HORNER HE800FOX100 Installation instructions

1 PRODUCT DESCRIPTION
For detailed installation, configuration and other information, refer to the hardware manual of the
controller you are using. See the Additional References section in this document.
The FOX100 allows an OCS/RCS to connect up to five Fiber Optic Expansion bases and hubs (i.e.,
FOX104 and FOX404).
Note: The FOX100 is designed for use only with the following OCS/ RCS controllers: OCS110 /
OCS210 / Graphic OCS250, and RCS250.
2 FOX SPECIFICATIONS
Table 1 – FOX100 Hub and Base Specifications
Maximum number of stacks (total
number of hubs and bases) 5
Maximum number of cable drops to
any specific hub or base 3 (See Section Five for Example Setups.)
Maximum length of Fiber Optic cable 10 Meters per Drop
Base ID# Each Base or Hub must have a unique Base ID #.
Expansion I/O EIAJ RC-5720 Plastic Fiber, TX+RX 10m per drop max host (OCS or
hub) to base
Type of Fiber Optic Cable EIAJ RC-5720 (RC)
Primary Power 9-30VDC @ 400mA maximum
Power Draw 9-30VDC @ 400mA maximum
Height 4.25” (108 mm)
Width 6.63” (168.3 mm)
Mounting Depth 4.7” (119.4 mm)
Operating Temperature 32 - 122°F (0 - 50°C)
Humidity 5% to 95% non-condensing
08 June 2005 MAN0509-03
Fiber Optic Expansion Module
(HE800FOX100)
Products Specifications
and Installation Data

PAGE 2 08 June 2005 MAN0509-03
001FOX007
IN
FIBER I/O
TO REMOTE BASE
OUT
3 INSTALLATION
Refer to the hardware manual of the controller you are using for more information. (See the Additional
References section in this document.)
3.1 Connectors
The FOX100 must be placed in the first slot of the controller. For Ethernet capability, the SmartStack
Ethernet Module (ETN1xx) is plugged into the FOX100. (In this case, the ETN needs to occupy the
second slot of the controller.)
Note: The FOX100 has a 10-pin connector, which is reserved for factory use only.
Figure 1 – FOX100 Connectors
Figure 2 – FOX100 Connectors
3.2 Fiber Optic Cable Installation
Important considerations for installing the FOX include the following guidelines:
a. To ensure reliable communication between the FOX base and OCS/RCS module, high quality
cables need to be installed. See Table 2 for fiber cable part numbers.
b. The maximum fiber optic cable distance is 10 meters between drops.
c. During installment of the fiber optic cable, all direction changes need to adhere to a Minimum
Bend Radius of one inch (25.44mm).
Figure 3 – Fiber Optic Cable Bend Radius
FIBER
OPTIC
MODULE
IN OUT
FIBER I/O
TO REMOTE BASE
001FOX010
1.00” (25.4mm) Min.
Bend Radius
001FOX011
2.00” (50.8mm)
Min. Diameter

MAN0509-03 08 June 2005 PAGE 3
FOX100
FIBER
OPTIC
MODULE
FIBER
OK
001FOX009
MODULE
OK
4 LEDs
Figure 4 – FOX 100 LEDs
Table 2 – LEDs (FOX100)
LED Meaning
Module OK ON if firmware is loaded and operating properly.
Fiber OK ON indicates a Fiber carrier is being received from first base/hub.

PAGE 4 08 June 2005 MAN0509-03
5 Example Setups
The following graphics depict the use of a FOX100 in a variety of setups.
The FOX100 allows an OCS/RCS to connect up to five Fiber Optic Expansion bases and hubs (i.e.,
FOX104 and FOX404). When the FOX100 / 110 is used with a FOX104 or FOX404, they extend a high-
speed OCS/RCS backplane enabling SmartStack I/O Modules to be mounted several meters from the
OCS/RCS. They also significantly increase the number of SmartStack I/O modules supported by one
OCS/RCS.
Figure 5 – OCS/RCS to FOX404 (Single Hub) via FOX100 / FOX110
001OCS010-R2
4 3 2 1
HOST
Color-Touch
OCS (Or) (Or) Using FOX100:
RCS250
Using FOX100:
OCS110,OCS210,
Graphic OCS
(OCS250)
HUB
FOX404

MAN0509-03 08 June 2005 PAGE 5
Figure 6 – OCS/RCS to FOX (One Hub [FOX404] and Multiple Bases [FOX104])
via FOX100
HOST
4 3 2 1
HOST HOST
001OCS012-R2
HOST
Color-Touch
OCS (Or) (Or) Using FOX100:
RCS250
Using FOX100:
OCS110,OCS210,
Graphic OCS
(OCS250)
HUB
FOX404 FOX104
FOX104
FOX104

PAGE 6 08 June 2005 MAN0509-03
Figure 7 – OCS/RCS to FOX (Multiple Hubs [FOX404] and Bases [FOX104])
via FOX100
HOST HOST
4 3 2 1
HOST HOST
001OCS011-R2
HOST
4 3 2 1
Color-Touch
OCS (Or) (Or)
Using FOX100:
RCS250
Using FOX100:
OCS110,OCS210,
Graphic OCS
(OCS250)
HUB
FOX404
HUB
FOX404
FOX104 FOX104
FOX104

MAN0509-03 08 June 2005 PAGE 7
6 SAFETY
All applicable codes and standards need to be followed in the installation of this product.
When found on the product, the following symbols specify:
For detailed installation and a handy checklist that covers panel box layout requirements and minimum
clearances, refer to the hardware manual of the controller you are using. (See the Additional
References section in this document.)
• All applicable codes and standards need to be followed in the installation of this product.
• For I/O wiring (discrete), use the following wire type or equivalent: Belden 9918, 18 AWG or
larger.
Adhere to the following safety precautions whenever any type of connection is made to the module.
• Connect the green safety (earth) ground first before making any other connections.
• When connecting to electric circuits or pulse-initiating equipment, open their related breakers. Do
not make connections to live power lines.
• Make connections to the module first; then connect to the circuit to be monitored.
• Route power wires in a safe manner in accordance with good practice and local codes.
• Wear proper personal protective equipment including safety glasses and insulated gloves when
making connections to power circuits.
• Ensure hands, shoes, and floor are dry before making any connection to a power line.
• Make sure the unit is turned OFF before making connection to terminals. Make sure all circuits
are de-energized before making connections.
• Before each use, inspect all cables for breaks or cracks in the insulation. Replace immediately if
defective.
Warning: Consult user documentation. Warning: Electrical Shock Hazard.
WARNING: To avoid the risk of electric shock or burns, always connect the safety (or earth)
ground before making any other connections.
WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly
recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the
source as possible.
WARNING: Replace fuse with the same type and rating to provide protection against risk of
fire and shock hazards.
WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure
indicates a defective condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with the construction and operation of
this equipment and the hazards involved should install, adjust, operate, or service this
equipment. Read and understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in severe bodily injury or
loss of life.

PAGE 8 08 June 2005 MAN0509-03
7 ADDITIONAL REFERENCES
The following table indicates the hardware manual numbers for the controller you are using. Hardware
manuals contain detailed installation, configuration and other pertinent information. See the Technical
Support section in this document for the web site address to download references and obtain revised
editions.
Additional References
Controller Manual Number
OCS NX Series Hardware
e.g. HE-NX220, HE-NX221, HE-NX250, HE-NX251 MAN0781
Operator Control Station Hardware (OCS, OCX)
e.g., OCS1XX / 2XX; Graphic OCS250
Remote Control Station Hardware (RCS [except
RCS116], RCX)
e.g., RCS210, RCS250
MAN0227
Color Touch OCS Hardware
e.g., OCS300, OCS301,OCS350, OCS351
e.g., OCS451, OCS551, OCS651 MAN0465
OCS LX Series Hardware
e.g., LX280 / LX300; RCS116 MAN0755
MiniOCS / MiniRCS / MiniOCX / MiniRCX Hardware
e.g., HE500OCSxxx MAN0305
Other Useful References
Cscape Programming and Reference MAN0313
DeviceNet™Implementation SUP0326
Wiring Accessories and Spare Parts Manual MAN0347
8 TECHNICAL SUPPORT
For assistance and manual updates, contact Technical Support at the following locations:
North America:
(317) 916-4274
www.heapg.com
email: [email protected]
Europe:
(+) 353-21-4321-266
www.horner-apg.com
email: [email protected]
Table of contents
Other HORNER Control Unit manuals
Popular Control Unit manuals by other brands

Nice
Nice TT6 Instructions and warnings for installation and use

ABB
ABB Relion SAM600 Applications manual

DINA
DINA Safeline DNSL-DS Original instruction manual

Stone
Stone STWA121WT-01 Equipment manual

Carrier
Carrier AppController OPN-APP Installation and startup guide

NOXAS
NOXAS ID-O-Matic quick start guide

NuAire
NuAire NSC1-A-B Series installation manual

Advantech
Advantech USB-5801 Startup manual

PROPOINT
PROPOINT 8688848 quick start guide

Bosch
Bosch Rextroth Indramat RECO R-IB IL CNT Applications manual

power automation
power automation PA 8000 installation instructions

Burkert
Burkert 6228 operating instructions