
20 I EN
If the flap closes too early, select positive values to extend the glowing phase.
If the flap closes too late, select negative values to shorten the glowing phase
5. Confirm the selected value by pressing OK button.
6. Select and confirm with the OK button to return to the main menu.
6.4 Settings of the circulation pump parameters (MODULE W) W
1. Choose MODULE W in the HOS main menu to open the circulation pump settings.
2. In the MODULE W menu, select:
· KP-START temperature setting (fireplace heat exchanger) of the start of the circulation pump.
· KP-STOP temperature setting (fireplace heat exchanger) of the stop of the circulation pump.
· WT-DIFF the difference between the water temperature in the heat exchanger and the average water temperature in the
accumulation tank. The circulation pump starts when the temperature in the heat exchanger is higher (of set difference) than the
average temperature in the accumulation tank.
· FT setting of the limit temperature in the fire chamber to start/stop the circulation pump.
· ALARM setting of the percentage value (accumulation tank charge). When value reached, sound notification starts.
· KPA regular start of the circulation pump function (off-season).
3. KP-START default set to 65 °C. Use the arrows to edit the temperature in a range 60–75 °C. Press OK to confirm.
4. KP-STOP default set to 60 °C. Use the arrows to edit the temperature in a range 50–70 °C. Press OK to confirm. (The device
does not allow setting the KP-STOP value higher than KP-START value).
5. WT-DIFF default set to 5. Use the arrows to edit the value in a range 0–10. Press OK to confirm.
6. FT default set to 65 °C. Use the arrows to edit the temperature in a range 60–100 °C. Press OK to confirm.
7. ALARM default set to 80 %. Use the arrows to change it in the range of 75–90 %. Press OK to confirm.
8. KPA default set to ON. Use the arrows to turn it OFF. If this parameter is active, the circulation pump starts once every 14 days for
3 minutes. After each restart of the device, the pump starts for 3 minutes as well.
9. Select and confirm with the OK button to return to the main menu.
MODULE W
KP-START
KP-STOP
WT-DIFF
FT
ALARM
KPA
6.5 Settings of the underpressure watcher parameters (MODULE U) U
1. Choose MODULE U in the HOS main menu to open the circulation pump settings.
2. In the MODULE U menu, select:
The KP START temperature value must always be at least 5°C higher than the KP STOP value. If you
set KP START or KP STOP out of this range, the second (not chosen) temperature will be updated
automatically in order to meet this condition.