Invertek Optidrive VTC User manual

User Guide
Optidrive VTC
Variable Torque Control
AC Variable Speed Drive 1.5 –160kW (2 –250HP)
Installation and operating instructions

Optidrive VTC –User Guide
2 www.invertek.co.uk
Declaration of Conformity:
Invertek Drives Ltd hereby states that the Optidrive VTC product range conforms to the relevant safety provisions of the Low Voltage Directive
2006/95/EC and the EMC Directive 2004/108/EC and has been designed and manufactured in accordance with the following harmonised European
standards:
EN 61800-5-1: 2003
Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
EN 61800-3 2nd Ed: 2004
Adjustable speed electrical power drive systems. EMC requirements and specific test methods
EN 55011: 2007
Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and
medical (ISM) radio-frequency equipment (EMC)
EN60529 : 1992
Specifications for degrees of protection provided by enclosures
Electromagnetic Compatibility
All Optidrives are designed with high standards of EMC compliance in mind. All versions suitable for operation on Single Phase 230 volt and Three
Phase 400 volt supplies and intended for use within the European Union are fitted with an internal EMC filter. This EMC filter is designed to reduce
the conducted emissions back into the supply via the power cables for compliance with harmonised European standards.
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC
legislation of the country of use. Within the European Union, equipment into which this product is incorporated must comply with the EMC
Directive 2004/108/EC. When using an Optidrive with an internal or optional external filter, compliance with the following EMC Categories, as
defined by EN61800-3:2004 can be achieved:
Drive Type / Rating
EMC Category
Cat C1
Cat C2
Cat C3
1 Phase, 230 Volt Input
ODV-x2xxx
No additional filtering required
Use shielded motor cable
3 Phase, 400 Volt Input
ODV-x4xxx
Use External Filter OD-Fx34x
No additional filtering required
Use screened motor cable
Note
For motor cable lengths greater than 100m, an output dv / dt filter must be used (part number OD-OUTFx, please refer to the Invertek
Stock Drives Catalogue for further details)
For Frame Size 5 and 6 drives, a ferrite ring must be installed on the output motor cable, with all three phases of the motor cable being
wrapped one turn around the ferrite ring.
All rights reserved. No part of this User Guide may be reproduced or transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by any information storage or retrieval system without permission in writing from the publisher.
Copyright Invertek Drives Ltd © 2009
All Invertek Optidrive VTC units carry a 2 year warranty against manufacturing defects from the date of manufacture. The manufacturer accepts no
liability for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning. The manufacturer also accepts
no liability for damage or consequences resulting from inappropriate, negligent or incorrect installation, incorrect adjustment of the operating
parameters of the drive, incorrect matching of the drive to the motor, incorrect installation, unacceptable dust, moisture, corrosive substances,
excessive vibration or ambient temperatures outside of the design specification.
The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local distributor should
be contacted first.
The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of continuous
improvement, the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User Guide
without notice.
This User Guide is for use with V3.10 Software.
User Guide Issue 3.11 11/09
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date
information, the information contained in this User Guide should be used for guidance purposes only and does not form the part of any contract.

Optidrive VTC –User Guide
www.invertek.co.uk 3
1. INTRODUCTION ................................................................................................................................. 4
1.1. Important safety information .......................................................................................................4
2. GENERAL INFORMATION AND RATINGS ............................................................................................. 5
2.1. Drive model numbers....................................................................................................................5
3. MECHANICAL INSTALLATION ............................................................................................................. 6
3.1. Mechanical dimensions and mounting .........................................................................................6
3.2. Before Installation.........................................................................................................................7
3.3. General Installation.......................................................................................................................7
3.4. Enclosure mounting ......................................................................................................................8
4. ELECTRICAL INSTALLATION ................................................................................................................ 9
4.1. Grounding the Drive......................................................................................................................9
4.2. Wiring Precautions........................................................................................................................9
4.3. Incoming Power Connection .........................................................................................................9
4.4. Connection Diagram ...................................................................................................................10
4.5. Motor Connection and Cables ....................................................................................................10
4.6. Motor Terminal Box Connections ...............................................................................................10
4.7. Dynamic Brake Resistor Connections..........................................................................................10
4.8. Control terminal connections .....................................................................................................11
5. OPERATION ......................................................................................................................................12
5.1. Managing the keypad..................................................................................................................12
5.2. Changing Parameters ..................................................................................................................12
5.3. Advanced Keypad Operation Short Cuts.....................................................................................13
5.4. Reset All Parameters to Factory Default Settings .......................................................................13
5.5. Terminal Control .........................................................................................................................14
5.6. Keypad Control............................................................................................................................14
5.7. Motor Autotuning.......................................................................................................................15
5.8. Operation of Three Phase drives on Single Phase Supplies ........................................................15
6. PARAMETERS ...................................................................................................................................16
6.1. Parameter Group 1 –Basic Parameters......................................................................................16
6.2. Parameter Group 2 - Extended parameters................................................................................17
6.3. Parameter Group 3 –PID Control ...............................................................................................20
6.4. Parameter Group 4 –High Performance Motor Control ............................................................20
6.5. Parameter Group 0 –Monitoring Parameters (Read Only) ........................................................21
6.6. Fire Mode....................................................................................................................................21
7. ANALOG AND DIGITAL INPUT CONFIGURATIONS...............................................................................22
7.1. Terminal mode (P1-12 =0) ..........................................................................................................22
7.2. Keypad mode (P1-12 = 1 or 2).....................................................................................................23
7.3. User PI control mode (P1-12 = 3)................................................................................................24
7.4. Modbus Control Mode (P1-12 = 4) .............................................................................................24
8. TROUBLESHOOTING..........................................................................................................................25
8.1. Fault messages............................................................................................................................25
9. TECHNICAL DATA..............................................................................................................................26
9.1. Environmental.............................................................................................................................26
9.2. Rating tables ...............................................................................................................................26
9.3. Maximum supply ratings for UL compliance:..............................................................................28
10. MODBUS COMMUNICATIONS...........................................................................................................29
10.1. Introduction ................................................................................................................................29
10.2. Modbus RTU Specification ..........................................................................................................29
10.3. RJ11 Connector Configuration ....................................................................................................29
10.4. Modbus Telegram Structure .......................................................................................................29
10.5. Modbus Register Map.................................................................................................................30
11. PARAMETER SETTING RECORD..........................................................................................................31

Optidrive VTC –User Guide
4 www.invertek.co.uk
1. Introduction
1.1. Important safety information
Please read the IMPORTANT SAFETY INFORMATION below, and all Warning and Caution information elsewhere.
Indicates a potentially hazardous situation which, if not
avoided, could result in injury or death.
Indicates a potentially hazardous situation which, if not
avoided, could result in damage to property.
This variable speed drive product (Optidrive) is intended for professional incorporation into complete equipment or systems as part of
a fixed installation. If installed incorrectly it may present a safety hazard. The Optidrive uses high voltages and currents, carries a high
level of stored electrical energy, and is used to control mechanical plant that may cause injury. Close attention is required to system
design and electrical installation to avoid hazards in either normal operation or in the event of equipment malfunction.
System design, installation, commissioning and maintenance must be carried out only by personnel who have the necessary training
and experience. They must carefully read this safety information and the instructions in this Guide and follow all information regarding
transport, storage, installation and use of the Optidrive, including the specified environmental limitations.
The level of integrity offered by the Optidrive control functions –for example stop/start, forward/reverse and maximum speed, is not
sufficient for use in safety-critical applications without independent channels of protection. All applications where malfunction could
cause injury or loss of life must be subject to a risk assessment and further protection provided where needed.
Within the European Union, all machinery in which this product is used must comply with Directive 98/37/EC, Safety of Machinery. In
particular, the machine manufacturer is responsible for providing a main switch and ensuring the electrical equipment complies with
EN60204-1.
The driven motor can start at power up if the enable input signal is present.
The STOP function does not remove potentially lethal high voltages. ISOLATE the drive and wait 10 minutes before starting any work on
it.
Electric shock hazard! Disconnect and ISOLATE the Optidrive before attempting any work on it. High voltages are present at the
terminals and within the drive for up to 10 minutes after disconnection of the electrical supply.
Where supply to the drive is through a plug and socket connector, do not disconnect until 10 minutes have elapsed after turning off the
supply.
Ensure correct earthing connections. The earth cable must be sufficient to carry the maximum supply fault current which normally will
be limited by the fuses or MCB. Suitably rated fuses or MCB should be fitted in the mains supply to the drive.
Flammable material should not be placed close to the drive
Parameter P1-01 can be set to operate the motor at up to 120,000 rpm, hence use this parameter with care.
If it is desired to operate the drive at any frequency/speed above the rated speed (P1-09/ P1-10) of the motor, consult the
manufacturers of the motor and the driven machine about suitability for over-speed operation.
Carefully inspect the Optidrive before installation to ensure it is undamaged
The Optidrive VTC has an Ingress Protection rating of IP20 or IP)) depending on the model. Units should be installed in a suitable
enclosure.
Optidrives are intended for indoor use only.
Do not perform and flash test or voltage withstand test on the Optidrive. Any electrical measurements required should be carried out
with the Optidrive disconnected.
The entry of conductive or flammable foreign bodies should be prevented
Relative humidity must be less than 95% (non-condensing).
Ensure that the supply voltage, frequency and no. of phases (1 or 3 phase) correspond to the rating of the Optidrive as delivered.
Never connect the mains power supply to the Output terminals U, V, W.
Do not install any type of automatic switchgear between the drive and the motor
Wherever control cabling is close to power cabling, maintain a minimum separation of 100 mm and arrange crossings at 90 degrees
Ensure that all terminals are tightened to the appropriate torque setting

Optidrive VTC –User Guide
www.invertek.co.uk 5
2. General Information and Ratings
2.1. Drive model numbers
480-525V ±10% - 3 Phase Input
kW Model
Number
kW
HP Model
Number
HP
Output
Current
(A)
Frame
Size
ODV-55550-xx
55
N/A
90
5
ODV-55750-xx
75
N/A
110
5
ODV-55900-xx
90
N/A
150
5
ODV-65132-xx
132
N/A
202
6
ODV-65160-xx
160
N/A
240
6
ODV-65200-xx
200
N/A
270
6
500-600V ±10% - 3 Phase Input
kW Model
Number
kW
HP Model
Number
HP
Output
Current
(A)
Frame
Size
ODV-25075-xx
0.75
ODV-25010-USA
1
1.7
2
ODV-25150-xx
1.5
ODV-25020-USA
2
3.1
2
ODV-25220-xx
2.2
ODV-25030-USA
3
4.1
2
ODV-25370-xx
3.7
ODV-25050-USA
5
6.1
2
ODV-25550-xx
5.5
ODV-25075-USA
7.5
9.5
2
ODV-35075-xx
7.5
ODV-35100-USA
10
14
3
ODV-35110-xx
11
ODV-35150-USA
15
18
3
ODV-35150-xx
15
ODV-35200-USA
20
24
3
ODV-45220-xx
22
ODV-45300-USA
30
39
4
ODV-45300-xx
30
ODV-45400-USA
40
46
4
ODV-45450-xx
45
ODV-45600-USA
60
62
4
Notes
Output current values shown in brackets are maximum values for UL
conformance.
* Indicates models that are not UL listed
Input line choke must be fitted for all size 2 500 volt units
200-240V ±10% - 1 Phase Input
kW Model
Number
kW
HP Model
Number
HP
Output
Current
(A)
Frame
Size
ODV-22150-xx
1.5
ODV-12020-USA
2
7
2
ODV-22220-xx
2.2
ODV-12030-USA
3
10.5
2
200-240V ±10% - 3 Phase Input
kW Model
Number
kW
HP Model
Number
HP
Output
Current
(A)
Frame
Size
ODV3-22150-xx
1.5
ODV3-22020-USA
2
7
2
ODV3-22220-xx
2.2
ODV3-22030-USA
3
10.5 (* 9)
2
ODV-32030-xx
3.0
ODV-32040-USA
4
14
3
ODV-32040-xx
4.0
ODV-32050-USA
5
18
3
ODV-32055-xx
5.5
ODV-32075-USA
7.5
25 (*24)
3
ODV-42075-xx
7.5
ODV-42100-USA
10
39
4
ODV-42110-xx
11
ODV-42150-USA
15
46
4
ODV-42150-xx
15
ODV-42200-USA
20
61
4
ODV-42185-xx
18.5
ODV-42250-USA
25
72
4
ODV-42220-xx
22
ODV-42300-USA
30
90
4
ODV-52300-xx
30
ODV-52400-USA
40
110
5
ODV-52370-xx
37
ODV-52500-USA
50
150
5
ODV-52450-xx
45
ODV-52600-USA
60
180
5
380-480V ±10% - 3 Phase Input
kW Model
Number
kW
HP Model
Number
HP
Output
Current
(A)
Frame
Size
ODV-24075-xx
0.75
ODV-24010-USA
1
2.2
2
ODV-24150-xx
1.5
ODV-24020-USA
2
4.1
2
ODV-24220-xx
2.2
ODV-24030-USA
3
5.8
2
ODV-24400-xx
4
ODV-24050-USA
5
9.5
2
ODV-34055-xx
5.5
ODV-34075-USA
7.5
14
3
ODV-34075-xx
7.5
ODV-34100-USA
10
18
3
ODV-34110-xx
11
ODV-34150-USA
15
25 (24)
3
ODV-34150-xx*
15
ODV-34200-USA*
20
30
3
ODV-44185-xx
18.5
ODV-44250-USA
25
39
4
ODV-44220-xx
22
ODV-44300-USA
30
46
4
ODV-44300-xx
30
ODV-44400-USA
40
61
4
ODV-44370-xx
37
ODV-44500-USA
50
72
4
ODV-44450-xx
45
ODV-44600-USA
60
90
4
ODV-54550-xx
55
ODV-54750-USA
75
110
5
ODV-54750-xx
75
ODV-54100-USA
100
150
5
ODV-54090-xx
90
ODV-54120-USA
120
180
5
ODV-64110-xx
110
ODV-64150-USA
150
202
6
ODV-64132-xx
132
ODV-64175-USA
175
240
6
ODV-64160-xx
160
ODV-64210-USA
210
300
6

Optidrive VTC –User Guide
6 www.invertek.co.uk
3. Mechanical Installation
3.1. Mechanical dimensions and mounting
3.1.1. Frame Size 2
Overall Dimensions
Height
260mm
Width
100mm
Depth
175mm
A
210mm
B
92mm
Incoming Power Terminals
C
25mm
Help Card
Keypad & Display –See Section 0 on page 12
Footprint View
RJ11 Connector –See Section
Infra Red Interface
Weight : 2.6Kg
Control Terminals –See Section on page 10
Motor & Brake Resistor Connection Terminals
Fixings : 2 x M4 Keyhole slots
Power Terminals Torque Setting : 1Nm
3.1.2. Frame Size 3
Overall Dimensions
Height
260mm
Width
171mm
Depth
175mm
A
210mm
B
163mm
Incoming Power Terminals
C
25mm
Help Card
Keypad & Display –See Section 0 on page 12
Footprint View
RJ11 Connector –See Section
Infra Red Interface
Weight : 5.3Kg
Control Terminals –See Section on page 10
Motor & Brake Resistor Connection Terminals
Fixings : 4 x M4 Keyhole slots
Power Terminals Torque Setting : 1Nm
3.1.3. Frame Size 4
Overall Dimensions
Height
520mm
Width
340mm
Depth
220mm
A
420mm
B
320mm
Incoming Power Terminals
C
50mm
Help Card
Keypad & Display –See Section 0 on page 12
Footprint View
RJ11 Connector –See Section
Infra Red Interface
Weight : 28Kg
Control Terminals –See Section on page 10
Motor & Brake Resistor Connection Terminals
Fixings : 4 x M8 Keyhole slots
Power Terminals Torque Setting : 4Nm

Optidrive VTC –User Guide
www.invertek.co.uk 7
3.1.4. Frame Sizes 5 & 6
Overall Dimensions
Height
1100mm
Width
340mm
Depth
230 (=<75kW)
330mm (>=90kW)
A
945mm
Incoming Power Terminals
B
320mm
Help Card
C
50mm
Keypad & Display –See Section 5.1
RJ11 Connector
Footprint View
Infra Red Interface
Control Terminals –See Section 4.8
Motor & Brake Resistor Connection Terminals
Weights :
Size 5 : 67Kg
Size 6 : 55Kg
(+ 27Kg Choke)
Fixings : 4 x M8 Keyhole slots
Power Terminals Torque Setting : 8Nm
3.1.5. Frame Size 6 Additional Input Choke
Optidrive VTC Frame Size 6 is supplied complete with an external Input Choke, which must be installed in the supply line to the drive
Overall Dimensions
Height H
230mm
Length L
240mm
Depth B
250mm
Mounting Holes
Centres N1
160mm
Centres N2
105mm
Slots D1
8.5 x 22mm
Busbar Connections
Length A1
40mm
Connection
Diameter D2
9mm
Note: The choke is always supplied with the drive, and MUST be used.
3.2. Before Installation
Carefully unpack the drive and check for any signs of damage. Notify the shipper immediately if any exist.
Check the drive rating label to ensure it is of the correct type and power requirements for the application.
Store the Optidrive in its box until required. Storage should be clean and dry and within the temperature range –40°C to +60°C
3.3. General Installation
The Optidrive should be mounted in a vertical position only on a flat, flame resistant vibration free mounting using the integral mounting
feet.
The Optidrive must be installed in a pollution degree 1 or 2 environment only.
Do not mount flammable material close to the Optidrive
Ensure that the minimum cooling air gaps, as detailed in section 3.4 are left clear

Optidrive VTC –User Guide
8 www.invertek.co.uk
3.4. Enclosure mounting
For applications that require a higher IP rating than the IP20 offered by the standard drive, the drive must be mounted in a suitable metallic
enclosure. The following guidelines should be observed for these applications:
For IP20 Optidrives, install in a suitable enclosure, according to EN60529 if specific Ingress Protection ratings are required.
Enclosures should be made from a thermally conductive material
Where vented enclosures are used, there should be venting above and below the drive to ensure good air circulation –see the diagram
below. Air should be drawn in below the drive and expelled above the drive.
In any environments where the conditions require it, the enclosure must be designed to protect the Optidrive against ingress of airborne
dust, corrosive gases or liquids, conductive contaminants (such as condensation, carbon dust, and metallic particles) and sprays or
splashing water from all directions.
High moisture, salt or chemical content environments should use a suitably sealed (non-vented) enclosure.
Enclosure Front View
Enclosure Side View
The enclosure design and layout should ensure that the adequate ventilation paths and clearances are left to allow air to circulate through the
drive heatsink. Invertek Drives recommend the following minimum sizes for drives mounted in non-ventilated metallic enclosures:-
Enclosure Minimum Dimensions
Drive Power rating
L
W
D
G
Size 2 1.5kW 230V / 2.2kW 400V
400
300
300
60
Size 2 2.2kW 230V / 4kW 400V
600
450
300
100
For drives mounted in free ventilated enclosures of force ventilated enclosures, Invertek Drives recommend the following minimum sizes and
airflow requirements:-
Drive Power
Rating
Free-Vented unit
Force-vented unit
L
W
D
G
L
W
D
G
Air Flow
Size 2 1.5 kW
400
300
150
75
275
150
150
50
> 15m3/h
Size 2 4 kW
600
400
250
100
320
200
200
75
> 45m3/h
Size 3 15 kW
800
600
300
150
400
250
200
100
> 80m3/h
Size 4 22 kW
100
0
600
300
200
800
500
250
130
> 300m3/h
Size 4 45 kW
-
-
-
-
800
500
250
130
> 300m3/h
Size 5 90 kW
-
-
-
-
1500
600
400
200
> 900m3/h
Size 6 160 kW
-
-
-
-
1600
600
400
250
>1000m3/h

Optidrive VTC –User Guide
www.invertek.co.uk 9
4. Electrical Installation
4.1. Grounding the Drive
This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance or the
non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated equipment. A hazard
of personal injury and/or equipment damage exists if codes are ignored during installation.
This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before working on the
drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to discharge to safe voltage levels.
Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should
install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety
before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
Grounding Guidelines
The ground terminal of each Optidrive should be individually connected DIRECTLY to the site ground bus bar (through the filter if installed).
Optidrive ground connections should not loop from one drive to another, or to, or from any other equipment. Ground loop impedance must
confirm to local industrial safety regulations. To meet UL regulations, UL approved ring crimp terminals should be used for all ground wiring
connections.
The drive Safety Ground must be connected to system ground. Ground impedance must conform to the requirements of national and local
industrial safety regulations and/or electrical codes. The integrity of all ground connections should be checked periodically.
Protective Earth Conductor
The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductor.
Safety Ground
This is the safety ground for the drive that is required by code. One of these points must be connected to adjacent building steel (girder, joist), a
floor ground rod, or bus bar. Grounding points must comply with national and local industrial safety regulations and/or electrical codes.
Motor Ground
The motor ground must be connected to one of the ground terminals on the drive.
Ground Fault Monitoring
If a system ground fault monitor is to be used; only Type B devices should be used to avoid nuisance tripping.
Shield Termination (Cable Screen)
The safety ground terminal provides a grounding point for the motor cable shield. The motor cable shield connected to this terminal (drive end)
should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to the safety ground
terminal.
When shielded cable is used for control and signal wiring, the shield should be grounded at the source end only, not at the drive end.
4.2. Wiring Precautions
Connect drive according to section 4.4 Connection Diagram, ensuring that motor terminal box connections are correct. There are two connections
in general: Star and Delta. It is essential to ensure that the motor is connected in accordance with the voltage at which it will be operated. For
more information, refer to section 4.6 Motor Terminal Box Connections.
For recommended cabling and wiring sizing, refer to section 9.2 Rating tables.
It is recommended that the power cabling should be 3-core or 4-core PVC-insulated screened cable, laid in accordance with local industrial
regulations and codes of practice.
4.3. Incoming Power Connection
For 1 phase supply power should be connected to L1/L, L2/N.
For 3 phase supplies power should be connected to L1, L2, and L3. Phase sequence is not important.
The Optidrive should be connected to a fixed supply using a suitable disconnecting device between the Optidrive and the AC Power
Source. The disconnecting device must conform to the local safety code / regulations.
The cables should be dimensions according to any local codes or regulations. Guideline dimensions are given in section 9.2.
Suitable fuses to provide wiring protection should be installed in the incoming supply line, according to the data in section 9.2. The fuses
must comply with any local codes or regulations in place. In general, IEC type gG or UL type T fuses are suitable. The operating time of
the fuses must be below 0.5 seconds.
Where allowed by local regulations, suitably dimensioned circuit breakers may be utilised in place of fuses. Thermal overload protection
is not required, as the Optidrive provides thermal protection for the motor and motor cable. Guideline dimensions are given in section
9.2.
When the power supply is removed from the drive, a minimum of 30 seconds should be allowed before re-applying the power. A
minimum of 5 minutes should be allowed before removing the terminal covers or connection.
The maximum permissible short circuit current at the Optidrive Power terminals as defined in IEC60439-1 is 100kA.
An Input Choke should be installed in the supply line for frame size 1 to 3 Optidrives where any of the following conditions occur:-
oThe incoming supply impedance is low or the fault level / short circuit current is high
oThe supply is prone to dips or brown outs
oAn imbalance exists on the supply (3 phase drives)
oAll installations of Frame Size 2 drives on 575 Volt Supply

Optidrive VTC –User Guide
10 www.invertek.co.uk
In all other installations, an input choke is recommended to ensure protection of the drive against power supply faults. The
recommended chokes can be found in the Invertek Stock Drives Catalogue
For compliance with CE and C Tick EMC requirements, a symmetrical shielded cable is recommended.
4.4. Connection Diagram
4.5. Motor Connection and Cables
The motor should be connected to the Optidrive U, V, and W terminals.
To comply with EMC requirements, a shielded cable should be used, with the shield bonded to earth at the Optidrive and the motor.
4.6. Motor Terminal Box Connections
Most general purpose motors are wound for operation on dual voltage supplies; this is indicated on the nameplate of the motor
This operational voltage is normally selected when installing the motor by selecting either STAR or DELTA connection. STAR always gives the
higher of the two voltage ratings.
Incoming Supply Voltage
Motor Nameplate Voltages
Connection
230
230 / 400
Delta
400
400 / 690
400
230 / 400
Star
4.7. Dynamic Brake Resistor Connections
For drives that have a dynamic brake transistor, an optional external braking resistor can be connected to +DC and BR when required. The brake
resistor circuit should be protected by a suitable thermal protection circuit. Further information can be found in the Advanced User Guide.
FS 6
External
Input Choke
(Optional
on FS 1 –5)

Optidrive VTC –User Guide
www.invertek.co.uk 11
4.8. Control terminal connections
Default Connections
Control Terminal
Signal
Description
1
+24V User
Output,
+24V, 100mA user control output
2
Digital Input 1
Positive logic
“Logic 1” input voltage range: 8V … 30V DC
“Logic 0” input voltage range: 0V … 8V DC
3
Digital Input 2 /
Digital Output 3
Input : Positive logic
“Logic 1” input voltage range: 8V … 30V DC
“Logic 0” input voltage range: 0V … 8V DC
Output : 24V 10mA Max ‘Drive Healthy’ Output
4
Digital Input 3 /
Analog Input 2
Digital : “Logic 1” input voltage range : 8 to 30V DC
“Logic 0” input voltage range : 0 to 8 V DC
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
5
+24V User
Output
+24V, 100mA, 1kΩ minimum
6
Bipolar analog
Input /
Digital Input 4
Digital : “Logic 1” input voltage range : 8 to 30V DC
“Logic 0” input voltage range : 0 to 8 V DC
Analog: 0 to 24V, 0 to 10V, -10 to +10V, -24 to + 24V
7
0V
User ground, connected to terminal 9
8
Analog Output /
Digital Output
Analog: 0 to 10V DC, 20mA Maximum
Digital: 0 to 24V DC, 20mA Maximum
9
0V
User ground, connected to terminal 7
10
Relay Common
Volt free contacts. Maximum load should not exceed
250Vac, 6A / 30Vdc, 5A
11
Relay NO
Contact

Optidrive VTC –User Guide
12 www.invertek.co.uk
5. Operation
5.1. Managing the keypad
The drive is configured and its operation monitored via the keypad and display.
NAVIGATE
Used to display real-time information, to access and exit
parameter edit mode and to store parameter changes
UP
Used to increase speed in real-time mode or to increase
parameter values in parameter edit mode
DOWN
Used to decrease speed in real-time mode or to decrease
parameter values in parameter edit mode
RESET /
STOP
Used to reset a tripped drive.
When in Keypad mode is used to Stop a running drive.
START
When in keypad mode, used to Start a stopped drive or to
reverse the direction of rotation if bi-directional keypad
mode is enabled
5.2. Changing Parameters
Procedure
Display shows...
Power on Drive
Press and hold the for >2 seconds
Press the Key
The and can be used to select the desired parameter
etc...
Select the required parameter, e.g. P1-02
Press the button
.
Use the and keys to adjust the value, e.g. set to 10
.
Press the key
The parameter value is now adjusted and automatically stored. Press the key for >2 seconds to return to
operating mode

Optidrive VTC –User Guide
www.invertek.co.uk 13
5.3. Advanced Keypad Operation Short Cuts
Function
When Display shows...
Press...
Result
Example
Fast Selection of
Parameter Groups
Note : Parameter Group
Access must be enabled
P1-14 = 101
xxx
+
The next highest
Parameter group is
selected
Display shows
Press +
Display shows
xxx
+
The next lowest
Parameter group is
selected
Display shows
Press +
Display shows
Select lowest Group
Parameter
xxx
+
The first parameter of a
group is selected
Display shows
Press +
Display shows
Set Parameter to
minimum value
Any numerical value
(Whilst editing a
parameter value)
+
The parameter is set to
the minimum value
When editing P1-01
Display shows .
Press+
Display shows.
Adjusting individual digits
within a parameter value
Any numerical value
(Whilst editing a
parameter value)
+
Individual parameter
digits can be adjusted
When editing P1-10
Display shows
Press+
Display shows
Press
Display shows
Press+
Display shows
Press
Display shows
Etc...
5.4. Reset All Parameters to Factory Default Settings
To reset all drive parameters to factory default settings, press + + for >2s. The display shows . Press the button to
acknowledge and reset the drive.

Optidrive VTC –User Guide
14 www.invertek.co.uk
5.5. Terminal Control
When delivered, the Optidrive is in the factory default state, meaning that it is set to operate in terminal control mode and all parameters have the
default values as indicated in section 6 Parameters.
Connect the drive to the supply, ensuring the correct voltage and fusing / circuit breaker protection –see section 9.2 on page 26.
Connect the motor to the drive, ensuring the correct star/delta connection for the voltage rating - see section 4.6 on page 10.
Enter the motor data from motor nameplate; P1-07 = motor rated voltage, P1-08 = motor rated current, P1-09 = motor rated frequency.
Connect a control switch between the control terminals 1 and 2 ensuring that the contact is open (drive disabled).
Connect a potentiometer (1kΩ min to 10 kΩ max) between terminals 5 and 7, and the wiper to terminal 6.
With the potentiometer set to zero, switch on the supply to the drive. The display will show .
Close the control switch, terminals 1-2. The drive is now ‘enabled’ and the output frequency/speed are controlled by the potentiometer.
On first enable from factory default parameters, the Optidrive will carry out an Autotune, and the display shows . Leave the
control switch closed an allow this to complete.
Following completion of the Autotune, the display shows zero speed in Hz (.) with the potentiometer turned to minimum.
Turn the potentiometer to maximum. The motor will accelerate to 50Hz, (60Hz for USA drives), the default value of P1-01, under the
control of the acceleration ramp time P1-03. The display shows 50Hz (.) at max speed.
If the potentiometer is turned to minimum, the motor will decelerate to 0Hz, the default minimum speed set in P1-02, under the control
of the deceleration ramp P1-04. The output speed can be adjusted anywhere between minimum and maximum speed using the
potentiometer.
To display motor current (Amps), briefly press the (Navigate) key.
Press again to display the motor power.
Press again to return to speed display.
To stop the motor, disable the drive by opening the control switch (terminals 1-2).
If the enable/disable switch is opened the drive will decelerate to stop at which time the display will show .
5.6. Keypad Control
To allow the Optidrive to be controlled from the keypad in a forward direction only, set P1-12 =1:
Connect the supply and motor as for terminal control above.
Enable the drive by closing the switch between control terminals 1 & 2. The display will show .
Press the key. If this is the first enable from factory default parameters, the drive will carry out an Autotune as described above. On
completion of the Autotune, the display shows ..
Press to increase speed.
The drive will run forward, increasing speed until is released.
Press to decrease speed. The drive will decrease speed until is released. The rate of deceleration is limited by the setting in
P1-04
Press the key. The drive will decelerate to rest at the rate set in P1-04.
The display will finally show at which point the drive is disabled
To preset a target speed prior to enable, press the key whilst the drive is stopped. The display will show the target speed, use the
& keys to adjust as required then press the key to return the display to .
Pressing the key will start the drive accelerating to the target speed.
To allow the Optidrive to be controlled from the keypad in a forward and reverse direction, set P1-12 =2:
Operation is the same as when P1-12=1 for start, stop and changing speed.
Press the key. The display changes to ..
Press to increase speed
The drive will run forward, increasing speed until is released. Acceleration is limited by the setting in P1-03. The maximum speed is
the speed set in P1-01.
To reverse the direction of rotation of the motor, press the key again.

Optidrive VTC –User Guide
www.invertek.co.uk 15
5.7. Motor Autotuning
Optidrive VTC uses a sophisticated Voltage Vector control method as a factory default setting to ensure best possible motor operation. This control
method requires the Optidrive to carry out an autotune to measure certain motor parameters prior to operation, to ensure this function operates
correctly, and reduce the risk of nuisance tripping.
Whilst the autotune procedure does not rotate the motor shaft, during the autotune procedure, the motor shaft may still turn. It
is not normally necessary to uncouple the load from the motor, however the user should ensure any that no risk arises from the
possible movement of the motor shaft.
Autotune after Factory Reset
Following a factory reset (See section 6.1.3), the correct data from the motor nameplate should be entered in P1-07, P1-08 and P1-09. Providing
that P1-08 is adjusted from the factory default setting, the Optidrive will automatically carry out an autotune on the motor the first time it is
enabled. During the autotune, the display will show . The test procedure may take several minutes to complete depending on the motor.
Once the autotune is completed, the drive will operate as normal, and no further autotuning will be required unless the motor or drive control
mode is changed (P4-01).
User Selected Autotune
The user can program the drive to carry an autotune if required, as follows:-
Ensure the motor nameplate values are correctly entered in P1-07 (Motor Rated Voltage), P1-08 (Motor Rated Current) and P1-09 (Motor Rated
Frequency)
Set P1-14 = 101 to allow access to Parameter Groups 2, 3 and 4
Set P4-02 = 1
The autotune will begin immediately when P4-02 is set to 1, and no external enable signal is required. During the autotune
procedure, the motor shaft may turn. It is not normally necessary to uncouple the load from the motor, however the user should
ensure any that no risk arises from the possible movement of the motor shaft.
5.8. Operation of Three Phase drives on Single Phase Supplies
Applies to: - Optidrive VTC, 230 Volt Supply versions, Size 3 and above
Optidrive VTC, 400 Volt Supply versions, Size 2 and above
It is possible to operate the above drive units from a single phase supply of the same rated voltage. When used in this way, the maximum output
current capacity is reduced by 50%. In order to operate on a single phase supply, the supply MUST be connected to the L1 and L2 terminals of the
drive. The user must then press + + for >2s. The display will show , and all parameters will be reset to factory default
settings. Press the button to acknowledge and reset the drive. The maximum motor rated current setting in P1-08 will now be limited to 50%
of its original value, and the Phase Loss and Phase Imbalance Protection features will be disabled.

Optidrive VTC –User Guide
16 www.invertek.co.uk
6. Parameters
6.1. Parameter Group 1 –Basic Parameters
NOTE
Default parameter values for Horse Power rated drives are shown in brackets
Following a factory reset, or when installing a drive for the first time, only Group 1 Parameter access is available. To allow access to Parameters
Groups 0, 2, 3 and 4, Parameters P1-14 and P2-37 must contain the same value. The factory set value for P2-37 = 101
Par.
Description
Range
Units
Default
Explanation
P1-01
Maximum Frequency /
Speed
P1-02 to 120.0Hz
Hz
Rpm
50.0
(60.0)
Maximum speed limit –Hz or rpm.
If P1-10 >0, the value entered is in Rpm
P1-02
Minimum Frequency /
Speed
0.0 to P1-01
Hz
Rpm
0.0
Minimum speed limit –Hz or rpm.
If P1-10 >0, the value entered is in Rpm
P1-03
Acceleration ramp
time
0.0 to 3000.0
seconds
30.0
Acceleration ramp time from 0 to base speed (P-1-
09) in seconds
P1-04
Deceleration ramp
time
0.0 to 3000.0
seconds
30.0
Deceleration ramp time from base speed (P1-09)
to standstill in seconds. When set to zero, fastest
possible ramp time without trip is activated
P1-05
Stop mode select
0 : Ramp to stop
(brown-out ride-through)
1 : Coast to stop
2 : Ramp to stop (fast stop)
-
0
0 : If the mains supply is lost, the drive will try to
continue running by reducing the speed of the
load using the load as a generator.
1 : When the enable signal is removed from the
drive, the motor will coast (freewheel) to stop
2 : If the mains supply is lost, the drive will ramp to
stop using the P2-25 decel ramp time
P1-06
Energy Optimiser
0: Disabled
1: Enabled
-
0 : Disabled
When enabled, automatically reduces applied
motor voltage on light load. Minimum value is 50%
of nominal
P1-07
Motor rated voltage
0, 20 to 250
0, 20 to 500
Volts
230
400
(460)
Rated (nameplate) voltage of the motor (Volts).
Value limited to 250V for low voltage drives.
Setting to zero disables voltage compensation
P1-08
Motor rated current
25% -100% of drive rated current
Amps
Drive rating
Rated (nameplate) current of the motor
P1-09
Motor rated frequency
25Hz to 120Hz
Hz
50
(60)
Rated (nameplate) frequency of the motor
P1-10
Motor rated speed
0 to 7200 rpm
Rpm
0
When non-zero, all speed related parameters are
displayed in rpm
P1-11
Preset Speed 1
-P1-01 to P1-01
Hz
50.0
(60.0)
Sets the speed the drive runs at when Preset
Speed 1 is selected
P1-12
Terminal / Keypad /
PID
Drive Control Mode
Selection
0 : Terminal control
1 : Keypad control –fwd only
2 : Keypad control fwd and rev
3 : PID Control
4 : Modbus Control
-
0
Primary Control Mode of the drive.
0 : Terminal control
1 : Uni-directional keypad control. Keypad START
button does not reverse direction.
2 : Bi-directional keypad control. Keypad START
button toggles between forward and reverse.
3 : User PI control with external feedback signal
4 : Modbus RTU Control
P1-13
Trip log
Last four trips stored
-
Read only
Previous 4 trips stored in order of occurrence, with
the most recent first.
Press UP or DOWN to step through all four.
The most recent trip is always displayed first.
UV trip is only stored once.
P1-14
Extended menu access
Code 0 to 9 999
-
0
Set to “101” (default) for extended menu access.
Change code in P2-37 to prevent unauthorised
access to the Extended Parameter Set

Optidrive VTC –User Guide
www.invertek.co.uk 17
6.2. Parameter Group 2 - Extended parameters
Par.
Description
Range
Units
Default
Explanation
P2-01
Digital input function
select
0 to 23
-
0
Defines the function of the digital inputs
depending on the control mode setting in P-12.
See section 7 Analog and Digital Input
Configurations for more information.
P2-02
Preset Speed 2
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 2
P2-03
Preset Speed 3
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 3
P2-04
Preset Speed 4
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 4
P2-05
Preset Speed 5
-P1-01 to P1-01
Hz
0.0
Sets jog /preset speed 5
P2-06
Preset Speed 6
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 6
P2-07
Preset speed 7
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 7
P2-08
Preset speed 8
-P1-01 to P1-01
Hz
0.0
Sets jog / preset speed 8
P2-09
Skip frequency
P1-02 to P1-01
Hz
0.0
Centre point of skip frequency band set up in
conjunction with P2-10
P2-10
Skip frequency band
0 to P1-01
Hz
0.0
Width of skip frequency band centred on
frequency set in P2-09
P2-11
Analog output /
Digital Output 1
Function select
Digital output mode
0 : Drive enabled
1 : Drive healthy
2 : Motor at target speed
3 : Motor Speed > 0
4 : Motor speed >= limit
5 : Motor current >= limit
6 : 2nd Analog Input >= limit
Analog Output Mode
7 : Motor speed
8 : Motor Current
9 : Motor power
7
Digital Output Mode. Logic 1 = +24V DC
0 : Logic 1 when the drive is enabled (Running)
1: Logic 1 When no Fault condition exists on the
drive
2 : Logic 1 when the motor speed matches the
setpoint speed
3 : Logic 1 when the motor runs above zero
speed
Options 4 to 6 : the Digital output is enabled
using the level set in P2-12h and P2-12L
Analog Output Mode
7 : Motor Speed, 0 to 10V = 0 to P-01
8 : Motor Current, 0 to 10V = 0 to 200% of P1-
08
9 : Motor power, 0 to 10V = 0 to 150% of drive
rated power
10 :
P2-12h
Digital Output Control
High Limit
0.0 to 200.0
%
100.0
With P2-11 = 4 to 6, Digital Output 1 is set to
Logic 1 (+24V DC) when the value set in P2-12h
is exceeded, and returns to Logic 0 (0V) when
the selected value reduces below the limit set
in P2-12L
P2-12L
Digital Output Control
Low Limit
0.0 to P2-12h
%
100.0
P2-13
User Relay Output
Function Select
0 : Drive enabled
1 : Drive healthy
2 : Motor at target speed
3 : Motor Speed >0
4 : Motor speed >= limit
5 : Motor current >= limit
6 : 2nd Analog Input >= limit
1
Selects the function assigned to the relay
output.
0 : Logic 1 when the drive is enabled (Running)
1 : Logic 1 When no Fault condition exists on
the drive
2 : Logic 1 when the motor speed matches the
setpoint speed
3 : Logic 1 when the motor runs above zero
speed
Options 4 to 6 : the Digital output is enabled
using the level set in P2-14h and P2-14L
P2-14h
Relay Output Control
High Limit
0.0 to 200.0
%
100.0
With P2-13 = 4 to 6, the User Relay Output is
set to Logic 1 (+24V DC) when the value set in
P2-14h is exceeded, and returns to Logic 0 (0V)
when the selected value reduces below the
limit set in P2-12L
P2-14L
Relay Output Control
Low Limit
0.0 to P2-14h
%
100.0
P2-15
Relay Output Mode
0 : Normally Open
1 : Normally Closed
-
0
Inverts the operating status of the User Relay
0 : Logic 1 = Relay Contacts Closed
1 : Logic 1 = Relay Contacts Open
The drive must be powered for the contacts to
close
P2-16
Standby Mode Wake Up
Speed
0.0 to 100.0
%
0.0
Drive will wake from Standby Mode if the
setpoint exceeds this value

Optidrive VTC –User Guide
18 www.invertek.co.uk
Par.
Description
Range
Units
Default
Explanation
P2-17
Start Mode Select
to
-
Edge-r : Following Power on or reset, the drive
will not start if Digital Input 1 remains closed.
The Input must be closed following a power on
or reset to start the drive.
Auto-0 : Following a Power On or Reset, the
drive will automatically start if Digital Input 1 is
closed.
Auto 1 to 5 : Following a Fault, the drive will
make up to 5 attempts to restart at 20 second
intervals. The drive must be powered down to
reset the counter
P2-18
Spin Start Enable
0 : Disabled
1 : Enabled
-
1 : Enabled
When enabled, on start up the drive will
attempt to determine if the motor is already
rotating, and will begin to control the motor
from its current speed. A short delay may be
observed when starting motors which are not
turning
P2-19
Keypad Restart Mode
0 : Minimum Speed, Edge-r
1 : Previous Speed, Edge-r
2 : Minimum Speed, Auto-r
3: Previous Speed, Auto-r
-
1
Active when P1-12 = 1 or 2
0 : Following a stop and restart, the drive will
run at minimum speed
1 : Following a stop and restart, the drive will
run at the last setpoint speed
2 : As per setting 0, except that the Run
command will be determined by the status of
Digital Input 1, and the user is not required to
press the keypad start button
3 : As per setting 1, except that the Run
command will be determined by the status of
Digital Input 1, and the user is not required to
press the keypad start button
P2-20
Standby Mode
0.0 : Disabled
0.1 to 60.0
seconds
0.0
When P2-20 >0, the drive enters standby mode
if the minimum speed is maintained for the
time period set in P2-20
P2-21
Display Scaling Factor
0.000 to 30.000
-
0.000
Disabled if P2-21 is set to 0.
If P2-21 is set >0, the variable selected in P2-22
is multiplied by the factor entered in P2-21, and
displayed whilst the drive is running
P2-22
Display Scaling Source
0 : 2nd Analog Input
1 : Motor Speed
2 : Motor Current
-
0
P2-23
Brake Circuit Enable
0 : Disabled
1: Enabled, Low Duty
2: Enabled, High Duty
3 : Enabled, No Protection
-
0
Enables the internal brake chopper on Size 2
and above drives. Settings 1 and 2 provide
software monitoring of the braking power
consumption. Setting 3 disables the protection,
and externally monitoring must be used
P2-24
Effective Switching
Frequency
4 to 16 / 24 / 32
Drive Power Rating Dependent
kHz
16
8
4
Effective power stage switching frequency.
Higher frequencies reduce the audible ‘ringing’
noise from the motor, and improve the output
current waveform, at the expense of increased
drive losses
P2-25
2nd Deceleration Ramp
time
0.0 to 3000.0
seconds
0.0
Deceleration 2nd ramp down time
Selected Automatically on mains power loss if
P1-05 = 2
Can also be selected by digital inputs,
dependent on P2-01 setting.
When set to 0, the drive decelerates as quickly
as possible, whilst preventing an overvoltage
trip
P2-26
Modbus Communication
Baud Rate
t9.6, t19.2, t38.4, t57.6, t115.2
r9.6, r19.2, r38.4, r57.6, r115.2
kbaud
t115.2
Modbus RTU serial data link communication
Baud Rate. A‘t’ Prefix indicates the drive will
trip if communication with the network master
is lost, after a preset time period. An ‘r’ Prefix
indicates that the Optidrive will Ramp to stop in
the event of a loss of communication with the
network master, after a preset time period.
P2-27
Drive Communication
Address
0: Disabled
1 to 63
-
1
Sets the communication address for the drive
when connected on an Optibus Network

Optidrive VTC –User Guide
www.invertek.co.uk 19
Par.
Description
Range
Units
Default
Explanation
P2-28
Master / Slave Mode
Select
0 : Slave Mode
1 : Master Mode
-
0
When in Master Mode, the drive transmits its
operational status via the serial data link. All
drives on the data link must have unique
addresses. Only one drive can be programmed
as a Master
P2-29
Digital / Slave speed
reference scaling factor
0.0 to 500.0
%
100.0
Scaling factor applied to any speed reference
on the serial data link, e.g. in Master / Slave
operation, a Slave drive will apply this scaling
factor to the transmitted Master speed
reference
P2-30
Bipolar analog input
format
= 0 - 24V DC
= 0 - 10V DC
= -10 to + 10V DC
= -24 to + 24V DC
-
Configures the analog input signal to match the
reference connected to terminal 6. Only
voltage signals can be directly connected, mA
reference signals require an external resistor
connection.
P2-31
Bipolar analog input
scaling
0.0 to 500.0
%
100.0
Scales the analog input by this factor, e.g. if P2-
30 is set for 0 –10V, and the scaling factor is
set to 200.0%, a 5 volt input will result in the
drive running at maximum speed (P1-01)
P2-32
Bipolar analog input offset
-500.0 to 500.0
%
0.0
Sets an offset, as a percentage of the full scale
range of the input, which is applied to the
analog input signal
P2-33
2nd analog input format
= Digital
= 0 to 10V DC
= 4 to 20mA
= 0 to 20mA
-
Selects the format for the 2nd analog input
Selecting sets the input up as a
digital input
P2-34
2nd analog input scaling
0.0 to 500.0
%
100.0
Scales the 2nd analog input by the factor set in
this parameter
P2-35
Digital speed reference
scaling control
0 : Disabled (No Scaling)
1 : Scaled by P2-29
2 : Scaled by P2-29, then bipolar
analog input added as an offset
3 : Scaled by P2-29 and by
bipolar analog input
-
0
Active in Keypad mode (P1-12 = 1 or 2) and
Master / Slave mode only.
1 : Actual Speed = Digital Speed x P2-29
2: Actual Speed = (Digital Speed x P2-29) +
bipolar analog reference
3 : Actual Speed = Digital Speed x P2-29 x
bipolar analog reference
P2-36
Analog output format
= 0 to 10V
= 4 to 20mA
= 10 to 0V
= 20 to 4mA
-
Selects the analog output signal format
P2-37
Extended menu access
code
0 to 9999
-
101
Defines the access code which must be entered
in P1-14 to access parameter groups above
Group 1
P2-38
Parameter Lock
0 : Unlocked
1 : Locked
-
0
When locked, all parameter changes are
prevented
P2-39
Hours Run Counter
0 to 99999
Hours
Read Only
Indicates the number of hours for which the
drive has run
P2-40
Drive Type / Rating
N/A
-
Read Only
Read only parameter, showing the drive type
and power rating

Optidrive VTC –User Guide
20 www.invertek.co.uk
6.3. Parameter Group 3 –PID Control
6.4. Parameter Group 4 –High Performance Motor Control
Par.
Description
Range
Units
Default
Explanation
P3-01
Proportional gain
0.1 to 30.0
-
2.0
PID Controller Proportional Gain. Higher values provide a greater
change in the drive output frequency in response to small changes
in the feedback signal. Too high a value can cause instability
P3-02
Integral time
constant
0.0 to 30.0
seconds
1.0
PID Controller Integral Time. Larger values provide a more damped
response for systems where the overall process responds slowly
P3-03
Differential time
constant
0.00 to 1.00
seconds
0.00
PID Differential Time Constant
P3-04
PID operating
mode
0 : Direct
1 : Inverse
-
0 : Direct
Direct operation –Motor speed increases with an increase in the
feedback signal
Inverse Operation –Motor speed decreases with an increase in the
feedback signal
P3-05
PID Setpoint /
reference select
0 : Digital
1 : Analog
-
0 : Digital
Selects the source for the PID Reference / Setpoint
0 : P3-06 is used
1 : Bipolar analog input is used
P3-06
PID digital
reference
0.0 to 100.0
%
0.0
Sets the preset digital PID reference / setpoint
P3-07
PID controller high
limit output
P3-08 to 100.0
%
100.0
Limits the maximum value output from the PID controller
P3-08
PID controller low
limit output
0.0 to P3-07
%
0.0
Limits the minimum output from the PID controller
P3-09
User PID output
limit / function
control
0 : Digital output limits
1 : Analog Upper Limit
2: Analog Lower Limit
3 : PID added to Bipolar
analog input reference
-
0
0 : PID output range limited by P3-07 & P3-08
1 : PID maximum output limited by the signal applied to the bipolar
analog input
2: PID minimum output limited by the signal applied to the bipolar
analog input
3: PID output is added to the speed reference applied to the bipolar
analog input
P3-10
PID feedback
source select
0 : 2nd Analog Input
1 : Bipolar analog input
-
0
Selects the source of the PID feedback signal
Par.
Description
Range
Units
Default
Explanation
P4-01
Reserved
-
-
P4-02
Motor parameter
autotune
0 : Disabled
1 : Enabled
-
0
When set to 1, the drive immediately carries out a non-
rotating autotune to measure the motor parameters for
optimum control and efficiency
Table of contents
Other Invertek Controllers manuals

Invertek
Invertek OPTIDRIVE E1 User manual

Invertek
Invertek Optidrive P2 series Manual

Invertek
Invertek OPTIDRIVE User manual

Invertek
Invertek SUNSTAR SERIES Owner's manual

Invertek
Invertek Compact 2 Series User manual

Invertek
Invertek Optidrive Elevator Troubleshooting guide

Invertek
Invertek Optidrive ODE-2-11005-1H01 User manual