janitza Prophi 6T User manual

Doc. no. 2.020.025.1.a 6.0.E - 04/2020
Janitza electronics GmbH
Vor dem Polstück 6
D-35633 Lahnau
Support: +49 6441 9642-22
E-Mail: [email protected]
www.janitza.com
www.janitza.com
Power Factor Controller
Prophi®6T
Manual
dynamic power factor controller
Prophi 6T
Manual
Version 6.0 D , 11/2019
123456
Power Factor Controller
Blindleistungsregler
Auto
Program
Manual
Service
Enter
OK
Prophi
®
®

Prophi®6T
2
CONTENTS
Section 1 General / type series and accessories 2
Section 2 Installation of the controller / connection diagram 4
2.1 Current measurement 5
2.2 Programming of phase-correction
2.3 Alarm output / error messages 6
Section 3 Operating modes 6
Section 4 Automatic operation / display functions 7
Section 5 Programming
5.1 Program menu 8
5.2 Programming lock 10
Section 6 Manual operation / Programming of fixed stages 11
Section 7 Service menu 12
Section 8 Expert mode 12
8.1 Expert mode 1
8.2 Expert mode 2 13
Section 9 Control principle 14
Section 10 Initial operation 15
Section 11 Maintenance and warranty 15
Section 12 Troubleshooting 16
Section 13 Technical data 17
Annex: Annex 1 Table of control series 18
Description of control-series editor
Annex 2 Default settings 19
Operating diagram (fast programming)
- 1 -

Prophi®6T
3
Section1 General
Main features:
R6 switching outputs
RMeasuring voltage of 30...525V (L-N) or (L-L)
RSupply voltage 110...230 VAC
R20 pre-programmed control series with a self-optimized intelligent control
response
RControl-series editor for user-defined control series
RComplete menu-guided operation and display (10 languages)
RIlluminated graphic display with 2 x 16 characters
RFour-quadrant operation
RDisplay of various line parameters (V, I, F, Q, P, S...)
RDisplay and monitoring of temperature
RStorage of maximum line-parameter
RManual / automatic operation
RProgramming of fixed stages and the option of skipping individual outputs
RNo-voltage turn-off
RError detection for various states and interference-message output
RSwitchboard-integrated housing 144x144x55 mm
The dynamic power factor controller Prophi-6T represents the consequent development
of the Prophi-series with new innovative ideas and a multitude of functions.
It has been especially designed to control thyristor modules for dynamic switching of
power capacitors for power factor correction (for example TSM-LC or similar). By using a
very fast type of processor, it has been possible to obtain extreme short switching cycles
which allows the usage for dynamic power factor correction.
In addition to a switching time of <20 ms, the intelligent control principle provides an
extremely fast tuning of the power factor by simultaneous switching of several steps.
Several parameters that can be edited allow an optimized adjustment to different
thyristor modules.
The device is distinguished by user-friendly operation based on menu-guided displays in
plain text. Its new features permit an intuitive mode of operation. Easy-to-understand
symbols and texts in 10 local languages combine simplest operability with self-evident
displays.
- 2 -

Prophi®6T
4
Fig.2 Rear view
- 3 -
Operating mode
- Automatic
- Programming
- Manual operation
- Service
- Expert mode
Enter / OK
Confirm and
store values
Increase
selected
parameter
Reduce
selected
parameter
The controller is supplied as standard for an operating voltage of 110...230VAC(+/-15%),
a measuring voltage of 30...525 VAC (L-N) or (L-L) and a measuring current of 5A or 1A.
(programmable). A voltage converter is required for different operating voltages.
Caution!
Voltages which exceed the allowed voltage range can damage the
device !
!
Fig.1 Front view
123456
Power Factor Controller
Blindleistungsregler
Auto
Program
Manual
Service
Enter
OK
Prophi
®
L1 ( R )
L2 ( S )
L3 ( T )
N
k l
P1 1 2 3 4 5 6
Blindleistungs-
reg l er Pro p h i 6T
T 2A
T 2A
PE
a b
Ub Um Im
(L) (N)
L3
(L1)
L2
(N) k l a b P1123456
Meßstrom
Im ( 5 A/ 1A)
Betriebs-
sp a nn ung
Ub
Me ß -
sp a nn ung
Um
MADE IN GERMANY
Schaltausgang
1- 6
Alarm-
re l ai s
Betriebs-
spannung
Meß-
spannung
Meß-
strom
Alarm-
relais
Transistorausgänge
Transistorausgänge 1-6

Prophi®6T
5
Section 2 Installation and connection of the controller
The device is designed to be incorporated into the front panel of a PFC-cabinet. It requires
a switchboard section of 138 x 138 mm to DIN 43700/ IEC 61554. The controller is
inserted from the front and is attached by means of the appended clamps. The
controller may be inserted only by qualified technicians and must be operated in
accordance with the specified safety regulations.
Before the controller is connected up, all leads and cables must be checked to ensure that
no current is flowing through them and the current converter must be short-circuited.
Care should be taken to ensure that the measuring voltage and current are in the correct
phase position. The measuring-current circuit must be wired with copper leads of
2
2.5mm . The connection should be set up as shown in Fig. 3. The specified safety
regulations must be observed.
The measuring voltage may lie in the range from 30- 525 V and can be connected between
L - N (default) or between L - L. (programming of phase correction needed).
The operating voltage is 110...230 V +/- 15% and can be connected between L - N or L-L.
(depending of the grid)
Fig. 3: Connection plan
- 4 -
L1 (R)
L2 (S)
L3 (T)
N
meas.current
Im (5A/1A )
1. capacitor-
branc
h
supply -
voltage
Ub
meas -
spannung
Um k l
P1
1 2 3 4 5 6
transistor-
output 1-6
alarm-
relay
P
P
r
r
o
o
p
p
h
h
i
i
6
6
T
T
T 2A
T 2A
PE
a b
Ub Um Im
(L) (N) L1 N k l
(L3) (L2)
TSM-LC
+24V-
+ -

Prophi®6T
6
2.2 Programming of phase-correction - e.g. connection directly L-L (400V)
Adjustment of phase-correction between voltage and current in the meas. system is done
in expert mode 1 (page 14)
Example:
Meas.current: L1
Meas. Voltage L3-L2
Phase U/I [ 90°]
- 5 -
2.1 Current measurement
When installing the current converter, care should be taken to ensure that the load
current flows through it. The outputs of the compensation network must be installed
behind the current converter (in the direction of current flow). If the device is connected
up via sum-current converters, the overall conversion ratio is entered.
kK k K
lL l L
Feed 1 Feed 2
K L K L
Measurement via sum current converter
Prophi-6T
Current
measurement
k l
k l
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A/5A
C.converter ratio is: 2000/5A
L1 (R )
L2 (S )
L3 (T )
N
k l
T 2A
T 2A
PE
Ub Um Im
(L) (N) (L3) (L2) k l
using meas. current meas. voltage phase-angle
preset L1 L1 - N 0°
L1 L1 - L2 30°
L1 (k<->l) L2 - N 60°
example L1 L3 - L2 90°
L1 L3 - N 120°
L1 L3 - L1 150°
L1 (k<->l) L1 - N 180°
L1 (k<->l) L1 - L2 210°
L1 L2 - N 240°
L1 L2 - L3 270°
L1 (k<->l) L3 - N 300°
L1 (k<->l) L3 - L1 330°

Prophi®6T
7
2.3 Alarm output / error messages
The alarm contact is closed in normal operation and opens in the event of a fault. The
relevant fault is simultaneously shown on the display in plain text (alternating with the
standard display in automatic operation). The following fault messages are displayed:
UNDER-COMPENSATED Display and relay output
missing reactive power
OVER-COMPENSATED Display and relay output
OVERCURRENT Display and relay output
MEASURING VOLTAGE ? Display and relay output
OVERTEMPERATURE Display and relay output
OVERVOLTAGE Display and relay output
UNDERVOLTAGE Display and relay output
HARMONICS Display and relay output
Section 3 Operating modes
When the operating voltage is switched on, the device displays its designation and
software version, then changes to its normal operating status (automatic operation). The
active cos-phi value is always displayed in the upper line and the currently connected
capacitors are shown as symbols in the lower line (operating display).
Additionally several messages for different operation states are generated. An individual
adjustment resp. suppression of particular messages is possible in expert mode 2. During
suppression, the indication of the message in the display, a possible release via alarm-
relays and effects on the controlling process will be prevented.
- 6 -
Automatic operation
Display of active power-line cos phi
Active capacitor
branches
Control direction
(here connected-in)
Supply display (for
4-quadrant operation)
The control direction is symbolized
by a closed arrow
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (discharge
time) is running before an impending
switching step
A double arrow symbolizes fast
switching of several branches
Connecting-in
Connecting-out
Automatic oper.
to display operation to programming to manual operation to value buffer to special functions
Programming Manual operation Service Expert mode
Repeated pressing of the "Operating Mode” key takes the user to the various menus in
sequence: Automatic operation - Programming - Manual (manual operation)-
Service - Expert mode and back.
cos 0.76 IND
j

Prophi®6T
8
Section 4 Automatic operation - display of network parameter
The controller is set to automatic operation as standard. Capacitor stages are then
automatically connected in or out in order to reach the target power factor. This happens
when the required reactive power exceeds the value of the smallest capacitor stage.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER” key:
Action Display
ENTER 1 LINE VOLTAGE in V
ENTER 2 APPARENT CURRENT in A / %
ENTER 3 REACTIVE POWER in kvar / %
ENTER 4 ACTIVE POWER in kW / %
ENTER 5 APPARENT POWER in kVA / %
ENTER 6 DIFF. kVAR TO TARGET COS
ENTER 7 FREQUENCY in Hz
ENTER 8 TEMPERATURE in °C / °F
ENTER 9 HARMONICS (3.-19.) V/%, I/%
ENTER 10 THD-V; THD-I in%
ENTER Software version
ENTER Return to: 1
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 60 seconds, the display automatically returns to the operating status!
- 7 -
Switching outputs
The switching outputs are executed as
transistor outputs.
The transistor outputs are used via an
additional auxiliary voltage (10 - 24 VDC) for
a direct triggering of thyristor switches for the
dynamic power factor correction (i.e. TSM).
Max.current for a single output: 40mA
Sum current all 6 outputs: 150mA
X2:1
X2:2
X2:6 (12)
X2:P 200mA
Further stages
J
to thyristor module
( e.g. TSM-LC...)
Block circuit of the transistor output
+ -
E.g. 24VDC
!WARNING: Mixing-up of outputs and thus applying of 230 VAC on
the transistor outputs will destroy the internal transistors !
1 LINE VOLTAGE
230.1 V

Prophi®6T
9
Section 5 Programming
Pressing the "Operating mode” key once takes the user from automatic operation to
Programming mode.
The upper display always shows the parameter and the lower one the set value. The
values are changed by pressing the é / ê keys. Subsequent pressing of the "ENTER” key
stores the value and takes the user to the next parameter.
To quit programming mode in any step, press the "Operating mode” key.
5.1. Program Menu
LANGUAGE SELECTION: This selects the language of the operating menu
(German, English, Spanish, French, Russian, Czech, Dutch, Polish,
Portuguese, Turkish)
1 I-CONVERTER PRIM: [ 5...13000]A
This selects the primary current of the current converter. Adjustment is
via the é / ê keys. Save and continue with ENTER
2 I-CONVERTER SEC: [ 5 or 1]A
This sets the secondary current of the current converter
Selection via é / ê. Save and continue with ENTER
3 END STOPP: [ 1...6 ]
By setting the end stopp, the number of active capacitor branches is
matched to the respective capacitor bank. This is done via the é / ê
keys. The visible symbols of the capacitors correspond to the connected
outputs. The maximum possible number of capacitor branches is pre-
set at the works (6 branches).
Save and continue with ENTER
4 CONTROL SERIES: [ 1...20 + E ]
The ratio of the capacitor branch power determines the control series,
the power of the first capacitor always being assigned the value 1. The
control series required for the compensation network is again selected
via the é/ê keys. If the required control series should exceptionally not
be present (Annex 1), the user may define a special one (control series
"E”).More on this point in the control-series editor in Annex 1.
Save and continue with ENTER
5 CONTROL PRINCIPLE: The control preference may be selected here:
SEQUENTIAL connection
LOOP connection
INTELLIGENT loop connection (default setting)
COMBINED CHOKE
See Section 9 for an explanation of the various control modes.
Selection with é / ê keys.
Save and continue with ENTER
- 8 -

Prophi®6T
10
6 POWER 1. STAGE: [ 0.01 ... 255.99 ] kvar
To determine the controller's response sensitivity, the dimensions of the network's
smallest capacitor (stage 1) must be known. They are entered in two steps in kvar.
The integral kvar values (before the comma) are initially selected via the é / ê
keys and saved with ENTER. The positions after the comma are then selected,
again via the é / ê keys. If the response sensitivity is being undercut, a warning
will occur ( indication of “!” in the display )
Save and continue with ENTER
7 TARGET COS PHI: [ 0.3 ind ... 0.3 cap ]
By setting the target cos phi, the power factor to be attained via the PF correction
is defined. It is also set via the é / ê keys.
Save and continue with ENTER
10 CONNECTING TIME [ 20...1000]ms
This refers to the time between connecting the capacitors to increase the
momentary network capacitance. It should be noted that in practical operation the
real connection time is affected by the discharge time (locking time).
Default setting: 1000 ms
Selection is performed via the é /ê keys. Continue with ENTER
8 MEASURING VOLTAGE [ 30 ... 525] V
Programming the measuring voltage. The values programmed here always refer
to the voltage at the clamps of the device!
The voltage is selected via the é /ê keys. Save and continue with ENTER.
9 V - CONVERTER RATIO [ NO ] possible: 230V...380kV / Vmeas.
When a measuring-voltage converter (e.g. for HV- measurement) is used, its
conversion ratio should be programmed here:
- Direct programming of the prim. voltage of the voltage converter
- - The sec. voltage is set automatically from the programmed meas.voltage under 8
Selection via the é /ê keys. Save and continue with ENTER.
- 9 -
L1 (R) L1 (R)
L2 (S) L2 (S)
L3 (T) L3 (T)
N
meas .current
Im (X/ 1A)
supp ly-
volt age
Vb
meas .-
volt age
Vm
P
P
r
r
o
o
p
p
h
h
i
i
-
-
6
6
T
T
T 2A
T 2A
PE
Vb VmIm
HV - voltage
20 kV / 400 V
20000
100

Prophi®6T
11
- 10 -
11 DISCONNECTING TIME [ 20 ... 1000]ms
This refers to the time between disconnecting the capacitors to reduce the
momentary network capacitance..
Default setting: 1000 ms
Selection is performed via the é /ê keys. Continue with ENTER
12 DISCHARGE TIME [ 20 ...1000]ms
This is the time for which an individual output is blocked between connecting and
disconnecting. This blocking time has priority over connecting and disconnecting
times. It depends on the capacitor discharge rating and thus is specified by the
compensation network.
Default setting: 200 ms
Selection is performed via the é /ê keys. Continue with ENTER
13 ALARM TEMP [ 50...85]°C
The alarm temperature programmed here is the temperature at which the
capacitor stages are disconnected in steps. The controller’s alarm relay responds
after 60 seconds. At the same time the display shows the cause of the alarm
(over-temperature). If the temperature drops again, the required branches are
automatically re-connected in steps.
The selection is performed with the é /ê keys. Save and continue with ENTER.
27
Default: 20 sec.
28 HARMONICS (harmonic limit) [ 7 ]% (0.5...25.5)%
A limit for THD-V (in%) can be entered here. When this threshold is exceeded, a
message is given. THD-V is the ratio of the geometric sum of the uneven
harmonics to the fundamental.
DELAY-TIME OF ERROR-MESSAGES [ 0... 255] sec.
The delay time for error-messages in the display can be changed here.
BASIC SETTING: [ YES / NO ]
When the selection is made with YES and confirmed with ENTER, all parameters
are reset to the basic setting made by the PFC-system manufacturer.
(Optimal network values when the controller was supplied with a complete PFC-
system). If the controller is supplied from the works, this point corresponds to the
default setting.
CAUTION: All user settings are lost!
Programming is now completed. The controller has returned to point 1 of the
programming menu.
5.2 Programming lock
The Prophi-6T is equipped with a programming lock to ensure protection from
unauthorized or inadvertent changes to the system parameters. The lock can be activated
in expert mode. If the lock is active, all parameters can be checked but not changed.

Prophi®6T
12
Section 6 Manual operation (initial operation, maintenance, service)
Programming of fixed stages
In manual operation, capacitor branches can be connected/disconnected in the set
control series and switching time - irrespective of prevailing power-line conditions.
The starting condition is STOPP (no stages connected). Connections are made by
pressing the é key. Pressing ê initially leads back to STOPP mode. Repeated pressing of
ê leads to the disconnection of stages. The active operating status and active power
factor are always shown on the display (self-explanatory).
Pressing ENTER takes the user to the menu point "Programming of fixed stages”.
In the normal case, all stages are programmed for automatic operation (default setting).
In special cases, all controller outputs (C1 - C6) may be permanently defined in
succession (continued switching via ENTER) for the following statuses:
OFF: The output is continuously disconnected - e.g. for temporarily disconnecting a
defective capacitor. The capacitor symbol for this output is faded out. Underlining
appears.
AUTO: Automatic (normal) operation
The relevant output is marked by a capacitor symbol.
FIXED: The output is continuously connected, e.g. for fixed PFC. The output is
marked by an underlined capacitor symbol.
TEST:
The active stage is blinking. The required status is set via é /ê. By pressing ENTER, the
user saves this step and moves to the next stage.
The programmed statuses for the outputs also remain visible on the display in automatic
operation.
After the required settings have been made, pressing the "Operating Mode” key takes the
user to the next menu ("Service”) or further to "Automatic Operation”.
short-term switch-on of individual outputs possible for test purpose
AUTO OFF FIX (Currently selected stage blinks)
Setting of fixed stages
Manual operation
- 11 -
STOP 0.99 CAPCAP ON 0.97 IND
C 6 - [FIXED]

Prophi®6T
13
Section 7 Service menu
The service menu is reached by the operating-mode key.
The stored maximum values of the network parameters can be displayed here.
In addition, a fault memory is available, in which the last 40 fault states of the system are
stored with fault code and in plain text. (This allows, for example, capturing short lived
events of overtemperature or overvoltage)
Action Display
ENTER 1 min./max. VOLTAGE in V
ENTER 2 max. REACTIVE POWER in kvar / %
ENTER 3 max. ACTIVE POWER in kW / %
ENTER 4 max. APPARENT POWER in kVA / %
ENTER 5 max. TEMPERATURE in °C / °F
ENTER 6 RESET the maximum values
ENTER ERROR MEMORY E [1] - .... in plaintext
ENTER ERROR MEMORY RESET
ENTER Back to 1
Section 8 Expert mode 1 and 2
The expert mode is meant for the adjustment of values which normally should not be
changed. As a protection against mal-operation this level has an access code branching
out in Expert mode 1 or 2.
Password: Expert mode 1: “ 6343” Expert mode 2: “2244”
8.1. Expert mode 1
2 BASIC SETTING NEW [NO] (NO / YES)
Storage of active programming as a new basic setting.
Caution: The original values are overwritten in the process!
3 SWITCHING POWER max [100] kvar (multiples of the smallest stage)
This factor specifies the maximum power which may be switched in one switching
step. It can be used to control the intelligent control system, which switches
several stages as a function of the power-factor requirement.
4 SWITCH.TRIGGER [66]% (30...100%)
Threshold for switching on of next stage.
It should not be changed in normal case!
5 OPERATING LOCK [NO] (NO / YES)
6 PHASE I [0°]
[L1] - L1 - N Adjustment of current phase position
7 PHASE U [0°]
L1 - [L1 - N] Adjustment of voltage phase position
Phase correction between voltage and current in the measuring system.
This setting allows to measure also in systems without neutral.(example p.5)

Prophi®6T
14
8 POWER 1. STEP [0...255] (0...2550)
Range for entering the stage outputs can be increased here (e.g. HV-measuring)
9 CONTROL [3] PHASE ( 3 / 1 )
The measuring system of the controller is generally based on single-phase
measurement. For all standard settings (three-phase), the measurement is
converted and all outputs displayed as three-phase values (symmetry in grid
assumed). In the single-phase setting, display and control apply only to the single-
phase value measured.
10 DISPLAY [cos Phi] (cos Phi/ tan Phi)
Changeover between cos/tan Phi for all displays and calculations in the device
11 HARMONICS [NO] (NO/ YES)
Release of calculation and display of harmonics.
8.2. Expert mode 2 ( Password: 2244)
The additional 2nd expert mode includes all messages for operation, warning and error which
are displayed by the Prophi-6T. Here they may be deactivated separately. When deactivated,
the indication of the message in the display as well as possible activation of the relay or effects
on the control behavior are suppressed.
EXPERT MODE 2 [YES] (YES/NO)
Activation of particular operation, warning and error messages (list of all
messages in menu plan last page)
2 ALARM TIME [120] sec. (1...255 sec.)
Time after which the alarm relay will respond
3 UNDERVOLTAGE [50] % (20...100%)
meas. voltage below this threshold will switch OFF all stages
at the same time
4 OVERVOLTAGE [115]% (105...140%)
meas. voltage above this threshold will switch OFF the stages
step by step
5 FREQUENCY [40...80]Hz (50Hz / 60Hz)
Measurement by the controller is done automatically in grids of 40 … 80 Hz.
In grids with extremely poor voltage quality it is recommend to select a fix frequency (50
or 60 Hz) to avoid measuring errors due to voltage sags.
- 13 -

Prophi®6T
15
- 14 -
Section 9 Control principle
The control response of the Prophi-6T can be selected in programming mode. In principle,
the controller has four different control modes:
1. Sequential connection
In sequential connection, the required capacitor stages are successively connected
and disconnected in stages (last in - first out). The ranking of each step always
corresponds to the power of the smallest stage.
Advantage: Exact definition of the next capacitor to be connected in each case
Disadvantage: Long settling time, high switching frequency of the small stages
In order to shorten the settling time, the BR6000 switches several stages
simultaneously for a large power-factor requirement. This applies to all
control types. The maximum dimensions of the simultaneously switching
branches can be changed in expert mode. If the value of the smallest stage
is pre-selected, the conventional sequential connection is obtained.
2. Loop connection
In this variant, the controller operates in loop mode (first in - first out) which
minimizes the wear on the capacitor bank, i.e. where stages are of equivalent
dimensions, the stage which was disconnected for the longest period of time is
always connected next.
Advantage: Balanced utilization of equivalent stages and thus an increased
operating life of the capacitor bank.
Disadvantage: This mode can only be used in control series with groups of the same
stage power and long settling time, as every switching step corresponds to the value
of the smallest stage.
3. Intelligent loop connection (default setting )
The intelligent control principle combines the advantages of the network-sparing
loop connection (first in - first out) with a much faster settling time, even for large
load skips, and reaches this goal with the fewest possible switching operations of the
capacitor stages. The optimized time response is achieved by the simultaneous
switching of several or larger capacitor groups as a function of the missing power
factor in the power line. Both the number of real switching frequencies of the
capacitors as well as the turn-on times of the branches are considered.
Advantage: Reaches the target cos phi in a fast-optimized settling time with a low
switching frequency of the capacitors.
4. Combined de-tuning (special case for combined de-tuned banks)
Within a combined de-tuned application, 2 adjoining equal steps are switched with
just one joint choke. This pairwise de-tuning requires an appropriate closed control
series (i.e. 1:1:1:1..., 1:1:2:2..., 1:1:2:2:4:4... or similar)
The condition for the switching behavior is defined in such a way that the number of
activated odd steps is always greater than or equal to the number of activated even
steps. The controller complies with the requirements of the control regime while
largely conforming to the intelligent switching behavior.

Prophi®6T
16
- 15 -
Section 10 Initial operation
The controller must have been installed before being set up and operated.
All network-specific parameters are fully programmed as described in section 5
(Programming) by being entered in sequence and stored. The controller is then set to
automatic operation with the operating mode key. It is now ready for operation.
Section 11 Maintenance and warranty
The controller should need no maintenance if the operating conditions are observed.
However, it is recommended that a functional check of the controller be performed in
conjunction with the regular checking of the capacitor bank. In the event of any
interventions in the controller during the warranty period, all warranty claims lapse.

Prophi®6T
17
- 16 -
Fault
At target cos phi=1 and inductive load,
switch-off or connection of capacitor in
the corrected line
Supply / Drawing mismatched
Wrong line cos phi is displayed
Display:"UNDER CURRENT”
Display: "OVERCURRENT”
Alarm relay: after 1 min.
Display: "UNDERCOMPENSATED”
Alarm relay: after 1 min.
Display: "OVERCOMPENSATED”
Alarm relay: after 1 min.
Display: "MEASUREMENT VOLTAGE ???”
Alarm relay: after 1 min.
Display: "OVERTEMPERATURE”
Alarm relay: after 1 min.
Stages are disconnected for an inductive
line or connected for a capacitive line
The controller does not connect all
stages, or cos phi does not change at the
last stages
In automatic operation, individual stages
are not connected or disconnected
In strongly asymmetrically loaded lines,
differences may occur between control
response and power-factor
measurement, as the power factor is
measured in single phase.
No operating voltage
Check / Solution
Check terminals of the measuring voltage and
current (l and k)!
Check phase position
See above
Current in measuring range?
Line interruption?
Wrong current-converter factor?
Current transformer short-circuited?
Check current-converter ratio
Go through measuring current range
Check connection and phase position!
All stages connected - target cos phi not
reached: compensation network sufficiently
dimensioned?
Check connection and phase position!
Capacitive grid, although all stages
disconnected
No measurement voltage!
Cabinet temperature too high: Outputs are
switched off in stages irrespective of power-line
conditions
If a target cos phi is set which deviates from 1
despite an inductive line load, the display <
(disconnect stages) may light up. The arrows
indicate the control direction and not the line
conditions.
Check END STOPP !
Check whether individual stages are
programmed as fixed stages or OFF in the
"Manual operation / Fixed stages” menu!
Line measurements allow the most favorable
phase for measuring the power factor to be
determined. The current converter is set
accordingly for the measuring current.
Note: No display, alarm relay is activated
(open)
Section 12 Troubleshooting

Prophi®6T
18
- 17 -
Section 13 Technical data
Type series
Outputs
Languages
Switching power of outputs
Number of active outputs
Operation and display
Number of control series
User-defined control series
Control principle
Operating voltage
Measuring voltage
Measuring current
Power drawn
Sensitivity
Target cos phi
Connecting time
Disconnecting time
Discharge time
Fixed stages/ skipped stages
Alarm relay
No-voltage triggering
Display of power-line parameters
Storage of maximum values
Temperature measurement range
Error memory
Accuracy
Housing
Weight
Operating ambient temperature
Protection type to DIN 40 050
Safety guidelines
Sensitivity to interference
(industrial areas)
Prophi-6T
6
G / E / ES / RU / NL / CZ / PL / F / PT/ TR
24 VDC, appr. 40mA for triggering TSM-LC
Programmable
Illuminated graphic display 2 x 16 characters
with convenient operating level
20
1
Sequential connection, loop connection or
self-optimized switching response
Four-quadrant operation
110...230 VAC, +/-15%, 50 / 60Hz
30...525 VAC, (L-N) oder (L-L), 50 / 60Hz
X : 5 / 1A selectable
< 5 VA
50 mA / 10 mA
0.3 inductive to 0.3 capacitive adjustable
Selectable from 20 ms - 1 sec.
Selectable from 20 ms - 1 sec.
Selectable from 20 ms - 1 sec.
Programmable
Standard
Standard
Power factor, voltage, apparent current,
frequency, reactive-, active-, apparent power,
missing kvar, temperature, harmonics
Voltage, reactive power, active power, apparent
power, temperature
-30 ... 100°C
Last 40 error states are stored
Current, voltage: 1%
Reactive-, active-, apparent power: 2%
Switchboard-integrated housing
DIN 43 700, 144 x 144 x 53 mm
1 kg
-20 to +60°C
Front: IP 54, Rear: IP 20
IEC 61010, EN 61010-1
IEC 61000-6-2, EN 61326
IEC 61000-4-2: 8kV
IEC 61000-4-4: 4kV

Prophi®6T
19
- 18 -
Annex 1: Table of control series
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
"E"
Control series
1 : 1 : 1 : 1 : 1 : 1
1 : 2 : 2 : 2 : 2 : 2
1 : 2 : 3 : 3 : 3 : 3
1 : 2 : 3 : 4 : 4 : 4
1 : 2 : 4 : 4 : 4 : 4
1 : 2 : 3 : 6 : 6 : 6
1 : 2 : 4 : 8 : 8 : 8
1 : 1 : 1 : 1 : 2 : 2
1 : 1 : 1 : 1 : 1 : 6
1 : 1 : 2 : 2 : 2 : 2
1 : 1 : 2 : 2 : 2 : 4
1 : 1 : 2 : 2 : 4 : 4
1 : 1 : 1 : 2 : 2 : 2
1 : 1 : 2 : 3 : 3 : 3
1 : 1 : 2 : 4 : 4 : 4
1 : 1 : 2 : 4 : 8 : 8
1 : 2 : 2 : 3 : 3 : 3
1 : 2 : 3 : 4 : 4 : 8
1 : 2 : 2 : 4 : 4 : 4
1 : 2 : 2 : 2 : 4 : 4
Control-series editor
Loop connection
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Possible
Control -series editor (programming up to a rating of 30)
The control-series editor allows the user to simply define his/her own control series if the
required control series is not available for any reason.
The last control series - Control Series E - is selected by pressing the "Programming” key
(point 4: Control series) and confirmed with ENTER. This leads to the insertion of an
additional menu point in the main menu -> the control-series editor. It may be reached
via the "Operating Mode” key.
In the control-series editor, all stages can be set in succession to the desired value with
the selection keys é / ê. The next stage in each case is reached by pressing ENTER.
In the control series editor, the various steps may be programmed up to a rating of 30 (!).
The rating >9 is indicated in the display as follows:
10=A, 11=B, 12=C, 13=D, 14=E, 15=F, 16=G .... 30=U
The maximum number of stages can be limited by a programmed END STOPP < 6
ALL control series can be generated (even downwards). The customer will decide
whether the generated control series is of sense.
ProgrammingAutomatic Control series
editor Manual operation Service Expert mode

Prophi®6T
20
Annex 2: Default settings
No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Parameter
LANGUAGE
I CONVERTER prim.
I CONVERTER sec.
END STOPP
CONTROL SERIES
CONTROL PRINCIPLE
POWER 1. STAGE
TARGET COS-PHI
MEASURING VOLTAGE
V- CONVERTER RATIO
SWITCH- IN TIME
SWITCH- OFF TIME
DISCHARGE TIME
ALARM TEMP.
DELAY ERROR MESSAGE
Capacitor stages
Password Expert mode 1
Password Expert mode 2
Trigger value
Max.simult.switch.power
Operating lock
Phase shift U/I
Power 1. stage
Control
Default setting
ENGLISH
1000 A
5 A
6
1
INTELLIGENT
25.00 kvar
0.98 IND
230 V L-N
- NO -
1 sec.
1 sec.
0.2 sec.
55 °C
20 sec.
AUTO
6343
2244
66%
4 x smallest stage
- NO -
0 °
0...255 kvar
3 - phase
Programmed values of this
system (to be entered by
manufacturer or operator)
Cannot be changed
Cannot be changed
Note: The following values for the default settings apply only if the controller is supplied
directly from the manufacturer. Otherwise, these values may have been replaced by
settings made by the manufacturer of the compensation network (optimal values for the
relevant network).
- 19 -
Other janitza Controllers manuals