ICP DAS USA LC-101H User manual

LC-101H/LC-102H User Manual
- 1 -
LC-101H/LC-102H
User Manual
Version: 1.0.0
Date: Jul. 2022

LC-101H/LC-102H User Manual
- 2 -
Warranty
All products manufactured by ICP DAS are warranted against defective materials for a
period of one year from the date of delivery to the original purchaser.
Warning
ICP DAS assumes no liability for damages consequent to the use of this product.
ICP DAS reserves the right to change this manual at any time without notice. The
information furnished by ICP DAS is believed to be accurate and reliable. However, no
responsibility is assumed by ICP DAS for its use, not for any infringements of patents or
other rights of third parties resulting from its use.
Copyright
Copyright © 2022 by ICP DAS.All rights are reserved.
Contact Us
If you have any questions, please feel free to contact us via email at:
Service@icpdas.com

LC-101H/LC-102H User Manual
- 3 -
Contents
1. Introduction................................................................................................................................4
2. Hardware....................................................................................................................................6
2.1 Specifications...................................................................................................................6
2.2 Appearance.......................................................................................................................8
2.3 Pin Assignments...............................................................................................................9
2.4 Wire Connections...........................................................................................................10
2.5 Internal I/O Structure.....................................................................................................11
2.6 Switch (SW1).................................................................................................................12
2.61 Switch (SW2)...............................................................................................................12
2.7 Dimensions (unit: mm)..................................................................................................13
3. Configuration via RS-485........................................................................................................14
Appendix A: Modbus Master Tool PC.........................................................................................18
Appendix B: Modbus Address Table ...........................................................................................22
Appendix C: DCON Command Sets ...........................................................................................31
DIP Switch setting .......................................................................................................................35

LC-101H/LC-102H User Manual
- 4 -
1. Introduction
The LC lighting control module is easy-to-use and requires no specialist skills to install
and operate, and no software is needed in order to control the lighting control channels.
The LC-101H is a 1-channel lighting control module with AC load current measurement
which provides 1-channel high power relay output and 1-channel AC digital input.
The LC-102H is a 2-channel lighting control module with AC load current measurement
which provides 2-channel high power relay output and 2-channel AC digital input.
The AC load current measurement is provided in the relay control loop. This function not
only allows the user to know the load current value, but also through the measurement
of the load current value, it can be used to know the switching state of the relay, whether
the load is working normally in the light control loop, or the relay is stuck and cannot be
switched.
The input channel can directly control the relay ON and OFF sequence without the host
command.
When required, the module can be communicated with the Modbus RTU protocol, and
an added benefit is that different addresses can be set for Modbus RTU communication
via hardware configuration.
Features
High Power Relay Output to turn ON/OFF the Lighting
Number of lighting fixtures That Can Be Connected:
Incandescent Lamp: 40 W/ 220 VAC * 5 Sets
LED(Electronic ballast): 40 W/ 220 VAC *8 Sets
0 to 5 A AC power Load Current Measurement Relay output
Isolated AC Digital Input
Node Addresses by hardware configuration
Low Power Consumption
Modbus RTU and DCON Protocols

LC-101H/LC-102H User Manual
- 5 -

LC-101H/LC-102H User Manual
- 6 -
2. Hardware
2.1 Specifications
Module
LC-101H
LC-102H
Communication
Ports 1 x RS-485
Data Format
N,8,1/O,8,1/E,8,1/N,8,2
Baud Rate Hardware Configuration: Fixed 9600 bps
Software Configuration: 1200 to 115200 bps
Protocol
Modbus RTU / DCON
Software
Function
Local and Remote Direct Control Relay ON/OFF and
Remote Status Monitoring
Node Addresses 32 to 63 for hardware configuration
LED Display
Status 1 LED as Power Indicator
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
EFT (IEC61000-4-4)
±4 kV for Power
SURGE(IEC 61000-4-5) ±2 kV for Power
Power
Reverse Polarity
Protection Yes
Input Voltage Range
10 ~ 30 VDC
Consumption 1.9 W Max. 2.8 W Max.
Mechanical
Dimensions (W x L x H) 72 mm x 95 mm x 57 mm
Installation
DIN-Rail
Environment
Operating Temperature
-25 to +75°C
Storage Temperature -30 to +80°C
Humidity
10 to 95% RH, Non-condensing

LC-101H/LC-102H User Manual
- 7 -
I/O Specifications
Module
LC-101H
LC-102H
Digital Input
Channels 1 2
Type
Wet Contact, 90 ~ 240 V
AC
On Voltage Level 65 VAC
Off Voltage Level
56 VAC
Input Impedance 68 KΩ, 2W
Isolation
3000 VDC
Relay Output with Load Current Measurement
Channels
1
2
Type Power Relay, Form C (SPDT N.O+N.C..)
Contact Rating
30 A @ 250 VAC
Max. Inrush Current 112A /1ms
Number of lighting
fixtures
(1).Incandescent Lamp: 40W/ 220VAC * 5 Sets
(2).LED(Electronic ballast): 40W/ 220VAC *8 Sets
Operate Time 15 ms Max
Release Time
22 ms Max.
Electrical Endurance 100,000 ops.
Mechanical Endurance
10,000,000 ops
AC Load Current
Measurement Yes, 0 ~ 5A range with 3% of FSR Accuracy.
Power-on Value
Yes
Safe Value Yes

LC-101H/LC-102H User Manual
- 8 -
2.2 Appearance
LED Indicators
PWR: Power/Communication Indicator
Switch (SW1)
AC Digital Input
Relay Output with Load Current Measurement
Power Indicator
(Red LED)
POWER
RS-485
Switch (SW1)
Switch (SW2)

LC-101H/LC-102H User Manual
- 9 -
Switch (SW2)
2.3 Pin Assignments

LC-101H/LC-102H User Manual
- 10 -
2.4 Wire Connections

LC-101H/LC-102H User Manual
- 11 -
2.5 Internal I/O Structure

LC-101H/LC-102H User Manual
- 12 -
2.6 Switch (SW1)
2.61 Switch (SW2)
SW1
0 to F for Address 32-47
(Node Address - Low)
0 to F for Address 48 -63
(Node Address - High)
SW2
1
ON
DCON Protocol
OFF
Modbus RTU Protocol
2
ON
Software Configuration
OFF
Hardware Configuration
3
ON
Node Address (High)
OFF
Node Address (Low)
4
ON
INIT Mode
OFF
Normal Mode

LC-101H/LC-102H User Manual
- 13 -
2.7 Dimensions (unit: mm)

LC-101H/LC-102H User Manual
- 14 -
3. Configuration via RS-485
The factory default settings for RS-485 communication
Address: 1
Protocol: Modbus RTU / DCON
Baud rate: Hardware Configuration: Fixed 9600 bps
Software Configuration: 1200 to 115200 bps
Data Format: N,8,1/O,8,1/E,8,1/N,8,2
Note
If there are multiple LC-101H/LC-102H connected to the same RS-485 network,
each module needs be set with a unique RS-485 address. More than one module
having the same address will cause communication failure
Testing RS-485 Communication
1. Download the DCON Utility Pro from
ICPDAS web site : https://www.icpdas.com/en/download/DCON_Utility_Pro
2. Launch the DCON_Utility_Pro.exe.
Set COM port Configuration
Start Search
Stop Search

LC-101H/LC-102H User Manual
- 15 -
3. Click the icon to configure the COM port.
4. Select the COM Port number used to connect the LC-101H/LC-102H logger.
5. The Baud Rate is factory default to 9600 bps.

LC-101H/LC-102H User Manual
- 16 -
6. Select the Protocol tab.
7. Select the Format tab and check the parity that set in the logger.
8. Click the Start Search icon.
9. The LC-101H/LC-102H logger searched out will be listed as below.

LC-101H/LC-102H User Manual
- 17 -
10. Click the module name to configure the logger.
Note
The Protocol/Baud Rate/Parity/Checksum items marked with ”(INIT*)” means that
when any of those items needs be modified, the pin 4.INIT needs to be set in ON
position and power cycle the logger, then the item can be modified.After complete
setting, set the pin 4. INIT back to OFF position and power cycle the logger again to
take the setting effect.

LC-101H/LC-102H User Manual
- 18 -
Appendix A: Modbus Master Tool PC
Modbus Master Tool PC is a free, easy-to-use tool for Modbus communication and
diagnosing the wiring.
ICPDAS web site :https://www.icpdas.com/en/download/ModbusMasterToolPC
This section intends to guide the steps for creating the Modbus communication with
LC-101H/LC-102H logger.
1. Launch the ModbusMasterToolPC.exe.
2. Select New in the File menu.
3. Input the file name and click on the Save button.

LC-101H/LC-102H User Manual
- 19 -
4. Select Connect in the Connection menu.
5. Select the communication interface.
When using RS-485 as the interface, select the COM port, check the RTU mode and
click on the OK button.
6. Select Definition in the Setup menu.

LC-101H/LC-102H User Manual
- 20 -
7. Select the Modbus function code, input the start address and length, and click on
the OK button.
8. Read data.
This manual suits for next models
1
Table of contents
Other ICP DAS USA Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Cold Jet
Cold Jet i3 MICROCLEAN Operator's manual

Delta
Delta 32-325 instruction manual

Contec
Contec CONPROSYS CPS-PC341EC-1-9201 Reference manual

Alfalaval
Alfalaval Toftejorg MultiMidget instruction manual

Carbide 3D
Carbide 3D Shapeoko HDZ 4.0 Assembly guide

Gema
Gema OptiFlex 2 V Operating instructions and spare parts list