
Do not tie the terminals with the tape too tight.
If any clearance or over-tightening may cause
condensation.
Please tie the pipe and power line together with vinyl
tape as shown in the figure showing the installation of
Indoor and Outdoor units.
To enhance the heat insulation and to prevent water
condensation, please cover the outdoor part of the
drain hose and pipe with insulation pipe.
Completely seal any gap with putty.
Insulation material for pipe
connection
Sleeve of
protection pipe
Putty
Putty
Wall hole
Pipe
Drain hose
Cable
Drain layout of
backward piping
The end of the refrigerating pipes are at
locations marked with “ ” symbol.
3 Heat Insulation and Finish of the Piping
Ceiling
Hanger
Pipe
support Transform after
bending downward.
RAK_RAS_18/25/35/50PEC_IM_English 1
Connecting cord Connected
section
pipe
Drain
Protection
hose
INDOOR UNIT
WARNING
THE CHOICE OF MOUNTING SITE (Please note the following matters and obtain permission from customer before installation.)
The unit should be mounted at stable, non-vibratory location
which can provide full support to the unit.
CAUTION
No nearby heat source and no obstruction near the air
outlet is allowed.
The clearance distances from top, right and left are
specified in figure below.
The location must be convenient for water drainage and
pipe connection with the Outdoor unit.
To avoid interference from noise, please place the unit and
its remote controller at least 1m from the radio and
television.
To avoid any error in signal transmission from the remote
controller, please put the controller far away from high-
frequency machines and high-power wireless systems.
OUTDOOR UNIT
WARNING
The Outdoor unit must be mounted at a location which can
support heavy weight. Otherwise, noise and vibration will
increase.
The installation height should be at least 2300 mm or more
from the floor.
Names of Indoor Components
Direction of Piping
Backward piping
from left
Connection
There are 6 directions allowed,
namely, backward piping,
backward piping from left,
horizontally piping from right,
horizontally piping from left,
vertically down from right, vertically
down from left.
Dimension of Mounting
Stand of the Outdoor unit
(unit : mm)
Figure showing the Installation
of Indoor and Outdoor Unit.
above
50mm
above 50mm
above 50mm
about 300mm
must not bend
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator is
insufficient, please use commercial
products.)
The refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
The difference in height between
the indoor and outdoor unit
should be kept below 10m.
The connecting pipe, no matter
big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).
The connection of insulated drain
hose.
Inner diameter 16mm
Please use insulated drain hose for
the indoor piping (commercial
product)
Be sure to
completely
seal any gap
with putty.
Mounting
Stand
2300 mm or more
No. Item Qty
Hanger
Screw for Hanger
AAA size Battery
Screw for holder of
Remote Controller
Remote Controller
Insulation sheet
Drain Pipe
The component of
the package of the outdoor unit.
is included
The component of
the package of the outdoor unit.
is included in
Bush
L.H
Maximum pipe length 20m
Minimum pipe length 3m
above 100mm
above 300mm
above 50mm
give clearance
as wide as
possible
above
200mm
above 200mm
For outdoor unit installation, allow at least
2 sides of space around the unit to ensure
ventilation flue.
87
1
2
3
4
5
6
7
8
12
(10)
10
500
660
50
34 12
297
80
317
792
500
340
32010
12
39 146
(10)
57
Mounting
Stand
The clearances of the
unit from top, left, right
and front are specified
in figure below. At least
three of the above sides
must be open air.
EN
1
Pull this to the front during the
connection of refrigerating
pipe to ease task.
Wall hole
Pipe
Drain
hose
Cable
Drain layout of
backward piping
from left
Heat
insulation pipe
Refrigerating
pipe
Connecting
cord
about 450m
Pipe Connecting cord
Drain hose
Besides, ventilation must be good and clear of obstruction.
The air blown out of the unit should not point directly to
animals or plants.
The clearances of the unit from top, left, right and front are
specified in figure below. At least there of the above sides
must be open air.
Be sure that the hot air blown out of the unit and noise do
not disturb the neighbourhood.
Do not install at a location where there is flammable gas,
steam, oil and smoke.
The location must be convenient for water drainage.
Place the Outdoor unit and its connecting cord at least 1 m
away from the antenna or signal line of television, radio or
telephone. This is to avoid noise interference.
CAUTION
Selecting the installation location: Suitable location that
will reduce the impact from rain and direct sun that may
affect the unit performance.
Drain Hose
Drain cap
Remove low cover
Insert drain cap up to the
Please use hexagonal wrench key(Φ4mm) to insert the drain cap.
(This is an easier way to install the drain cap.)
location securely till the cap stops.
Push the pipe deeply until the insulating
section of the drain hose end gets over
the rib at the indoor unit side.
Drain hole
Hexagonal wrench
key (Φ4mm)
Drain hole
Hexagonal wrench
key (Φ4mm)
Visible outline of the
Drain Hose
RAK-18PED/RAC-18WED
RAK-35PED/RAC-35WED
RAK-50PED/RAC-50WED
RAK-25PED/RAC-25WED RAK-35PEDC/RAC-35WED
RAK-50PEDC/RAC-50WED
RAK-25PEDC/RAC-25WED
(RAC-50WED)
RAC-18/25/35WED
RAC-50WED
SAFETY PRECAUTION
Read the safety precautions carefully before operating the unit.
The contents of this section are vital to ensure safety. Please pay special attention to the following sign.
WARNING .......... Incorrect methods of installation may cause death or serious injury.
CAUTION .......... Improper installation may result in serious consequence.
Make sure to connect earth line.
This sign in the figures indicates prohibition.
Be sure that the unit operates in proper condition after installation. Explain to customer the proper operation and maintenance of
the unit as described in the user' s guide. Ask a customer to keep this installation manual together with the instruction manual.
WARNING
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you do the
installation work yourself.
Please observe the installation stated in the installation manual during the process of installation. Improper installation may cause
water leakage, electric shock and fire.
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the units may
collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when dealing
with the electrical work. Use cables which are approved official in your country. Be sure to use the specified circuit. A short circuit and
fire may occur due to the use of low quality wire or improper work.
Be sure to use the specified cables for connecting the indoor and outdoor units. Please ensure that the connections are tight after the
conductors of the wire are inserted into the terminals to prevent the external force is being applied to the connection section of the
terminal base. Improper insertion and loose contact may cause over-heating and fire.
Please use the specified components for installation work. Otherwise, the unit may collapse or water leakage, electric shock, fire or
stronger vibration may occur.
Be sure to use the specified piping set for R410A, R32. Otherwise, this may result in broken copper pipes or faults.
When installing or transferring an air conditioner to another location, make sure that air other than the specified refrigerant (R32)
does not enter the refrigeration cycle. If other air should enter, the pressure level of the refrigeration cycle may increase abnormally
which could result in a rupture and injury.
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the
room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
Be sure to connect the earth line from the power supply wire to the outdoor unit and between
the outdoor and indoor unit. Do not connect the earth line to the gas tube, water pipe, lighting rod or the earth line of the
telephone unit. Improper earthing may cause electric shocks.
When finishing the refrigerant collection (pumping down), stop the compressor and then remove the coolant pipe.
If you remove the refrigerant pipe while the compressor is operating and the service valve is released, air is sucked and a
pressure in the freezing cycle system will build up steeply, causing an explosion or injury.
When installing the unit, be sure to install the refrigerant pipe before starting the compressor.
If the refrigerant pipe is not installed and the compressor is operated with the service valve released, air is sucked and the
pressure level of the refrigeration cycle may increase abnormally which could result in a rupture and injury.
CAUTION
A circuit breaker must be installed in the house distribution box for the direct connected power supply cables to the
outdoor unit. In case of other installations a main switch with a contact gap or more than 3mm has to be installed.
Without a circuit breaker, the danger of electric shock exists.
Do not install the unit near a location where there is flammable gas. The outdoor unit may catch fire
if flammable gas leaks around it.
Please ensure smooth flow of water when installing the drain hose. Improper installing may wet your fu niture.
An IEC approved power cord should be used. Power cord type: NYM.
The electric cables should neither be reworked nor added.
Make sure to use an exclusive circuit breaker.
Otherwise fire or electric shock might occur by connection failure, isolation failure or over current.
Make sure to connect cables to terminal properly and terminal cover should close firmly.
Otherwise, over heating at terminal contact, fire or electric shock might occur.
Make sure that there is no dust on any connected points of electric cables and fix firmly.
Otherwise, fire or electric shock might occur.
r
This appliance is filled with R32.
Never install a drier to this R32 unit in order to guarantee its lifetime.
indoor unit
440mm
534mm
780mm
65mm
450mm
445mm
220mm
123mm
85mm
60mm 80mm
22mm 32.5mm
123mm
280mm
42.5mm
184mm 59mm
45mm
115mm
15mm
Wall hole
Hanger
Screw for Hanger
Level
Weight
Line
42.5mm
R410A R32)
R32
Be sure to cut the extra binding band.
(Otherw se, t may result n abnormal no se or dewfall.)
B nd ng band
9
B nd ng band
9
Insulation pipe (must be
wrapped with
at every 120 mm)
vinyl tape
B nd ng band can be
nstalled to wh chever
s de of the nstallat on
po nts. However, t s
recommended to attach
t on the r ght s de
v ew ng from the rear.
Please mount the Outdoor unit of stable ground to prevent vibration and increase
of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side cover, please pull the handle after undoing the hook by pulling
it downward. Reinstall the side cover in the reverse order of the removal.
CONDENSED WATER DISPOSAL OF OUTDOOR UNIT
There is holes on the base of Outdoor unit for condensed water to exhaust.
In order to flow condensed water to the drain, the unit is installed on a stand or a
block so that the unit is 100mm above the ground as shown figure. Join the drain
pipe to one hole.
After installation, check whether the drain pipe clings to the base firmly.
Install the outdoor unit horizontally and make sure that condensate drains away.
In case of using in chilly area
Especially, in case that there are many snows by very cold in chilly area, condensed
water freezes on the base and may result not to drain. In this case, please remove
the bush and the drain pipe at the bottom of unit. (Left and center near discharge
portion of air, each 1 place). It becomes smooth drain.
Ensure that the distance from the drain hole to the ground is 250 mm or more.
CAUTION
Remove burr and jagged edge will cause leakage.
Point the side to be trimmed downwards during trimming to prevent copper
chips from entering the pipe.
Copper pipe
Trimming tool
Before flaring, please put on the flare nut.
A
Die
Die
Copper pipe
2 Pipe Connection
CAUTION
In case of removing flare nut of a indoor unit, first remove
a nut of small diameter side, or a seal cap of big diameter
side will fly out. Free from water into the piping when
working.
Be sure to tighten the flare nut to the specified torque with
a torque wrench.
If the flare nut is overtightened, the nut may be split after a
long period has passed, and may cause a refrigerant leak.
Please be careful when bending the copper pipe.
Screw in manually while adjusting the center. After that, use a torque wrench to
tighten the connection.
OME
RRIA
DNASE
PIPGN
ITARE
GIRFE
RFON
OITALL
ATSN LI AV
Torque
wrench
Flare nut
Wrench
3 Remove of Air From The Pipe And Gas Leakage Inspection
LA
VOME
RRIA
Procedures of using Vacuum Pump for Air Removal
As shown in right figure, remove the cap
of valve core. Then, connect the charge
hose. Remove the cap of valve head.
Connect the vacuum pump adapter to the
vacuum pump and connect the charge
hose to the adapter.
1
Fully tighte the "Hi" shuttle of the manifold
valve and completely unscrew the "Lo"
shuttle. Run the vacuum pump for about
10-15 minutes, then completely tighten the
"Lo" shuttle and switch off the vacuum
pump.
Loosen the spindle of the service valve
with small diameter by 1/4 turn and
tighten the spindle immediately after 5
to 6 seconds.
Remove the charging hose from the
service valve.
2
Completely unscrew the spindle of the
service valve (at 2 places) in anticlockwise
direction to allow the flow of refrigerant
(using Hexagonal Wrench key).
3
Tighten the cap of valve head. Check the
cap's periphery if there is any gas leakage.
The task is then completed.
4
The body of service
valve
Cap of
valve core
Hexagonal wrench Key
Cap of valve
head
Gas leakage inspection
Please use gas leakage detector to check if leakage occurs at
connection of Flare nut as shown on the right.
If gas leakage occurs, further tighten the connection to stop leakage.
DROCREWOPFONOITCENNOC
WARNING
TINUROODTUO
NOITALLATSNIFOEGATSLANIF
1 Preparation of Pipe
Use a pipe cutter to cut the copper pipe and remove burr.
Power Source And Operation Test
WARNING
THIS APPLIANCE MUST BE
EARTHED.
Procedures of Wiring
Cap of valve
head
CAUTION
Do not touch the suction
por t, bottom surface, or
aluminum fin of the outdoor
unit.
Failure to do so may cause
an injury.
WARNING
Leave some space in the connecting cord for maintenance
purpose and be sure to secure it with the cord band.
Secure the connecting cord along the coated part of the wire
using the cord band. Do not exert pressure on the wire as this
may cause overheating or fire.
Indoor Unit Outdoor Unit
WARNING
If you cannot attach the side plate due to the connection cord, please
press the connecting cord in the direction to the front panel to fix it.
Be sure that the hooks of the side cover fixed in certainly. Otherwise water
leakage may occur and this causes short circuit or faults.
The connecting cord should not touch to service valve and pipes. (it
becomes high temperature in heating operation.)
Wiring of the Outdoor Unit
Please remove the side cover for wire connection.
Checking for the electric source and the voltage range
Before installation, the power source must be checked and necessary wiring work must
be completed. To make the wiring capacity proper, use the wire gauge list below for the
wiring from house distribution fuse box to the outdoor unit in consideration of the blocked
rotor current.
Investigate the power supply capacity and other
electrical conditions at the installing location.
Depending on the model of room air conditioner to be
installed, request the customer to make arrangements
for the necessary electrical work etc.
The electrical work includes the wiring work up the
outdoor unit. In localities where electrical conditions
are poor, use of a voltage regulation is recommended.
Install outdoor for the room air conditioner within the
reaching range of the line cord.
IMPORTANT
Fuse Capacity
1 A time delay fuse
Push up the [PUSH] sections at the bottom of the indoor unit and
pull the bottom plate towards you. Then the claws are released
from the stationary plate.
(The [PUSH] sections are indicated by 2 arrows in the right figure)
HOW TO REMOVE INDOOR UNIT
Wiring of The Indoor Unit
For wire connection of the Indoor unit, you need to remove the front cover, the low cover
under the body of the unit and terminal cover.
The naked part of the wire core should be 10mm fix it to the terminal tightly. Then
try to pull the individual wire to check if the contact is tight. Improper insertion may
burn the terminal.
Be sure to use only wire specified for the use of air-conditioner.
Please refer to the manual for wire connection and the wiring technique should
meet the standard of the electrical installation.
There is an AC voltage drop between the LN terminal if the power is on.Therefore,
be sure to remove the plug from its socket.
For cable connection to control P.W.B., you need to
remove front cover and electrical box cover.
Each connecting location is as below.
Wired Remote Control : CN20
Please check and confirm manuals attached to each
optional parts for more connection details.
You can refer to this installation manual how to remove
and re-attach the front cover.
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
Remove the cover from the terminal base and screw the cable.
Method to remove the low cover
Pull at the and in
the directions as shown
by arrows to remove the
cover.
5
ler
above
BASE
Outer diameter:
16 mm or more
When the meter reaches - 101KPa
(-76cmHg) during pumping lly
tighten the shuttle.
Meter showing
pressure
Closed
Manifold
valve
Vacuum
pump
Valve
Charge
hose
Vacuum
pump
adapter
When pumping starts, slightly
loosen the flare nut to check of
air sucked in. Then tighten the
flare nut.
Valve
70mm
Please face this side (suction side)
of the unit to the wall. Please remove terminal cover
when connecting the piping
and connecting cord.
Pull downward
L N
Connecting Cord
AC 220-230V
1ø 50Hz
1 2 3 1 2 3
Detail of Cutting the Connecting Cord
cover
Cord band
Earth terminal
7 DRAIN PIPE
160mm
10mm
100mm
1
2
3
70mm
10mm
10mm
45mm
1
2
3
Connecting cord
Strip
wires
Green +
Yellow 20mm
Strip
wires
Connecting cord
Green + Yellow
(ground)
Indoor Unit Outdoor Unit
WARNING
When the fuse (F5 or F6) has been blown out by the improper connection of
power cable, it can be restored by
RAK_RAS_18/25/35/50PEC_IM_English
Pull downward
Please face this side (suction side)
of the unit to the wall.
Please remove terminal cover
when connecting the piping
and connecting cord.
BUSH
Push Push
DRAIN HOLE
DRAIN HOLE
above
100mm
BASE
Outer diameter:
16 mm or more 7 DRAIN PIPE
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
13.7-18.6 (140 - 190)
34.3-44.1 (350 - 450)
44.1-53.9 (450 - 550)
19.6-24.5 (200 - 250)
19.6-24.5 (200 - 250)
12.7 (1/2")
12.3-15.7 (125 - 160)
Small diameter side
Outer diameter
of pipe (ø)
Large diameter side
Small diameter side
Large diameter side
Valve core cap
Torque N·m
(kgf·cm)
Valve
head cap
29.4-34.3 (300 - 350)
L N 1 2 3
Abdeck
L N 1 23
cover
Earth terminal
Cord band
A time delay fuse25
Wire length
up to 6m 1.5mm
2
up to 15m 2.5mm
2
up to 20m 4.0mm
2
Wire cross-section
How to connect the optional parts
Dry contact: CN6
Terminal marking
sPlease ensure that the air conditioner is in normal operating
condition during the operation test.
sExplain to your customer about the proper operation procedures
as described in the operation manual.
sIf the indoor unit won’t operate, check the cable for correct
connection.
Power Source
WARNING
Never remodel the power plug nor extend the long-distance
cord.
Keep additional length for the power cord and do not render
the plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
The power cable easily generates heat. Do not bring the
cable together with a wire or vinyl tie.
Operation test
2
8
RAC-18/25/35WED
RAC-50WED
RAC-50WED
RAC-18/25/35WED
RAC-18/25/35WED RAC-50WED
RAC-18/25/35WED RAC-50WED
BUSH
8
(WIFI Adapter, H-LINK RAC Adapter, Dry contact, Wired Remote Controller)
WIFI Adapter H-LINK RAC Adapter: CN7or
6,35 (1/4")
9,52 (3/8")
0 - 0,5
0 - 0,5
1,0
1,0
0 - 0,5 1,0
12,7 (1/2")
Outer A (mm) Rigid Flaring Tool
Diameter (Ø) For R410A,R32 tool For R22 tool
Please use
exclusive tool for
refrigerant R410A,
R32.
R410A,R32
[PUSH] mark positions
exchanging the fuse (service part No
HWRAC-50NX2 A52)
,fu
n
Connecting
cord
Cord band
After remove the screw
and terminal cover, and
put the connecting cords
and fix the terminal cover
with screw.
Earth
Ple se exch nge the blown-out fuse fter m king sure the right connection.
CN7
CN20
CN6
How to remove the front cover How to Attach the Front Cover
After installing the front cover onto the unit, hook three claws
at upper side of the cover securely. Then, push the center of
the front cover to lock the claws.
Tighten the 3
Assemble the cover of electric box.
screws.
Install the filter.
Remove the filters.
After removing 3 screws,
pull the
the
center of the front cover towards you and release
Pull the side faces (lower sections) of the front cover towards
you as shown in the figure and remove the cover.
1
2
Remove the front panel
Push the end of the right-side arm outward to release the
tab.
Move the left-side arm outward to release the left tab, and
then pull the panel towards you.
Insert the shaft of the left arm along the step on the unit into
the hole.
Securely insert the shaft of the right arm along the step on
the unit into the hole.
Make sure that the front panel is securely attached, and then
close the front panel.
Attaching the Front Panel
1
2
Push
Arm
SClaw
Claw Claw Claw
crew
Screw
remove the cover of electric box,
claws.
cover

This manual suits for next models

10

Other Hitachi Air Conditioner manuals

Hitachi RAC-70WPA User manual

Hitachi

Hitachi RAC-70WPA User manual

Hitachi RA-13JF1 Specification sheet

Hitachi

Hitachi RA-13JF1 Specification sheet

Hitachi RAS-10JH3 User manual

Hitachi

Hitachi RAS-10JH3 User manual

Hitachi RAK-18PPB User manual

Hitachi

Hitachi RAK-18PPB User manual

Hitachi airHome MultiPro RAM-G55N3HAE User manual

Hitachi

Hitachi airHome MultiPro RAM-G55N3HAE User manual

Hitachi RAC-30MH1 User manual

Hitachi

Hitachi RAC-30MH1 User manual

Hitachi RAS-S25YHA User manual

Hitachi

Hitachi RAS-S25YHA User manual

Hitachi RPC-1.5FSN3 User manual

Hitachi

Hitachi RPC-1.5FSN3 User manual

Hitachi RA-13JF2 Specification sheet

Hitachi

Hitachi RA-13JF2 Specification sheet

Hitachi RAS-S10CYT User manual

Hitachi

Hitachi RAS-S10CYT User manual

Hitachi RAD-18NH7A User manual

Hitachi

Hitachi RAD-18NH7A User manual

Hitachi airHome 300 User manual

Hitachi

Hitachi airHome 300 User manual

Hitachi RPK- Summit User manual

Hitachi

Hitachi RPK- Summit User manual

Hitachi CHL-MBS-01 User manual

Hitachi

Hitachi CHL-MBS-01 User manual

Hitachi RAC-8CH9 User manual

Hitachi

Hitachi RAC-8CH9 User manual

Hitachi RAF-25NH5 User manual

Hitachi

Hitachi RAF-25NH5 User manual

Hitachi RAC-18WEB User manual

Hitachi

Hitachi RAC-18WEB User manual

Hitachi RAS-10CE9 User manual

Hitachi

Hitachi RAS-10CE9 User manual

Hitachi RAS-10MH1 User manual

Hitachi

Hitachi RAS-10MH1 User manual

Hitachi RPC-1.5FSN3 Instruction Manual

Hitachi

Hitachi RPC-1.5FSN3 Instruction Manual

Hitachi RAS-70YHA User manual

Hitachi

Hitachi RAS-70YHA User manual

Hitachi Summit RAS-50YH5 User manual

Hitachi

Hitachi Summit RAS-50YH5 User manual

Hitachi RAS-18EH2 User manual

Hitachi

Hitachi RAS-18EH2 User manual

Hitachi RAS-30CX9S User manual

Hitachi

Hitachi RAS-30CX9S User manual

Popular Air Conditioner manuals by other brands

Toshiba RAS-13SKHP-E Service manual

Toshiba

Toshiba RAS-13SKHP-E Service manual

York F2FP040H06 User's information manual

York

York F2FP040H06 User's information manual

Daikin FTKS50EV1B Operation manual

Daikin

Daikin FTKS50EV1B Operation manual

Sears Kenmore P/N93SR-D02 owner's manual

Sears

Sears Kenmore P/N93SR-D02 owner's manual

AirStage ASUA7RLAV installation manual

AirStage

AirStage ASUA7RLAV installation manual

Stealth Designer SC-24CC-UM quick start guide

Stealth

Stealth Designer SC-24CC-UM quick start guide

McQuay MDB075D owner's manual

McQuay

McQuay MDB075D owner's manual

Panasonic CU-E9GFE-2 operating instructions

Panasonic

Panasonic CU-E9GFE-2 operating instructions

Tycoon TS2MVI32-09 Service manual

Tycoon

Tycoon TS2MVI32-09 Service manual

Midea PD series manual

Midea

Midea PD series manual

Technibel KPAFP125R5IA Series instruction manual

Technibel

Technibel KPAFP125R5IA Series instruction manual

EIC Solutions AAC-145A-4XT Series Installation and operation manual

EIC Solutions

EIC Solutions AAC-145A-4XT Series Installation and operation manual

Lennox FLEXY FX 025 Application guide

Lennox

Lennox FLEXY FX 025 Application guide

Sanyo THX2452 user manual

Sanyo

Sanyo THX2452 user manual

CLIMAVENETA i-ACCURATE i-AX Installation manual - user and maintenance

CLIMAVENETA

CLIMAVENETA i-ACCURATE i-AX Installation manual - user and maintenance

Panasonic CS-YS9TKV operating instructions

Panasonic

Panasonic CS-YS9TKV operating instructions

Matsui MAT-9KACW manual

Matsui

Matsui MAT-9KACW manual

INVENTOR P7MVI-09WiFi user manual

INVENTOR

INVENTOR P7MVI-09WiFi user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.