2.2 Insert the flat cable / version Quad
►Insert the incoming AS-i flat cable (yellow or black for the external voltage
supply) into the cable duct "Line 1".
►Insert the outgoing AS-i flat cable (yellow or black) into the cable duct "Line 2".
►Place the cables correctly in the profile slot.
The two cable ducts are electrically connected in parallel.
►For the Quad version always use two AS-i flat cables of the same
colour (yellow/yellow or black/black) in "Line 1" and "Line 2".
2.3 Insert the flat cable / version Quad M12
►Insert the AS-i flat cable (yellow) into the cable duct "Line 1".
►Insert the 24 V flat cable (black) into the cable duct "Line 2".
►Place the cables correctly in the profile slot.
2.4 Installation of the upper part
►Position the upper part
and tighten the screws (5)
crosswise (tightening torque
2.5 Nm).
Ground the devices via the
earth springs (6) if necessary.
For connection of a plug to Quad M12:
Tightening torque of the M12 socket: 0.8 Nm. Also observe the tightening
torque of the connection cable used.