
3.3 Operating modes
The RoofVent®RP has the following operating modes:
■Ventilation
■Ventilation (reduced)
■Air quality
■Recirculation
■Exhaust air
■Supply air
■Standby
The TopTronic®C control system regulates these operating
modes automatically for each control zone in accordance
with the specifications in the calendar. The following points
also apply:
■The operating mode of a control zone can be switched
over manually.
■Each RoofVent®unit can operate individually in a local
operating mode: Off, Recirculation, Supply air, Exhaust
air, Ventilation.
Code Operating mode Description
VE Ventilation
The unit blows fresh air into the room and exhausts polluted room
air. The room temperature set value day is active. Depending on the
temperature conditions, the system continuously controls:
■the energy recovery
■the heating/cooling
Supply air fan................... on 1)
Exhaust air fan................. on 1)
Energy recovery............... 0-100 %
Extract air damper............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
1) Adjustable flow rate
VEL Ventilation (reduced)
As VE, but the unit only operates with the set minimum values for
the supply and exhaust air volumes
Supply air fan................... MIN
Exhaust air fan................. MIN
Energy recovery............... 0-100 %
Extract air damper............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
AQ Air quality
This is the operating mode for demand-controlled ventilation of the
room. The room temperature set value day is active. Depending on
the temperature conditions, the system continuously controls:
■the energy recovery
■the heating/cooling
Depending on the room air quality or room air humidity, the system
operates in one of the following operating states:
AQ_REC ■Air quality Recirculation:
When air quality is good and air humidity appropriate, the unit
heats or cools in recirculation operation.
Like REC
AQ_ECO ■Air quality Mixed air:
When ventilation requirements are medium, the unit heats or
cools in mixed air operation. The supply and exhaust air volume
is based on the air quality.
Supply air fan................... MIN-MAX
Exhaust air fan................. MIN-MAX
Energy recovery............... 0-100 %
Extract air damper............ 50 %
Recirculation damper ....... 50 %
Heating/cooling ................ 0-100 %
AQ_VE ■Air quality Ventilation:
When ventilation requirements are high or the room air humidity
is too high, the unit heats or cools in pure ventilation operation.
The supply and exhaust air volume is based on the air quality.
Supply air fan................... MIN-MAX
Exhaust air fan................. MIN-MAX
Energy recovery............... 0-100 %
Extract air damper............ open
Recirculation damper ....... closed
Heating/cooling ................ 0-100 %
10
Roof Vent ®RP
Construction and operation
4 221 975-en-01