Honeywell Home SiXCOMBO-CN Assembly instructions

1
SiXCOMBO-CN
Combination Smoke/Carbon Monoxide (CO) Detector w/Built-in Wireless
Transmitter (features voice and 360 degree viewable LED ring)
Installation and Setup Guide
This device is intended for use with Honeywell Home control panels that support SiX series devices.
Before installing detectors, please thoroughly read these installation instructions and read the
Limitations of Fire Alarm Systems Insert (P/N 800-15144 5/13), System Smoke Detectors
Application Guide (P/N SPAG9101 7/12), and Limitations of Carbon Monoxide Detectors (P/N
K14670V1 4/8 Rev B).
See Quick Installation Guide I56-6225 – https://mywebtech.honeywellhome.com.
FEATURES
•Multi-Criteria Sensing: uses four
sensing elements to react faster
while minimizing false alarms:
- Photoelectric smoke sensor
detects airborne smoke
particles
- Carbon Monoxide (CO) sensor
detects smoldering fires
- Infrared (IR) sensor measures
ambient light and flame
signatures, such as flame
flicker
- Heat detection monitors for
dangerous rise in temperature
•One Go / All Go: all smoke
detectors in the system
programmed as one-go-all-
go will sound on alarm.
•CO Detector End-of-Life
reporting (detector needs
replacing)
•Smoke detector maintenance
reporting (detector needs
cleaning)
•Low Battery Detection
Table 1: Operation Modes
MODE
Status LED
(Top)
LED Windows
(Side)
Sounder Speaker
Power Up Blink Green,
every 2 secs Dark Silent
Voice welcome,
instructions after first
time power up or
after default
Normal
(Standby)
Single Blink
Green every
10 secs
Dark Silent Silent
Smoke
Alarm
Blink Red
every 10 secs
Blink red Temp-3
Voice smoke
warning
Heat
Alarm
Blink Red
every 10 secs
Blink red Temp-3
Voice smoke
warning
CO Alarm
Blink Red
every 10 secs
Blink blue Temp-4
Voice CO
warning
Powered
Down
Dark Dark Silent Silent
ENROLLMENT
The SiXCOMBO has a unique MAC ID number. The heat,
smoke, and CO are assigned to loops 1-3 respectively
and are enrolled in separate zones.
NOTE: Once enrolled, the device cannot be used with
another system until it is removed from the current
controller. See the 24-hour Enrollment Deletion
section below or the controller’s instructions.
Enroll the Device Services (Smoke, Heat, CO)
1. Remove the detector from the base plate (tamper
switch must be faulted when enrolling).
2. Put the control panel in Programming mode, when
prompted:
3. Pull the battery tab to activate enrollment process (be
sure batteries are seated properly to avoid a false low
battery condition). If the battery tab has already been
removed and the unit is powered up, press either Test
switch for less than 3 seconds to activate the
enrollment process.
4. The device attempts enrollment (green LED flashes about 8 seconds). If
successful, the green LED lights steady for 3 seconds and the device
announces successful enrollment.
If the LED does not light steady, enrollment failed. Retry by pressing either
Test switch for less than 3 seconds.
All services (Smoke, Heat, and CO) are automatically enrolled in sequential
(or next available) zone numbers with the following default attributes:
Zone Device Type
Zone Response
Type
Smoke
Det.
Smoke Detector Fire No Verification
Heat Det.
Heat Sensor
Fire No Verification
CO Det.
Carbon Mono.
Det.
Carbon Monoxide
NOTE: Maintenance and CO End-of-Life are automatically enrolled for
the respective smoke and CO zones. Contact ID code E386 “Low
Maintenance Smoke” is sent for the CO zone at End-of-Life and Contact ID
code E385 “High Maintenance Smoke” is sent for the Smoke Zone when dirty.
Supervision: Detector supervision is factory set for 1 minute and is not
programmable.
24-Hour Enrollment Deletion
Use this procedure within 24 hours of initial enrollment to delete this
device from the controller. This allows reenrollment in a specific
controller in case enrollment in that controller failed. This resets the
device to factory default settings and removes the communication link
data in the controller in which it is enrolled.
1. Press and hold both the Smoke and CO test switches
simultaneously until the welcome message announces, then
release.
2. Wait for the green LED to flash rapidly.
3. Press and hold both switches again for one second and release.
4. LED blinks rapidly after 15 seconds, confirming deletion.
LANGUAGE SELECTION
1. Press and hold both the Smoke and CO test switches
simultaneously for 5 seconds until Welcome message is
announced, then release. The green light flashes rapidly.
2. Pres the Test button corresponding to the desired language:
English: Press the Smoke (•) test button
Spanish: Press the CO (••) test button
MOUNTING
After enrolling, verify adequate signal strength with the
device in its intended mounting location. Adjust the
device location and orientation as necessary.
1. Using two supplied screws and anchors, mount the
base.
2. Attach the smoke detector to the mounting base
with a clockwise motion.
3.Test each detector as described in the Testing
section.
4. Confirm all desired signals have been received by
the Central Station.
NOTE: NFPA 72 recommends the installation of
detectors only after completing construction or any
other dust producing activity.
NOTE: This device should not be located within 5 ft.
(1.5 m) of any cooking appliance.

2
TESTING
Test communications between the detector and the control panel. The
detector mode has two test buttons; one for smoke testing and one for
CO testing.
The detector may also be functionally tested using canned smoke and
canned CO. If the detector fails any of the test methods, the detector
should be replaced.
NOTE: Testing the detector will activate the alarm and send a signal to the
panel. Before testing, notify the proper authorities to avoid any
false alarms.
Smoke Test (Alarm Test)
Press and hold the Smoke Test button for 1 to 2 seconds. The
detector will sound and illuminate per Table 2 and send a smoke alarm
signal to the control panel (all programmed smoke detector loops are
signaled). Verify that the smoke alarm signal was received at the
control panel.
Smoke System Test (Functional Smoke Test)
CANNED SMOKE NOTE: Detector sounds an alarm when using
canned smoke ONLY when in Functional Test mode (canned smoke
does not cause alarm sounding when in normal mode.)
Press and hold the Smoke Test button for 3 to 5 seconds to enter the
functional smoke test mode. See Functional Smoke Test section below.
Functional Smoke Test
With the detector in smoke system (functional) test mode, spray
canned smoke into the detector. The canned smoke that can be used
and is approved for test include: Home Safeguard Industries 25S, SDi
CHEK02 and CHEK06, SDi SOLOA4, and SDi SMOKESABRE.
1. The detector will sound and illuminate per Table 2 and a smoke
alarm signal will be sent to the panel.
2. Verify the smoke alarm signal was received by the control panel.
CO Test (Alarm Test)
Press and hold the CO Test button for 1 to 2 seconds. The control
panel should display and sound a CO alarm (all programmed CO
detector loops are sent).
CO System Test (Functional CO Test)
CANNED CO NOTE: Detector sounds an alarm when using canned
CO ONLY when in Functional Test mode (canned CO does not
cause alarm sounding when in normal mode.)
Press and hold the CO Test button for 3-5 seconds to enter the
functional gas test mode. See Functional Gas Test section below.
Functional Gas Test
Solo C6 brand canned CO may be used to verify the detector’s ability to
sense CO by utilizing the RealTest® feature as follows:
1. Press and hold the CO test button for 3 to 5 seconds. The green
LED will start blinking once per second indicating the detector is in
RealTest® mode. (If the detector will not go into RealTest® mode,
the CO sensor may be in fault or at end-of-life.)
2. While the green LED is blinking once per second, spray a small
amount of canned CO directly into the CO gas entry port.
3. Upon successful gas entry and if functioning properly, the detector
will go into CO alarm and send an alarm to the control panel.
4. The CO test will automatically clear when the CO clears from the
sensor or in 30 seconds if no CO was introduced.
HUSH FEATURE / ALARM SILENCE
If required, the audible alarm for smoke and CO conditions can be
silenced for 5 minutes by pushing the “Test/Hush” button. In addition,
low battery chirping can be silenced for 12 hours when the Test/Hush
button is pressed.
During a Smoke alarm, if an alarm condition still exists after the 5-
minute hush period, the alarm will sound. The hush feature will not
operate at levels above 4%/ft. smoke concentration.
During a CO alarm, if carbon monoxide is still present after the 5-minute
hush period, the alarm will sound. The hush feature will not operate at
levels above 350 ppm (parts per million) carbon monoxide.
CO SENSOR END-OF-LIFE FEATURE
When the CO sensor has passed end-of-life, a trouble signal will be
sent to the control panel (if programmed). This indicates that the CO
sensor inside the detector must be replaced. If unresolved for 30 days,
the detector will chirp every 45 seconds. The typical life of the CO
sensor is ten years from the date of manufacture. It is recommended to
periodically check the “Replace by” date located on the label on the
back of the detector head.
Table 3: Carbon Monoxide Detector: Events &
Contact ID Codes
Event
Panel Display
CS Report
Alarms
CO Alarm
CO alarm (CID 162)
Test
CO Alarm
CO alarm (CID 162)
Low Battery Lo Bat
RF low-battery
(CID 384)
Detector
Supervision
CO Supervision
Loss of RF Supervision
(CID 381)
Detector end-
of-life/trouble
Low
Maintenance
Sensor trouble - (CID
386) Low Maintenance
Tamper
Disarmed or Armed
= Tamper
RF sensor tamper
(CID 383)
Table 4: Smoke and Heat Detector: Events &
Contact ID Codes
Event
Panel Display
CS Report
Alarms
Fire Alarm
Fire Alarm (CID 110)
Test
Fire Alarm
Fire Alarm (CID 110)
Low Battery Lo Bat
RF low-battery
(CID 384)
Detector
Supervision
Smoke or Heat
Supervision
Loss of RF Supervision
(CID 381)
Detector
Maintenance
(Needs
cleaning)
Maintenance
Smoke
Smoke Detector
High Sensitivity
(CID 385)
Tamper
Disarmed or Armed
= Tamper
RF sensor tamper
(CID 383)
Table 2: LED Indication & Sounder during Test and Trouble
MODE
Status LED
(Top)
Side LED
Windows
Sounder Speaker
Smoke Test
Blink Green
once every
second
Dark Temp-3
Warning of
alarm signal
transmission.
Voice smoke
warning
Functional SMOKE
Test – Waiting for
canned smoke
entry
Blink Green
once a sec Dark Silent
Voice
instructions
and warning
of alarm
signal
Functional
SMOKE Test -
Successful smoke
entry
Blink Red
every 10 secs
Blink Red
every 10
secs
Temp-3
no voice
announcem
ent
RealTest™
Functional CO gas
entry test – Waiting
for gas entry
Blink Green
once per
second
Dark Silent
Voice
instructions for
testing; warning
of alarm signal
RealTest™
Functional CO gas
entry test -Upon
successful gas
entry
Blink Red
once every
10 secs
Blink blue
every
10 secs
Modified
Temp-4
Voice carbon
monoxide
warning
Low Battery Blink Amber
every 10 secs Dark
Chirp
every 45
secs
after 7
days
Voice instruc-
tions when
chirp is
silenced by
pressing either
test button
Smoke
Maintenance
Blink Amber
every 5 secs Dark Silent
Voice smoke
maintenance
instructions if
either test
button is
pressed
CO Trouble
Double Blink
Amber every
5 secs
Dark Silent Silent
CO End of Life –
First 29 days
Double Blink
Amber every
3 secs
Dark Silent
Voice end-of-
life instructions
when either test
button is
pressed
CO End of Life –
after 30 days
Double Blink
Amber every 3
secs
Dark
Chirp
every 45
secs
Voice end-of-life
instructions
when
either test button
is pressed
Power Up Blink Green,
for 30 secs Dark Silent
Language set
instructions only
on first time
power-up
Normal (Standby)
Single Blink
Green every
10 secs
Dark Silent Silent

3
LED INDICATORS
The SiXCOMBO-CN has a multi-color top LED:
Green = Supervisory indication; blinks during power on,
reset, and during normal operation
Amber = Signal maintenance and trouble events
Red = Alarm condition (either Smoke, CO, or Heat)
Side LED windows indicate alarms:
Red = smoke
Blue = CO
CLEANING
IMPORTANT: This detector must be tested and maintained
regularly following NFPA-72 requirements. The detector should
be cleaned at least once a year.
NOTE: When household cleaning supplies or other similar
contaminants are used, the space must be well ventilated to
prevent false alarms.
1. Remove the detector from the base plate by turning
counterclockwise.
2. Clean the outside casing with a cloth. Ensure that the holes
on the front of the alarm are not blocked with dirt and dust.
Canned air can be used to remove any dust or debris.
3. Reattach the detector to the base plate by rotating
clockwise.
4. Test the detector to insure it is fully functional. (See Testing
section).
5. Notify the proper authorities and Central Station when the
system is back in service
REPLACING THE BATTERIES
CAUTION: The batteries used in this device may present a fire
or chemical burn hazard if mistreated. Do not recharge,
disassemble, heat above 100°C (212°F) or dispose of in fire.
Use only Panasonic CR123A Lithium batteries. Use of other
batteries may present a risk of fire or explosion. Keep used
batteries away from children. Dispose of used batteries
properly.
Remove old batteries. Wait 10 seconds and then replace with
four new batteries. To avoid a low battery indication when
installing new batteries, all 4 batteries must be installed within
15 seconds of installing the first one. Any low battery condition
that may have occurred should clear when the base plate is
installed.
NOTE: Constant exposure to high or low temperature or high
humidity may reduce battery life.
LIMITED LIFE OF CO SENSOR
This detector is manufactured with a long-life electrochemical
carbon monoxide sensor. Over time the sensor will lose
sensitivity and will need to be replaced. The life span of the CO
sensor is approximately ten years from the date of manufacture.
Periodically check the detector’s replacement date. Refer to the
‘replace by’ sticker placed on the side of the detector. This is the
date beyond which the device may no longer detect carbon
monoxide accurately and should be immediately replaced.
Reminder: This detector is also equipped with a feature that will
signal the panel once the CO sensor has passed the end of its’
useful life. If this occurs, it is time to replace the detector.
What to do if the detector goes into CO alarm:
If the detector goes into CO alarm (4 beeps), immediately
move to a spot where fresh air is available, preferably
outdoors, where the air is safe and call your security service
provider. Tell your provider the detector alarm status, and that
you require professional assistance in ridding your home of the
carbon monoxide.
This detector is NOT:
•A substitute for the proper servicing of fuel-burning
appliances or the sweeping of chimneys.
•To be used on an intermittent basis or as a portable alarm
for the spillage of combustion products from fuel-burning
appliances or chimneys.
Carbon monoxide gas is a highly poisonous gas which is
released when fuels are burnt. It is invisible, has no smell and
is therefore is impossible to detect with the human senses.
Under normal conditions in a room where fuel burning
appliances are well maintained and correctly ventilated, the
amount of carbon monoxide released into the room by
appliances should not be dangerous.
WARNINGS:
•This device will only indicate the presence of carbon
monoxide gas at the sensor. Carbon monoxide gas may be
present in other areas.
•This device is designed to protect individuals from the acute
effects of carbon monoxide exposure. It will not fully
safeguard individuals with specific medical conditions. If in
doubt consult a medical practitioner.
•Installation of the device should not be used as a substitute
for proper installation, use, and maintenance of fuel-burning
appliances, including appropriate ventilation and exhaust
systems.
MAINTENANCE
Do not paint, and do not use cleaning agents, bleach or
polish the detector.
NOTE: Before performing any maintenance on the detector,
notify the proper authorities and Central Station that
maintenance is being performed and the system will be
temporarily out of service. Disable the zone or system
undergoing maintenance to prevent any unwanted alarms.
Power must be removed from the detector before performing
maintenance of any kind.
The SiXCOMBO-CN detector reports maintenance issues to
the control panel and communicates them visually and audibly
per Table 2.
Trouble feature: When the sensor (supervision) is in a trouble
condition (such as a detector that is dirty or CO sensor non-
functioning), the detector will send a trouble signal to the
control panel. Depending on the issue, the detector must then
be serviced or replaced.
NOTE: Smoke detectors are not to be used with detector
guards unless the combination is evaluated and found suitable
for that purpose.
SYMPTOMS OF CARBON MONOXIDE POISONING
Carbon monoxide bonds to the hemoglobin in the blood and
reduces the amount of oxygen being circulated in the body.
The following symptoms are examples taken from NFPA 720;
they represent approximate values for healthy adults.
Exposure Symptoms
Mild Exposure
Headaches, running nose, sore eyes, often described as
‘flu’ like symptoms
Medium Exposure
Dizziness, drowsiness, and vomiting
Extreme Exposure
Unconsciousness, brain damage, death
Many cases of reported carbon monoxide poisoning indicate
that while victims are aware that they do not feel well, they
become so disoriented that they are unable to save
themselves by either exiting the building or calling for
assistance. Also, young children, elderly and pets may be the
first to be affected. This should be discussed with ALL
members of the household.
CO ALARM ACTIVATION
Per UL standard 2075, the SiXCOMBO-CN detector has been
tested to the sensitivity limits defined in UL standard 2034.
CO Alarm Thresholds
Parts per Million (ppm)
Detector Response Time (Min.)
30+-3ppm
No alarm within 30 days
70+-5ppm
60-240
150+-5ppm
10-50
400+-10ppm
4-15
SPECIFICATIONS
Electrical Specifications
Voltage:......................................................................3 volts DC
Battery Type:..................................................... CR123A lithium
Battery Manufacturer:.......................... Panasonic CR123A only
Number of Batteries: ................................................................ 4
Sensitivity:.... UL limits .9 to 3.50%/ft / ULC limits .9 to 3.08 %/ft
Thermal alarm:.................................................... 135° F (57° C)
Audible Signal: ................................................................ 85dBA
Physical Specifications
Diameter: .................................6.3 in. Diameter x 1.65 in. Thick
(16.002 cm x 4.19 cm Thick)
Weight:............................................................... 14.3 oz (406 g)
Operating Temperature Range: ........... 38° - 100° F (0° - 38° C)
Storage Temperature Range: ..............14 - 158° F (-10 - 70° C)
Operating Humidity Range:......................................20-95% RH

For information on creating a family escape plan refer to the control’s user guide in which this device is being installed.
(i) WARNING
Actuation of this device indicates the presence of carbon monoxide (CO) which can KILL YOU.
If alarm signal sounds (3 pulses for Fire/Heat and 4 pulses for CO):
(1) immediately move to fresh air - outdoors or by an open door or window. Check that all
persons are accounted for. Do not re-enter the premises or move away from the open door/window until the emergency services
responders have arrived, the premises have been aired out, and your alarm remains in its normal condition;
(2) call your emergency local service (fire department or 911)
(ii) if “service” signal sounds (See “LED Indication & Sounder during Test and Trouble” Table) take appropriate action for each signal.
CAUTION
This device will only indicate the presence of carbon monoxide gas at the sensor. Carbon monoxide gas may be present in other
areas. This device is designed to protect individuals from the acute effects of carbon monoxide exposure. It will not fully safeguard
individuals with specific medical conditions. If in doubt consult a medical practitioner.
APPROVAL LISTINGS
FCC
Listed to UL 268 & UL 2075.
CSA 6.19 MAR2001 (R2016)
Other Standards: RoHS
FEDERAL COMMUNICATIONS COMMISSION (FCC) & INDUSTRY CANADA (IC) STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual.
Unauthorized changes or modifications could void the user's authority to operate the equipment.
CLASS B DIGITAL DEVICE STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for
your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the
manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the
limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• If using an indoor antenna, replace it with a quality outdoor antenna.
• Reorient the receiving antenna until interference is reduced or eliminated.
• Move the radio or television receiver away from the receiver/control.
• Move the antenna leads away from any wire runs to the receiver/control.
• Plug the receiver/control into a different outlet so that it and the radio or television receiver are on different branch circuits.
• Consult the dealer or an experienced radio/TV technician for help.
INDUSTRY CANADA CLASS B STATEMENT
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada.
FCC / IC STATEMENT
This device complies with Part 15 of the FCC Rules, and Industry Canada’s license-exempt RSSs. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including
interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC et exempt de licence RSS d’Industrie Canada. Son fonctionnement est
soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer d’interférences nuisibles. (2) Cet appareil doit accepter toute
interférence reçue y compris les interférences causant une réception indésirable.
Responsible Party / Issuer of Supplier’s Declaration of
Conformity: Honeywell International, 2 Corporate Center
Drive., Melville, NY 11747, Ph: 516-577-2000
Partie responsable / Émetteur de la déclaration de conformité
du fournisseur : Honeywell International, 2 Corporate Center
Drive., Melville, NY 11747, Tél. 516 577-2000
SUPPORT & WARRANTY
For the latest documentation and online support information, please go to:
https://mywebtech.honeywellhome.com/
For the latest warranty information, please go to:
https://www.security.honeywellhome.com/hsc/resources/wa/index.html
For patent information,, please go to:
https://www.resideo.com/patent
MyWebTech
Warranty
Patents
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS USED FOR DETAILS
REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
2 Corporate Center Drive
P.O. Box 9040, Melville, NY 11747
© 2018 Resideo Technologies, Inc.
www.resideo.com
Agile Ref: 800-24314-1 7/18 Rev B
I56-6241-001 7/18
The Honeywell Home Trademark is used under
license from Honeywell International Inc.
Other Honeywell Home Gas Detector manuals