ZAPP utilizes a free topology transceiver (FTT10A) Link
Power compatible LONWORKS®network that allows daisy-
chain, loop, and star network configurations or any
combination thereof.
Depending upon the LONWORKS ® network configuration
used, one or two termination modules may be required (see
Fig. 4). Different connections to the termination module are
necessary, depending upon whether it is used in a singly- or
doubly-terminated network configuration.
NOTES:
— The LONWORKS ® network is insensitive to polarity,
eliminating installation errors due to miswiring.
—For installations, try to avoid areas of high
electromagnetic noise (EMI).
Range of RF Transmission
Because of ZAPP's radio-frequency characteristics, it is not
possible to exactly define its transmission range.
The transmission range is comparable to that of cordless (not
cellular!) telephones, i.e. about 30 meters inside a building.
As a rule of thumb, the signals can travel through one wall
and one ceiling or through two walls.
It is recommended that you always first test ZAPP in the
actual environment in which it is to operate. Use LonMaker or
EXCELON in conjunction with nvoRfState.LastCommand to
verify a successful transmission from the handheld unit to the
receiver.
Wiring Details
Fig. 5 illustrates the terminal assignments of the ZAPP
receiver. Refer to job drawings for specific wiring diagrams.
Connections to the ZAPP receiver are made at an internal
terminal block accessible beneath the front cover. No tools
are required to remove the front cover.
1. Simply pull away the cover from the sub-base as
shown in Fig. 6.
Use a minimum wire size of 20 AWG (0.5 mm2) for all
input/output connections. The maximum length of all
input/output cables is 65 ft (20 m).
Wire to the terminal blocks as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Ensure that the wire entering the terminal block does
not extend above the numbered face of the terminal
block to avoid contact between the wires and the
printed circuit board on the underside of the front
cover (see Fig. 7).
TERMINATION
MODULE (209541B)
BROWN
ORANGE
5
6
7
8
5
6
7
8
Fig. 4. Termination module connection (daisy-chain
network configuration)
ZAPP RECEIVER
L
ON
W
ORKS
NETWORK IN
L
ON
W
ORKS
NETWORK OUT
1
2
3
4
5
6
7
8
24 VAC
120/240 VAC
24 VAC
24 VAC
24 VAC
LonWorks
LonWorks
LonWorks
LonWorks
24 VAC
24 VAC COM
Fig. 5. ZAPP receiver terminal assignments
Fig. 6. Terminal cover removal
1
2
3
4
5
6
7
9
10
8
Fig. 7. Terminal box connections