
-13--12-
current drawn by the motors. Should either motor
draw excessive current, the relay will open to
cause the compressor to stop. The relays are
normally closed, operate on a 12-volt DC circuit
and are shipped from the factory in the automatic
reset position. The relays are identified on
electrical schematics as 1OL for the main motor
and 2OL for the fan motor.
Basically, the overload relay has a heat-generat-
ingelement for eachofthethreephasessupplying
current to the motor. The heater element is sized
for the current drawn by the motor at full load
conditions. Should an overload condition develop
to draw higher than normal current, the heater
elements produce additional amounts of heat.
Theadditionalheatissensedbyasmallstripmade
of two dis-similar metals bonded together having
different rates of expansion. As the bi-metal strip
heats up, it bends as a result of the two different
expansion rates until it trips the overload relay
contacts to the open position. As the contacts
open, the compressor is shut down in an alarm
condition.
After cooling, the relay can be reset manually or
automatically.
Coolant Filter Differential Pressure Switch
(CPS)
A differential pressure-sensing switch is installed
to monitor the condition of the coolant filter. The
switchisnormallyopenandclosesacrossa12volt
DC circuit when the filter differential exceeds 20
psi.
Emergency Stop - Logic Circuit (ES-2)
A normally closed contact in the 12 volt DC circuit
that opens when the Emergency Stop button is
pressed. As the contact opens, power is removed
from the controller circuit. See the emergency
stop switch section for further information.
Remote Stop Button (RSP) (Optional)
The button is intended to stop a running com-
pressor from a remote location.
When the Remote Start/Stop option is installed
and turned on in the set point routine, a normally
closed switch must be connected between P3
terminals 19 and 20. The switch must be a
momentary opening type (approximately .1
second). If a start attempt is made while the
switch remains open, the controller will issue a
Remote Stop alarm.
Remote Start Button (RST) (Optional)
Thebuttonisintendedto start a stopped compres-
sor from a remote location.
When the Remote Start/Stop option is installed
and turned on in the set point routine, a normally-
open switch must be connected between P3
terminals 21 and 22. The switch must be a
momentaryclosingtype(approximately2seconds).
ARemote Start alarm will be issued by the control-
ler if the button is not released by the end of the
star-delta transition time on star-delta units or 7