  9. ICP DAS USA WF-2055 User manual

ICP DAS USA WF-2055 User manual

Other ICP DAS USA I/O System manuals

ICP DAS USA PIO-DA4 User manual

ICP DAS USA

ICP DAS USA PIO-DA4 User manual

ICP DAS USA M-7084 User manual

ICP DAS USA

ICP DAS USA M-7084 User manual

ICP DAS USA SG-3071 User manual

ICP DAS USA

ICP DAS USA SG-3071 User manual

ICP DAS USA tGW-700 Series User manual

ICP DAS USA

ICP DAS USA tGW-700 Series User manual

ICP DAS USA PET-7000 Series User manual

ICP DAS USA

ICP DAS USA PET-7000 Series User manual

ICP DAS USA CAN-2015C User manual

ICP DAS USA

ICP DAS USA CAN-2015C User manual

ICP DAS USA ET-2217CI User manual

ICP DAS USA

ICP DAS USA ET-2217CI User manual

ICP DAS USA A-812PG Instructions for use

ICP DAS USA

ICP DAS USA A-812PG Instructions for use

ICP DAS USA PISO-813 User manual

ICP DAS USA

ICP DAS USA PISO-813 User manual

ICP DAS USA I-7019R User manual

ICP DAS USA

ICP DAS USA I-7019R User manual

ICP DAS USA I-7017(F)C User manual

ICP DAS USA

ICP DAS USA I-7017(F)C User manual

ICP DAS USA ET-7000 series User manual

ICP DAS USA

ICP DAS USA ET-7000 series User manual

ICP DAS USA A-826 Series User manual

ICP DAS USA

ICP DAS USA A-826 Series User manual

ICP DAS USA WP-5238-CE7 User manual

ICP DAS USA

ICP DAS USA WP-5238-CE7 User manual

ICP DAS USA PET-7050 User manual

ICP DAS USA

ICP DAS USA PET-7050 User manual

ICP DAS USA M-7011 User manual

ICP DAS USA

ICP DAS USA M-7011 User manual

ICP DAS USA CAN-2024C User manual

ICP DAS USA

ICP DAS USA CAN-2024C User manual

ICP DAS USA I-7053 FG User manual

ICP DAS USA

ICP DAS USA I-7053 FG User manual

ICP DAS USA DIO-96/144 User manual

ICP DAS USA

ICP DAS USA DIO-96/144 User manual

ICP DAS USA I-7019R User manual

ICP DAS USA

ICP DAS USA I-7019R User manual

ICP DAS USA PCI-P16R16 Series Mounting instructions

ICP DAS USA

ICP DAS USA PCI-P16R16 Series Mounting instructions

ICP DAS USA tM-R5 User manual

ICP DAS USA

ICP DAS USA tM-R5 User manual

ICP DAS USA UA-2241M User manual

ICP DAS USA

ICP DAS USA UA-2241M User manual

ICP DAS USA I-2533CS Series User manual

ICP DAS USA

ICP DAS USA I-2533CS Series User manual

Popular I/O System manuals by other brands

WAGO 750-344 manual

WAGO

WAGO 750-344 manual

Teknim TWM-1887 Installation & user manual

Teknim

Teknim TWM-1887 Installation & user manual

Intelligent Appliance IA-2662-E user manual

Intelligent Appliance

Intelligent Appliance IA-2662-E user manual

BERGHOF ECC DIO 16/16 User handbook

BERGHOF

BERGHOF ECC DIO 16/16 User handbook

Advantech PCM-27J3AU Startup manual

Advantech

Advantech PCM-27J3AU Startup manual

Festo CP-E08-M12-CL manual

Festo

Festo CP-E08-M12-CL manual

Measurement Computing PCI-DAS64/M1/16 user guide

Measurement Computing

Measurement Computing PCI-DAS64/M1/16 user guide

Hitachi HX-RIO3 Series user manual

Hitachi

Hitachi HX-RIO3 Series user manual

NUUO SCB-A08 user manual

NUUO

NUUO SCB-A08 user manual

M-system R3Y-RS8 instruction manual

M-system

M-system R3Y-RS8 instruction manual

jablotron JB-110N user manual

jablotron

jablotron JB-110N user manual

Omron SYSMAC C200H Operation guide

Omron

Omron SYSMAC C200H Operation guide

DOLD SAFEMASTER M Safety Technique

DOLD

DOLD SAFEMASTER M Safety Technique

ABB OPT-MF-001 user manual

ABB

ABB OPT-MF-001 user manual

Omron SYSMAC C2000H Operation guide

Omron

Omron SYSMAC C2000H Operation guide

Helmholz TB20 manual

Helmholz

Helmholz TB20 manual

Automationdirect.com DL305 manual

Automationdirect.com

Automationdirect.com DL305 manual

WAGO I/O SYSTEM 750 750-833 manual

WAGO

WAGO I/O SYSTEM 750 750-833 manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

WF-2055 Quick Start RevB1.0 2016/09
1/8
Quick Start
「WF-2055」Package Checklist
The package includes the following items:

One WF-2055 module

One Quick Start

One software utility CD

One screw driver

One RS-232 cable (CA-0910)

One Antenna 2.4GHz - 5 dBi (ANT-124-05)
Note:
1.
If any of these items are missed or damaged, contact the local distributors
for more information. Save the shipping materials and cartons in case you
want to ship in the future.
2.
This document supports the RevB version for the WF-2055 module. For
the previous version, please refer the v1.x version quick start on the CD.
Appearance and pin assignments
Figure 1:Appearance of the WF-2055
WF-2055 Quick Start RevB1.0 2016/09
2/8
Table 1:I/O Connector - WF-2055
I/O Connector - WF-2055
Terminal No. Pin Assignment Terminal No. Pin Assignment
1 DI.COM 2 EXT.PWR
3DI7 4DO7
5 DI6 6 DO6
7 DI5 8 DO5
9 DI4 10 DO4
11 DI3 12 DO3
13 DI2 14 DO2
15 DI1 16 DO1
17 DI0 18 DO0
19 DI.GND 20 EXT.GND
Table 2: Power/Signal Connector
Power/Signal connector
Pin Assignment Description
F.G Frame Ground
+Vs +10 ~ +30 VDC
GND Power / RS-232 GND
RxD RS-232 RxD
TxD RS-232 TxD
Table 3: Operating Mode Selector Switch
Operating Mode Selector Switch
Mode Jumper Position Description
FW
Firmware update mode
OP
Firmware operation mode
Hardware Connection
Power and Serial port connection
The following figures describe the Power and the COM port to a serial device
via serial network.
WF-2055 Quick Start RevB1.0 2016/09
3/8
Figure 2:Power and Serial port wire connection
I/O connection
Figure 3:DI / DO wire connection
WF-2055 Quick Start RevB1.0 2016/09
4/8
Installation
Before use, associated hardware configuration, the steps described as
follows:
Step 1: Checking the WF-2000 series firmware operation mode
It needs to set the DIP switch to the "OP" position (operation mode), as
resetting the power, WF-2000 series will be in the operation mode.
Step 2: Serial port connection
WF-2000 series supports RS-232 serial communication. The circuit
configuration is as shown in Figure 2.
If you do not need parameter setting, this step can be omitted.
Step 3: Power connection
Connect the power supply to WF-2000 series' power terminator, as shown in
Figure 2.
WF-2000 series connection setting
WF-2000 Series Connection Configuration
Figure 5:Connection Configuration
WF-2055 Quick Start RevB1.0 2016/09
5/8
01、Net ID : The Unit Identifier in Modbus TCP/IP application data unit. This
case is set as "1".
02、IP Address:
WF-2000 series' IP address. Here set to "192.168.255.1".
03、Subnet Mask : Net Mask settings. Here set to "255.255.0.0".
04、Gateway : Gateway settings. Here set to "192.168.255.254".
05、Wi-Fi Mode : Wireless network connection mode settings. Here set to
"Limited AP" mode. (If select the "Limited AP" mode, the "DHCP Server"
function is enabled)
06、SSID : Service set identifier. Here set to "WF-2055".
07、Encryption : Encryption mode settings. Here set "NONE" (without
encryption).
08、Wireless Key : Wireless encryption Key. Here does not have the setting.
09、Wireless CH : Wi-Fi connection channel settings. Here set to "2".
10、Upload parameters : After completing the settings above, select the "RS-
232" interface, communication "Net ID" and "COM Num". Press "Write"
button to upload the parameters.
PC Wireless Network Configuration and Connection
01、TCP/IP Setting :
a. Entry the IP address as "192.168.255.x", where "x" is a number
between 1 and 254 except 1, Subnet mask as "255.255.255.0".
Finally, press "OK" button.
02、Wireless network connection :
a. View available wireless networks and you can see the "WF-2055"
wireless network in the list.
b. Select the "WF-2055" and press the "Connect" button.
c. After waiting for a while, there will appear connection success screen.
Figure 6:IP configuration interface Figure7:Connection interface
WF-2055 Quick Start RevB1.0 2016/09
6/8
Access I/O data
01、Connection with Modbus TCP utility
a. Open Modbus TCP utility and key in the IP address as "192.168.255.1",
Port as "502". Finally, press the "Connect" button.
Figure8:Modbus TCP utility Connection interface
b. Use the function code "0x0F", and set the reference number as "0x00"
to do the DO output control.
Figure 9:DO output control interface
c. Use the function code "0x01", and set the reference number as "0x00"
to get the DO output monitor data.
Figure 10:DO output monitor interface
d. Use the function code "0x02", and set the reference number as "0x00"
to get the DI input monitor data.
Figure 11:DI input monitor interface
WF-2055 Quick Start RevB1.0 2016/09
7/8
e. Use the function code "0x04", and set the reference number as "0x32"
to get the Counter monitor data.
Figure 12:Counter monitor interface
Table 3: (0xxxx) DO address
Begin Address Points Descriptions Range Access Type
00001 1~8 Digital Output 0=OFF, 1=ON R/W
00011 1~8
Clear
High Speed Counter 1=Clear W
00021 1~8
Clear
Low Speed Counter 1=Clear W
Table 4: (1xxxx) DI address
Begin Address Points Descriptions Range Access Type
10001 1~8 Digital Input 0=OFF, 1=ON R
Table 5: (3xxxx) AI address
Begin Address Points Descriptions Range Access Type
30051
1~16
(2 points/ Each
Channel)
High Speed Counter 0~4294967295 R
30071
1~16
(2 points/ Each
Channel)
Low Speed Counter 0~4294967295 R
WF-2055 Quick Start RevB1.0 2016/09
8/8
Troubleshooting
Item
Problem
Description
Solution
1 Power Failure
(PWR LED Off)
1. Please return to the ICP DAS for inspection and repair
2
WLAN connection
can not be
established
1. Make sure that the service set identifier device (SSID) settings
are the same.
2. Make sure Wi-Fi transmission Channel settings are the same.
3. Make sure encryption is set, encryption keys are the same
way
4. Make sure antenna is connected
5. Please confirm whether there are barriers on the scene. That
could result in poor signal quality.
3
TCP connection can
not be established
1. Make sure WLAN connection is established successfully
2. Make sure the network configuration is good (TCP / IP Port,
Local IP, Net Mask)
4 How to restore
factory default
1. Power on the WF-2000 series I/O module
2. Change the Dip-Switch position of the WF-2000 series and to
complete the following steps in 5 seconds.
Step1. From “OP” to “FW” position.
Step2. From “FW” to “OP” position.
Step3. From “OP” to “FW” position.
Step4. From “FW” to “OP” position.
3. When the correct implementation of the above steps, the
Signal Strength LEDs and PWR/Wi-Fi LEDS of the WF-2000
series should be turn on, and that should be turn off after 500
ms later.
4. Reset the power the WF-2000 series would back to factory
defaults.
Technical Support
If you have problems about using the WF-2000 series I/O mod
ule
,
please contact ICP DAS Product Support.
Email: serv[email protected]m
Step1
Step2