manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. jablotron
  6. •
  7. Control Unit
  8. •
  9. jablotron AC-82 User manual

jablotron AC-82 User manual

The AC-82 wireless relay output module MJT51202
1
The AC-82 wireless relay output module
The AC-82 is a component of Jablotron’s Oasis JA-80 system. It is
mains-powered (230V AC) and it provides 2 relays which can be
controlled by radio signals and offers the following:
•Remotely controllable relay outputs which follow JA-80 control
panel programmable PG outputs
•Remote control of appliances using RC-8x controllers
•Relay output of JA-8x wireless detectors
•Relay output of TP-8x wireless thermostats
1
2
3
4
R
A
D
I
O
max F 5A/250V
buttons
LEDs
fuse
max 5 A
X
Y
Installation
Installation of this module shall only be undertaken by technicians holding a
certificate issued by an authorized distributor.
.
Warning: this device is galvanically connected to the mains.
Open the module’s cover (1 screw) and take out the circuit board (2
tabs). Install the back part of the housing to the desired place, re-install
the circuit board, connect the wires and enroll the desired wireless
devices.
Terminals
L,N Power: 230V AC/50Hz
COM Common terminal for the output contacts X and Y (fused by a 5
Amp fuse)
RE1 Normally open relay X contact
RE2 Normally open relay Y contact
The enrollment of transmitters
The X and Y relays are totally independent. Jablotron Oasis devices with
transmitters can be enrolled to them individually using the X and Y enrollment
buttons. Each relay offers 4different enrollment modes (1 to 4, see the following
table). The reaction of a relay to a transmitter signal depends on which
enrollmentmode thetransmittingdevice has beenenrolledto.
Enrollment procedure
•Use the X or Y button depending on which relay you want to enroll a device
to.
•Repeatedly press the relevant X or Y button to select the desired
enrollment mode 1 to 4 as indicated by the flashing of corresponding LEDs 1
to 4(seethetableforguidance onchoosing therightenrollmentmode).
•Activate the transmitter whilethe LED is flashing, as follows:
okey fob – press abutton
odetector or thermostat – connect its battery up (if it has already been
connected,first disconnect it, and then wait 10 seconds)
oControl panel PG output –keyin299inservicemode
•Enrollment isconfirmedby ashortflash from all theAC-82 indicators
•If no enrollment signal has been received within 10 sec., enrollment mode
automaticallyends.
•If youwish to enrollanotherdevice, repeat the aboveenrollment procedure.
Notes:
•If a device does not enroll, either it is too far from the receiver, or there is
another device already enrolled which cannot be combined with the new
one, or the maximum number of devices has beenexceeded.
•Each device can have its own individual reaction (it is possible to combine
different reactions for a single relay = enrolling different devices in different
enrollmentmodestothesame relay).
•The relay always performs the last received instruction (e.g. if the relay is
already on and a signal for a 2 minute pulse is received, the relay will stay
on for another 2 minutes andthen it will turn off).
•Each transmitting device (keyfob, detector, control panel, etc.) can be
enrolled to an unlimited numberof different receivers.
•Devices are enrolled to a non-volatile memory, so the AC-82 will not forget
them if its poweris disconnected
Use with RC-8x remote controllers
•Up to60 remote controllers canbeenrolledtoeach relay.
•To operate garage door or parking gate actuators, use the 1 sec. pulse
mode and connect the NC relay contact to the push button input of the
actuatorunit.
Use with JA-8x wireless detectors
•Detectors can be enrolled to pulse modes 1 and 2 (up to 60 detectors to each
relay). The 2 minute mode is suitable for automatically switching on lights,
ventilatorsetc.
•If a detector(s) is enrolled in mode 3, then the relay will be switched if the
detector’s tamper sensor is triggered. In this mode up to 8 detectors can be
enrolled to a single relay (which will be switched if any of the detectors is
tampered with), but no otherkind of device canbe enrolled, only detectors.
•If a detector(s) is enrolled in mode 4, then the relaytriggers if the detector’s
No.
Reaction Device Enrollment method Max.
number
Notes
1 1sec. pulse keyfob button pressing 60 •key fobs and detectors canbe combined
•the relay stays on1sec, turns off andisthen readyto beactivated again(the pulse is not
extended ifanother 1 sec. pulse activation signal is received whilethe relayis still on)
detector connectingbatteryup
2 2min. pulse keyfob buttonpressing 60 •keyfobs and detectors canbe combined
•if another 2min. activation signal isreceived whilethe relay is onfor 2min., then therelay
stays on2 min. more (the 2 minute pulse is extended if re-activated during the pulse)
detector connectingbatteryup
3 Latch keyfob buttonpressing 60 •impossible to combine keyfobs with detectors
•*latch= on –off– on – off….
•Tamper= on= relay turnson whena detector’s tampersensoristriggered.
Tamper= on detector connectingbatteryup 8
4 On / off
keyfob
buttonpressingenrolls
a pairof buttons 60 •impossible to combine keyfobs with detectors or with acontrol panelPG output
PG outputof
controlpanel entry of 299 in Service
mode 1 •impossible to combine PG output with detectorsorwith keyfobs
thermostat connectingbatteryup 8 •can be combined with keyfobs, detectors and a control panel PG output
Triggering =on detector connecting batteryup 8 •impossibleto combinedetectors with keyfobs or with a control panel PG output
The AC-82 wireless relay output module MJT51202
2
sensor is triggered. In this mode up to 8 detectors can be enrolled to a single
relay (which triggers if any of the detectors is triggered), but no other kind of
device canbe enrolled, only detectors.
•If the same detector is enrolled to relay X in mode 4 and to relay Y in
mode 3, then relay X will work as its sensortrigger output and the relay Y as
itstamperoutput.
Using the AC-82 with control panel PG output signals
•if the control panel is enrolled to the X relay (in mode 4 by entering 299) then
theX relay works as a control panel PGX output.
•if the control panel is enrolled to the Y relay (in mode 4 by entering 299) then
theY relay works as a control panel PGY output.
•Only one control panel PG output can be enrolled to each relay. No other
transmitting devices can be enrolled to a relay already occupied by a control
panelPG output.
Using the AC-82 with TP-8x wireless thermostats
•If a thermostat is enrolled to a relay (enrolled in mode 4 by connecting its
battery up), then this relaycan be used to controlthe heating.
•The enrollment of a thermostat to a relay is indicated by LED 1 for relay X
andLED 3 forrelayY.
•Up to 8 thermostats can be enrolled to each relay. A relay energizes if any
of thethermostatsrequires theheatingtobeon.
•Other devices can be combined with a thermostat and all be enrolled
to the same relay (a total of 8 devices, including the thermostat).
•Wireless devices enrolled together with a thermostat to a single relay
can be used to determine how that relay reacts signals from the
wireless thermostat. If desired, the relay can react only to the freezing
protection signal from the thermostat to turn on the heating when the
temperature gets below about +6C, or alternatively it can react to the
thermostat signal which demands heating when the room temperature
is lower than that pre-programmed in the thermostat. The relay can be
switched between these two modes by operating the wireless devices.
•If enrolled with a thermostat, the wireless devices have following
functions:
•Key fob RC-8x: A pair of buttons is enrolled. Pressing one button switches
the relay to regulating the heating to the pre-programmed temperature, and
pressing the other button switches the relay to regulating the heating to +6C
to avoid freezing. Multiplekey fobs canbe enrolledand can also be combined
with windowdetectors (see below).
•Window detectors: If a window is open, the relay reacts to the signals from
the JA-80M or JA-82M window detectors by switching to regulating the
heating to +6C to avoid freezing. Multiple window detectors can be enrolled
andthey canbecombined withkeyfobstoo.
•Control panel (CP) PGoutputs: To switch the relay between regulating the
temperature to the pre-programmed temperature or to +6C, the CP PG
outputs should be programmed in the CP to have an ON/OFF function (see
the CP manual). Theheating modecan then be selected from devices able to
switch the CP PG output such as the alarm system keypad, keyfob or even a
detector programmed to control the PG output. It could also be done remotely
by phone or the Internet (if a suitable communicator is used in the control
panel). Remember that PGX can only be enrolled to the X relay, and PGY to
the Y relay (see the above section), and it is not recommended to enroll key
fobs or detectors to the same relay to which thermostat(s) and PG outputs
are enrolled as the control panel repeats currently valid PG signals every 9
minutes. If you wish to combine keypad operation with keyfobs, it is best to
enroll the keyfobs to the control panel and program them to control the PG
output whichis enrolled to the relevantrelay.
•If the relay is in the mode which regulates the heating to a pre-programmed
temperature, this is indicated byLED 1for relay X, and LED 4for relayY. The
current contact status of relay X is shown by LED 2, with relay Y’s being
shownby LED4.
•The thermostat repeats its signal every 9 minutes, so if the AC-82
power is turned off for a while, and then on again, the relay will
synchronize with the thermostat within 9 minutes.
•If you switch the relay to the mode for regulating the heating to the pre-
programmed temperature (e.g. by keyfob etc.), then the mode is
changed instantly, however, the relay will only switch the heating on
after the thermostat has sent an instruction to turn the heating on (i.e.
the heating system’s reaction can be delayed by up to 9 minutes after
the request has been sent).
Resetting the AC-82 unit
New AC-82 units are sold with factory-default settings (i.e. both relays
have nothing enrolled). To reset a particular relay, do the following:
•Repeatedly press the X button (or the Y button for the Y relay) to
achieve the highest number LED flashes (4, or if not possible, then 3).
•Then, continuously press the same button and keep pressing it until all
the LEDs flash a couple of times (= reset). Then release the button.
Inverting the relay function (to a N.C. contact)
Both relays have only normally open contacts. If a normally closed
contact function is required (e.g. to turn off an appliance if the alarm
system is armed), then you can invert the relay function as follows:
•First reset the AC-82 unit.
•Using button X for relay X (or button Y for relay Y) makes LED number
4 flash.
•Now keep both the X and Y buttons pressed until all the LEDs flash a
couple of times.
•Therelay nowhas a normally closed contact function.
•To returnit toits normalfunction,resettheAC-82unit.
Note: Please remember, that if a relay has a normally closed contact function,
therelaywill switch offif theAC-82power isturned off.
Technical specifications
Power supply: 230V AC/50Hz, class protection II
Consumption about 1W
Relay contact rating
resistive load max. 2,5A / 250V AC
inductive (capacitive), lamp load max. 0,5A / 250V AC
Required fuse rating max. 5A
Communication band 868 MHz, Oasis protocol
Minimum distance from transmitting devices 1 meter
Dimensions, weight: 76 x 110 x 33 mm, antenna 35 mm, 120 g
Operating environment general, indoor –10 to +40 °C
Enclosure IP40 EN 60529
Mechanical immunity IK08 EN 50102
Complies with ETSI EN 300220, EN-50130-4, EN-55022 and EN 60950-1
Can be operated according to ERC REC 70-03
JABLOTRON ALARMS a.s. hereby declares that the AC-82 is in
compliance with the essential requirements and other relevant provisions of
Directive
99/5/EC
The original of the conformity assessment can be found
at www.jablotron.com, Technical Support section
Note: Although this product does not contain any harmful materials we
suggest you return the product to the dealer or directly to the producer after
use.

Other jablotron Control Unit manuals

jablotron JA-154E User manual

jablotron

jablotron JA-154E User manual

jablotron JA-112M User manual

jablotron

jablotron JA-112M User manual

jablotron JA-120N User manual

jablotron

jablotron JA-120N User manual

jablotron JA-153E User manual

jablotron

jablotron JA-153E User manual

jablotron UC-82 User manual

jablotron

jablotron UC-82 User manual

jablotron JB-111N User manual

jablotron

jablotron JB-111N User manual

jablotron JA-114E User manual

jablotron

jablotron JA-114E User manual

jablotron JA-153E User manual

jablotron

jablotron JA-153E User manual

jablotron JA-113E User manual

jablotron

jablotron JA-113E User manual

jablotron JA-120N User manual

jablotron

jablotron JA-120N User manual

jablotron JA-101K User manual

jablotron

jablotron JA-101K User manual

jablotron JA-120N Instruction manual

jablotron

jablotron JA-120N Instruction manual

jablotron JA-154E User manual

jablotron

jablotron JA-154E User manual

jablotron JA-190X User manual

jablotron

jablotron JA-190X User manual

jablotron AC-82 User manual

jablotron

jablotron AC-82 User manual

jablotron JA-113E User manual

jablotron

jablotron JA-113E User manual

jablotron JA-120N User manual

jablotron

jablotron JA-120N User manual

jablotron JA-101K User manual

jablotron

jablotron JA-101K User manual

jablotron JA-152E User manual

jablotron

jablotron JA-152E User manual

jablotron JA-120N User manual

jablotron

jablotron JA-120N User manual

Popular Control Unit manuals by other brands

SSS Siedle TLM/LL 611-02 Product information

SSS Siedle

SSS Siedle TLM/LL 611-02 Product information

Yingli Solar YL P-35b Series Installation and user manual

Yingli Solar

Yingli Solar YL P-35b Series Installation and user manual

Gardena 1278 Operator's manual

Gardena

Gardena 1278 Operator's manual

Cognex In-Sight 1400 Installation and reference manual

Cognex

Cognex In-Sight 1400 Installation and reference manual

Festo CPX-E-PN instructions

Festo

Festo CPX-E-PN instructions

Alfalaval Aseptic Mixproof Series instruction manual

Alfalaval

Alfalaval Aseptic Mixproof Series instruction manual

Tecnocontrol SE293K user manual

Tecnocontrol

Tecnocontrol SE293K user manual

mundoclima H10X Series instruction manual

mundoclima

mundoclima H10X Series instruction manual

Control Technologies CTI 2451 Installation and operation guide

Control Technologies

Control Technologies CTI 2451 Installation and operation guide

wink haus FM.V.SW operating instructions

wink haus

wink haus FM.V.SW operating instructions

EP Solar eBox-WIFI manual

EP Solar

EP Solar eBox-WIFI manual

SIGMA TEK BL 011 instruction manual

SIGMA TEK

SIGMA TEK BL 011 instruction manual

Paradox IP150 user guide

Paradox

Paradox IP150 user guide

FOR-A MFR-16 Operation manual

FOR-A

FOR-A MFR-16 Operation manual

Pegasus Astro ULTIMATE POWERBOX V2 product manual

Pegasus Astro

Pegasus Astro ULTIMATE POWERBOX V2 product manual

Sferalabs Strato Pi SPTM20XP user guide

Sferalabs

Sferalabs Strato Pi SPTM20XP user guide

SIGMA TEK SCP 011 manual

SIGMA TEK

SIGMA TEK SCP 011 manual

Planet CS6-PWR550-AC quick start guide

Planet

Planet CS6-PWR550-AC quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.