HACCP
Actual temperature measurement for the HACCP h01
Last registered peak temperature h10
Selection of function and sensor for the HACCP function.
HACCPfunction.1=S4used(maybealsoS3).2=S5
h11 0 2 0 0
Alarm limit for the HAC CP function h12 -50.0°C 50.0°C 8.0°C 8.0°C
Time delay for the HACCP alarm h13 0 min. 240 min. 30 min. 30 min.
Select signal for the HACCP function. S4% (100% = S4, h14 0% 100% 100% 100%
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01- 0 hours 23 hours 0 hours 0hours
Six start times for defrost.
Setting of minutes.
0=OFF
t11- 0 min 59 min 0 min 0min
Clock - Setting of hours t07 0 hours 23 hours 0 hours 0hours
Clock - Setting of minute t08 0 min 59 min 0 min 0min
Clock - Setting of date t45 1 31 1 1
Clock - Setting of month t46 1 12 1 1
Clock - Setting of year t47 0 99 0 0
Miscellaneous
Delay of output signals after start-up o01 0 s 600 s 5 s 5s
Input signal on DI1. Function: o02 1 11 0 0
Network address o03 0 240 0 0
On/Off switch (Service Pin message) o04 OFF ON OFF OFF
Access code 1 (all settings) o05 0 100 0 0
9sed sensor type (Pt /PTC/NTC) o06 Pt ntc Pt Pt
Display step = 0.5 (normal 0.1 at Pt sensor) o15 no yes no no
Max hold time after coordinated defrost o16 0min 60min 20 20
Select signal for display view. S4% (100%=S4, 0%=S3) o17 0% 100% 100% 100%
Input signal on DI2. Function: o37 0 12 0 0
Configuration of light function (relay 4) o38 1 3 1 1
Activation of light relay (only if o38=2) o39 OFF ON OFF OFF
Rail heat On time during day operations o41 0% 100% 100 100
Rail heat On time during night operations o42 0% 100% 100 100
Rail heat period time (On time < Off time) o43 6 min 60 min 10 min 10 min
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All o46 0 2 0 0
Selection of EL diagram. See overview page 6 o61 1 10 1 1
Download a set of predetermined settings. See overview o62 0 6 0 0
Access code 2 (partly access) o64 0 100 0 0
Save the controllers present settings to the o65 0 25 0 0
Load a set of settings from the programming key o66 0 25 0 0
Replace the controllers factory settings with the present o67 OFF On OFF OFF
Service
Status codes are shown on page 17 S0-S33
Temperature measured with S5 sensor u09
Status on DI1 input. on/1=closed u10
Temperature measured with S3 sensor u12
Status on night operation (on or off ) 1=closed u13
Temperature measured with S4 sensor u16
Thermostat temperature u17
Read the present regulation reference u28
Status on DI2 output. on/1=closed u37
Temperature shown on display u56
Measured temperature for alarm thermostat u57
Status on relay for cooling u58
Status on relay for fan u59
Status on relay for defrost u60
Status on relay for railheat u61
Status on relay for alarm u62
Status on relay for light u63
Status on relay for valve in suction line u64
Status on relay for compressor 2 u67
7
*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***) With access code 2 the access to these menus will be limited
Factory setting
If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep both buttons depressed at the same time as you reconnect the supply voltage
AK-CC 210 Manual RS8EP402 © Danfoss 05-2014 21