Interflex IF-800 User manual

Interflex Datensysteme GmbH & Co. KG 1/7
1 Slave Terminal IF-800
Thank you for using a terminal of the series IF-800 for recording
access data.
Scope of Delivery:
Slave terminal IF-800.
I/O controller board for controlling locking devices
Terminal strip board
Material required for mounting in a DIN appliance case
Peripherals CD
Please check the completeness and condition of the
shipment upon receipt.
1.1 Intended Use
Slave terminals of the series IF-800 are designed for recording time data, controlling access as well as for
controlling and monitoring locking devices. Any other use is not in accordance with the intended purpose and
is therefore not permitted.
2 Electrical Installation
Electric shock can cause severe injuries or death.
Connection to mains voltage may therefore only be carried out by persons trained in electrical
engineering.
Initial operation may only be performed by persons instructed on accident prevention regulations (VBG
4).
Interflex systems may only run on electrical installations which correspond to DIN VDE 0100. To
guarantee trouble-free operation, we recommend carrying out the electrical installation according to the
principles of a TN-S system, which means using separate neutral and protective earth conductors.
Secure the power cable with a strain relief.
The device must have an external separator.
The device must be equipped with an external fuse protection with a maximum nominal current of 10 A.
3 Function of the Slave Terminal
Access terminals of the series IF-800 are part of a time and attendance recording or access control system.
They are preferably installed directly next to locking devices. In general, they are connected with an RS485
data cable to a master terminal, access manager or terminal controller. Terminals of the series IF-800 are
designed for controlling the access of persons who identify themselves with RFID identification media, as
well as for controlling and monitoring locking devices.
We recommend:
installing a separate, fuse-protected circuit.
keeping a minimum distance of 30 cm between the slave terminal and other systems with RFID readers.
keeping a distance of 10 cm between connecting cables and power lines.
95-10287__ IF-800_1312_3
Access Terminal IF-800

Interflex Datensysteme GmbH & Co. KG 2/7
4 Installation into an Appliance Case
1 I/O controller board 6 RFID reader
2 Terminal strip board 7 Anti-tamper switch
3
Protective cover
8
DIP switches for light emitting diodes
4 DIN appliance case 9 Address switch
5 Adjusting screw for reader adjustment 10 MPU board
The terminal strip board or the I/O controller board is mounted into the DIN appliance case using the
adhesive tape included in the delivery.
5 Installation
1. Install all cables. Use the right cable types ("Function of the Cables and Cable Types" on page 3).
2. Plaster the appliance case into the wall in such a way that the screws of the case are at the top and
bottom.
3. Making Electrical Connections
- Fasten terminal strip board or I/O controller board into the appliance case (see note).
- Connect the power supply.
- Connect the data cables.
- Connect actuators and possible feedback sensors.
4. Set the hardware address.
5. Installation of the Terminal
Mount the IF-800 terminal into the appliance case so that the large cutouts on the reader are at the top
and bottom.
6. Switch on the operating voltage.
7. Initial operation and device function check
- Reader adjustment
- Setting the LEDs
8. Mount front design panel so that the Interflex logo is at the top.
If the I/O controller board is mounted into the appliance case, the terminal strip board
is not required. However, there is then the danger of manipulation.

Interflex Datensysteme GmbH & Co. KG 3/7
Recommendation: For security reasons, the I/O controller board should always be mounted in a secured
area.
5.1 Electrical Connections
5.1.1 Function of the Cables and Cable Types
Function of the Cable Max. Length
Recommended Cable Type
1 Voltage supply 230 VAC to mains transformer 20 VAC
1.5A (order number 41-10106) NYM 3 x 1.5 mm²
2 Low-voltage cable J-Y(ST) Y 4x 2x 0.6mm²
3 Shielded cable from terminal strip board to I/O controller
in secured area. 100 m J-Y(ST) Y 4x 2x 0.6mm²
4 Voltage supply to actuator. J-Y(ST) Y 4x 2x 0.6mm²
5 Connection cable to floating sensors. 100 m J-Y(ST) Y 2x 2x 0.6mm²
6
Connection to actuator (up to max. 30 V, 2 A)
J-Y(ST) Y 4x 2x 0.6mm²
7 Spur line from BUS to installation site. 100 m J-Y(ST) Y 4x 2x 0.6mm²
8 RS485 BUS cable 1200 m J-Y(ST) Y 4x 2x 0.6mm²
Install the power supply line in duplicate (one conductor pair each). The protective
conductor should likewise be installed in duplicate, whereby the continuity wire can also be installed.

Interflex Datensysteme GmbH & Co. KG 4/7
5.2 Connections
1
Terminal strip board
5
Circuit example: Control of an actuator (door opener)
2 I/O controller board 6 Circuit example: Connection of both inputs
3 Circuit example: Voltage supply 7 IF-800 Terminal
4 Circuit example: RS485 connection

Interflex Datensysteme GmbH & Co. KG 5/7
BR.1 For operation as I/O controller board (relay 1), the jumper is plugged in. For operation as an I/O
expansion (relay 2), the jumper is removed.
BR.2 Normal open / Normal closed. This jumper is used to set the relay contact. Opening or closing
contact.
BR.3 When the jumper is removed, an external anti-tamper switch can be connected.
A shielded cable with a core diameter of at least 0.6 mm² must be used for the connection between the
terminal strip board and the I/O controller board.
For security reasons, the I/O controller board should be mounted in a secured area.
5.3 How to Set the Hardware Address
There is a 4-button DIP switch on the MPU board for setting the device address.
Switch 1 2 3 4
Address 1 OFF OFF OFF OFF (not required if connected to a master terminal)
Address 2 ON OFF OFF OFF
Address 3 OFF ON OFF OFF
Address 4 ON ON OFF OFF
Address 5 OFF OFF ON OFF
Address 6 ON OFF ON OFF
Address 7 OFF ON ON OFF
Address 8 ON ON ON OFF
5.4 Install the terminal.
1 Anti-tamper switch
2 RFID board
3 Design kit
4 Large cutouts for latching the front panel.
5 Metal retaining clips for fastening in the appliance case
6
7-wire cable from the terminal to terminal strip board
7 Protective cover

Interflex Datensysteme GmbH & Co. KG 6/7
Make sure that the lettering TOP on the IF-800 terminal is always on top. Only then can the design kit
(accessory) be properly installed.
5.5 Reader Adjustment
After mounting the reader into the appliance case, adjust it using the adjustment set (order no.
75-99-0004).
Turn the adjusting screw until the field indicator reaches maximum.
1 Adjusting screw
2
3-pin DIP switch for setting the LEDs
5.6 Setting the LEDs
Set the function of the light-emitting diodes with the 3-pin DIP switches on the front panel according to
the design kit chosen.
Design kit
/white
/blue
Glass, white OFF ON ON
Glass, black ON ON ON
IF design OFF ON ON
Third-party design
OFF
OFF
OFF
6 Remote Placement of the I/O Controller Board
To protect the I/O controller board against manipulation, it should be installed in a secured area.
It can, for example, be installed in a junction box together with the voltage supply. In such case, the terminal
strip board must be connected directly to the terminal.
The connection between the terminal strip board and the I/O controller board must be made with a
shielded cable.
The cable length may not exceed 100 m.
Adhesive tape for fastening the terminal strip board in the appliance case is included in the delivery.

Interflex Datensysteme GmbH & Co. KG 7/7
7 Technical Specifications
Power supply
Low-voltage 12 - 27 VAC or 11 - 38 VDC (measured directly at the terminal)
Power consumption Max. 4 VA
Fuse protection via PTC resistor
Interfaces
RS485; 9600/ 19200 baud (automatic configuration)
Reader RFID reader, Mifare or LEGIC (depending on order)
Read range Up to 50 mm
Sensor inputs 4 floating sensors (2 per I/O controller board)
Output relays 2 relays with max. 30 V 2 A (1 per each I/O controller board)
User information Buzzer; Green and red LEDs (white and blue are not visible)
General data
Anti-tamper switch Activated when front panel is removed
Ambient temperature -25º C to +55º C
Humidity Max. 95%, non-condensing
Product safety EN 60950-1
Compatibility (EMC) EN 300330-1/-2 EN 301489-1/-3
Dimensions (H x W x D) 71 x 71 x 27 mm
Weight Approx. 0.35kg
8 Disposal
After proper operation, the device is to be disposed of properly as electronic scrap. The
owner can dispose of the device himself or return it to the supplier.