janitza Prophi 15T-III User manual

Dok. Nr. 2.020.022.1.a 1.2.E - 02/2020
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Telefonischer Support: +49 6441 9642-22
E-Mail: [email protected]
www.janitza.com
www.janitza.com
Power Factor Controller
Prophi®15T-III
Manual
Power Factor Controller
Prophi 15T-III
Manual
Version 1.2 E

Prophi®15T-III
2
!
CAUTIONS:
1. High voltage !
2. The device may only be used indoor !

Prophi®15T-III
3
CONTENTS
Section 1 General p.3
Section 2 Installation and instructions for usage p.4
Section 3 Connection alternatives measuring voltage p.6
and measuring current
Section 4 Display functions p.8
Section 5 Display of grid parameters p.9
Section 6 PROGRAM-MODE / Manual programming p.11
6.1 Programming lock p.19
Section 7 HELP-function / actual assignment of outputs p.19
Section 8 MANUAL OPERATION p.21
Section 9 SERVICE MENU / Error storage p.22
Section 10 EXPERT MODE
10.1 Expert-Mode 1 p.23
10.2 Expert-Mode 2 p.25
Section 11 Control principle p.26
Section 12 Interfaces p.27
12.1 Application: Controller-coupling p.28
12.2 Application: Hybrid-mode p.29
Section 13 Alarm relay / Error messages p.31
Section 14 Display-editor p.31
Section 15 OSCI-MODE p.31
Section 16 Maintenance and warranty p.31
Appendixes/ Tables:
Annex 1 Control series table p.32
Control series editor
Annex 2 Troubleshooting p.33
Annex 3 Technical data p.35
Annex 4 Factory settings p.37
Annex 5 Operation diagram p.39
- 2 -

Prophi®15T-III
4
Section 1: GENERAL
The power factor controller Prophi-15T-III is the consequent follow-up development of
the well proven series Prophi.
The main distinctive feature is the new 3-phases measuring system. Due to the 3-phases
recording of voltage and current the device allows a convenient usage as grid measuring
device and as power factor controller.
All measuring values can be edited and may be displayed in big letters for easier
readability.
2 interfaces are standard. By means of the comfortable windows-software that is included
in the delivery and by using one interface for a connection to a PC the execution and
evaluation of grid measurements is possible. The second interface can be used for
customer specific purposes.
Used as PF-controller various control modes are available. They allow not only to control
according to the phase with the highest load or the average demand of the phases, but
also to realize a real single-phase control (balancing) or a mix of balancing and
conventional three-phases-control.
For an easy usage the concept of graphic menu navigation has mainly been adapted.
New are amongst others an integrated help (HELP-button) and the possibility to jump
back in the programming menu by an additional ESCape-button.
The usage of a fully graphic support display allows an additional Oscilloscope-Mode where
the phases (half waves) of voltage and current can graphically be displayed.
R3 x 5 free programmable switching outputs
R1 alarm relay, 1 programmable message relay, 1 relay for the cabinet fan
ROperating voltage: 110 ... 230VAC (+/-15%)
RMeasuring voltage: 3 x 30 ... 440 VAC (L-N) / 50...760 V (L-L)
RMeasuring current: 3 x 5A / 1A
RPre-programmed control series and control series editor
RIlluminated graphic display 128 x 64 dot, graphical menu navigation
R4-quadrant-operation
RMeasuring of capacitor current possible
RThree-phase display of various grid parameters ( U, I, F, Q, P, S Delta Q ... )
RSwitch over to large display possible
RDisplay up to 31st harmonic of voltage and current
RSimultaneous graphical display 1 period of voltage and current in Osci-mode
RMonitoring of temperature
RStorage of maximum grid parameters with time stamp
RManual/automatic operation
RProgramming of fixed steps or mascing of particular outputs possible
RControl possible as 3-phase, 1-phase or mixed-mode
RDisplay of different error messages
RError storage
RComplete 2nd parameter set programmable
R2 integrated separate interfaces
RIntegrated clock, several timers possible
RIntegrated help-function/plain text
RPanel-mounted instrument 144 x 144 x 60 mm
- 3 -

Prophi®15T-III
5
- 4 -
Section 2: INSTALLATION AND INSTRUCTIONS FOR USAGE
The controller is designed as panel mounting instrument in PFC-systems. This requires a
cut out of 138 x 138 mm according to DIN 43700 / IEC 61554. The controller has to be
inserted from the front and fixed with the clamps (included in delivery). The device may
only be installed by qualified personnel and may only be operated according the given
safety regulations. In addition the relevant legal and safety instructions have to be
obeyed.
The measuring input is designed for 1- and 3-phase grids.
The maximum measuring voltage is 440V~ (L-N) / 760V ~ (L-L).
The supply voltage is 110...230 V +/-15%.
Wiring connections must be suitable for the particular voltages. Input leads have to be
protected by over-current-protection devices. The supply voltage must be protected by a
fuse; it must be possible to switch off the supply voltage by a separator.
The device must not be operated without protective earth contactor connected!
Before connecting, it has to be checked that all connections are at zero potential; current
transformers have to be short circuited. Correct phasing of measuring voltage and
measuring current have to be checked. The measuring current circuits must be wired with
2
minimum 2.5 mm Cu.
Terminals may only be plugged when de-energized!
Attention!
The controller may only be operated when installed. The complete programming of all
application-specific parameters is done according chapter programming. Then the device
is set to automatic operation by pushing the operation mode button. The controller is now
ready for operation.
Operating the controller without following to these operating instructions may be harmful
and dangerous!
!
!
!

Prophi®15T-III
6
Rear view
Operating mode:
- Automatic
- Program.
- Manual oper.
- Service
- Expert Mode
- Osci - Mode
- Display Editor
ENTER/ OK
Confirmation
storage of
values
Increase
selected
parameter
HELP
opens
Help pages
Reduce
selected
parameter
Escape
previous
page/value
in the display
- 5 -
Front view
The controller is supplied for a standard operating voltage of 110...230VAC (+/-15%), a
measuring voltage of 30...440 V~ (L-N) resp. 50...760V~ (L-L), 50/60Hz, and a
measuring current of 5A or 1A (programmable). A voltage converter is required for
different operating voltages.
Caution!
Voltages which exceed the allowed voltage range can damage the
device !
!
Power factor controller
Type: Prophi 15T-III
Meas voltage: 50 - 760VAC 50/60Hz
Supply voltage:110 - 230VAC 50/60Hz
Ser.Nr.: 0815 / 2019
P1
P2
P3
1
6
11
2
7
12
3
8
13
4
9
14
5
10
15
Meas.current
k L1 l
Supply voltage
85...265V~
Measuring voltage
30 ... 440V L-N
Transistor output 11-15
Transistor output 6-10
Transistor output 1-5
Switching outputs:
Fan relay
Message relay
Alarm relay
Meas.current
k L2 l
Meas.current
k L3 l
Interface 1
Contact assignment 2nd terminal at bottom
Interface 2
External input
110...230V~
GND B A PE
L1 N L1 L2 L3 Monitoring
24VDC
The allocation of switching outputs 1 … 15 to
the capacitors complies to the selected
connection variant and the desired
CONTROL-MODE
(Programming/point 2)
Especially in ”Mixed Mode“ where some
outputs are used for single phase capacitors,
others for 3-phase-capacitors the proper
connection must be assured!
In the “HELP”-menu the controller directly
displays the actual correct allocation of
outputs (AUTO-MODE: Help-page).
For examples also see page 12.
H
H
e
e
l
l
p
p
E
E
S
S
C
C

Prophi®15T-III
7
Section 3: CONNECTION ALTERNATIVES MEASURING VOLTAGE
AND MEASURING CURRENT
According to the existing grid and the desired operating mode (CONTROL-MODE
Programming) the controller has to be connected accord. one of the following
alternatives. The separate auxiliary voltage (24 V DC) that is needed for the thyristor
switches has to be conducted to P1…P3 and to the connection “control 24V”. The
connection of PE is mandatory!
Alternative 1: measuring performed in each phase - 3 current transformers needed
Use: CONTROL-MODE: 1 - 4; 7-12; 15 (control modes see page 11)
Alternative 2: single-phase measuring via current transformer in L1 Values extrapolated (balance assumed).
Measuring complies with conventional measuring for switching of three-phase capacitors.
Use: CONTROL-MODE 5; 13; 14; 16
Alternative 3: single-phase measuring as alternative 2 , but with capacitor current measuring in the compensation
system for collection of real capacitor currents.
Use: CONTROL-MODE 6
Reserve
- 6 -
PE
N
L2 (S)
L3 (T)
L1 (R)
( L1) ( N )
( L1) ( N )
( L1) ( N )
L1 L2 L3 monitoring
24VDC
aux. voltage
24VDC
aux. voltage
24VDC
aux. voltage
24VDC
L1 L2 L3 monitoring
24VDC
L1 L2 L3 monitoring
24VDC
Supply voltage
110-230V~
Supply voltage
110-230V~
Supply voltage
110-230V~
Measuring voltage
to P1...P3
to P1...P3
to P1...P3
Measuring voltage
Measuring voltage
L3
L3
L3
Measuring current
L2
Measuring current
L2
Measuring current
L2
L1
L1
L1
L1 (R)
L2 (S)
L3 (T)
PE
N
L1 (R )
L2 (S )
L3 (T )
PE
N
L1 L2 L3 N
PFC-system
Load-
site
Load-
site

Prophi®15T-III
8
- 7 -
kK k K
lL l L
Feed 1 Feed 2
K L K L
Measurement via sum current converter
P.F.Controller
Current
measurement
k l
k l
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A / 5A
C.converter ratio is: 2000 /5A
Connection of current transformer / sum current transformer
When installing the current converter, care should be taken to ensure that the load
current flows through it. The outputs of the compensation network must be installed
behind the current converter (in the direction of current flow). If the controller is
connected up via sum-current converters, the overall conversion ratio is entered.
Caution!
The secondary clamps of the CT
have to be short circuited before
current leads are iterrupted !
!
High Voltage Application
The example shows the connection in HV-application.
The measuring current is taken off primary via X/1A transformer. Measuring voltage
produced via transformer 20000/100 V. In this case, the Prophi 15T-III has to be
programmed as follows:
4 I-CONVERTER sek: X / 1A
14 MEASUR.VOLTAGE: 100 V
15 V-CONVERTER: 20kV / 100 V
L1 (R) L1 (R)
L2 (S) L2 (S)
L3 (T) L3 (T)
N
Meas.current
Im (X/1A)
supply
voltage
Ub
Meas-
voltage
Um
PE
Meas.current Meas. voltage Um Supply voltage Ub
L1 L2 L3 L1 L2 L3 N L1 N
HIGH VOLTAGE LOW VOLTAGE
20 kV / 400 V
20000
100

Prophi®15T-III
9
Section 4: DISPLAY - FUNCTIONS
After the operating voltage has been switched on, the controller briefly indicates with
description and software-version before changing to automatic operation.
Actual values and symbols of the particular operation state are shown in the display.
In the automatic operation (standard) capacitor steps are automatically switched on or
off to reach the pre-set target cos-phi. This happens when the required reactive power is
higher than the value of the smallest capacitor step.
Example 1: Automatic operation
L1...L3: Individual compensation by single-phase capacitors
- 8 -
Number of switching outputs until end stop.
Here: 15 three-phase capacitors, end-stop: 15
Control direction is symbolized by a
compact arrow:
Connecting-in
Connecting-out
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (Discharge time)
is running before an impending
switching step
A double arrow symbolizes switching of
several branches
The sigma-sign indicates the three-
phase-value (mean-value) resp.
activated three-phase-capacitors
Alarm relay activated
(declines in case of error)
Message relay activated: “SUPPLY”
Message relay activated:“Undercurrent”
Message relay aktivated: “Harmonics”
FAN-relay: ON
The particular capacitor outputs are
permanently monitored. Inverse display
= capacitor out of range
Display of 2nd parameter-set
Supply display (i.e.generator operation)
nd
2 Target-cos phi activated by timer
nd
2 Target-cos phi activated by supply
S
A
U
H
F
2
T
é
é
Example 2: Automatic operation (Mixed Mode)
L1...L3: phase wise compensation by
single phase capacitors
S: Three-phase capacitors activated
Example 3: Automatic operation
Measuring in one phase
Controlling of 15 three-phase-capacitors
S
AUTO-MODE 1/2
cosj 0.869 IND
cosj 0.869 IND
cosj 0.869 IND
cosj 0.917 CAP
L1
L1
L2
L2
L3
L3
1 2 3 4
S
S
S
AUTO-MODE 1/3
AUTO-MODE 1/2
L1
L2
L3
1 2 3 4
123456789
10 11 12 13 14 15
control direction
(here: connected-in)
active capacitor
branches

Prophi®15T-III
10
Section 5: DISPLAY OF GRID PARAMETERS
Display of 3 selected grid parameters
In Auto-Mode, button é leads to display mode 1. Here 3 (free selectable) grid parameters
are displayed in large letters. The selection and storage of these values is done in the
Display- Editor.
Example: Display mode 1:
Desired values selected in the
Display Editor (see section 14 )
Display of particular grid parameters (from AUTO-MODE by pressing ENTER)
By repeated activation of the “ENTER”-button (in automatic operation) several grid
parameters can be displayed (s. table below):
Action Display Unit in% large display Bargraph 3-phase
possible possible
ENTER 1 LINE VOLTAGE V x x
ENTER 2 APPARENT CURRENT A x x x
ENTER 3 REACTIVE POWER kvar x x
ENTER 4 ACTIVE POWER kW x x
ENTER 5 APPARENT POWER kVA x x
ENTER 6 DIFF. kvar to target kvar x x
ENTER 7 TEMPERATURE °C / °F x
ENTER 8 3.-31. HARMONICS V/ I x x x
ENTER 9 HARMONICS THD-V/I x x x
ENTER 10 Comp.- power (only at real capacitor current measurement)
ENTER 11 TIME / DATE é / ê change the date format
ENTER 12 Software version
ENTER return to: 1
Buttons é / ê change the display format:
The values can be displayed in their unit, in % or as large display resp. bar chart.
Examples, see next page.
- 9 -
AUTO-MODE 2/2
14
137
140
kvar
kW
kVA
Q
P
S

Prophi®15T-III
11
=== DISPLAY ===
Examples of different displays:
VOLTAGE 3-phas. CURRENT: 3-phas. REACTIVE PWR 3-phas.
HARMONICS in % TEMPERATURE °C REACTIVE PWR in %
LARGE LETTERS
HARMONICS diagram THD V/I as bar diagram REACTIVE POWER
LARGE LETTERS
- 10 -
Repeated pressing of the "Operating Mode” key activates the various menus in sequence:
Automatic operation - Programming - Manual (manual operation)- Service - Expert
mode - OsciMode - DisplayEditor and back to Auto.
AUTO-MODE
to display operation to programming to manual operation to value buffer special functions to graphic. mode display-functions
PROGRAMMING
MANUAL-MODE
SERVICE EXPERT-MODE OSZI - MODE
DISPLAY-EDITOR
DISPLAY 7/9
8 HARMONICS [3.]
L1 V 0.4% I 0.5%
L2 V 1.4% I 0.8%
L3 V 1.4% I 0.7%
DISPLAY 3/4
7 TEMPERATURE
25 °C
DISPLAY 1/3
1 LINE VOLTAGE
L1-N 233 V
L2-N 233 V
L3-N 233 V
24VDC 24 V
DISPLAY 3/3
25
25
25
kvar
kvar
kvar
Q1
Q2
Q3
ANZEIGE 1/3
2 APPAR.CURRENT
L1 235 A
L2 133 A
L3 133 A
DISPLAY 1/2
3 REACTIVE POWER
L1 71 kvar
L2 23 kvar
L3 22 kvar
116 kvar
DISPLAY 2/3
3 REACTIVE POWER
L1 31 %
L2 10 %
L3 10 %
17 %
HARMONICS [V-1]
1.0%
0.5%
0%
3579
11 13 15 17 19 21 23 25 27 29 31
THD 1/2
20%
10%
0%
THD V 1 2 3 THD I 1 2 3
DISPLAY 1/3

Prophi®15T-III
12
Section 6: PROGRAM-MODE (manual programming)
Pressing the button “Operation Mode“ one time switches from automatic operation to the
program mode.
The upper part of the display always shows the parameter, the adjustable values are
shown in the lower part. Editable values are generally given in square brackets. Changes
of these values can be done by the buttons é / ê. By pressing the “ENTER-button” the
value is stored. Pressing the “ESC”-button allows to go one step back (without storing).
1 LANGUAGE
This selects the language of the operating menu
[GERMAN, ENGLISH, SPANISH, RUSSIAN, TURKISH]
2 CONTROL-MODE [1...16]
16 different controlling operation modes can be adjusted at the Prophi 15T-III
according the following table:
Mode Kind of measure- Number/type Connection of Operation mode
No. ment(number CT) of capacitors capacitors
see page 6
1 3-phase 3x 5 single phase L-N Stand-alone
2 3-phase max.3x4 1-phase L-N Stand-alone
+ Rest 3-phase 3-phase MIX - MODE
3 3-phase 3x 5 single phase L-L Stand-alone
4 3-phase 1x 15 threephase 3-phase Stand-alone
5 1-phase 1x 15 threephase 3-phase Stand-alone
6 1-phase 1x 15 threephase 3-phase Sytem current meas.
internal via L2 / L3
7 3-phase 3x 5 single phase L-N Hybrid mode
1x Prophi 12RS
8 3-phase 3x 5 single phase L-N Hybrid mode
2x Prophi 12RS
9 3-phase 3x 5 single phase L-L Hybrid mode
1x Prophi 12RS
10 3-phase 3x 5 single phase L-L Hybrid mode
2x Prophi 12RS
11 3-phase 1x 15 three phase 3-phase Hybrid mode
1x Prophi 12RS
12 3-phase 1x 15 three phase 3-phase Hybrid mode
2x Prophi 12RS
13 1-phase 1x 15 three phase 3-phase Hybrid mode
1x Prophi 12RS
14 1-phase 1x 15 three phase 3-phase Hybrid mode
2x Prophi 12RS
15 3-phase 1x 15 three phase 3-phase Coupling mode
16 1-phase 1x 15 three phase 3-phase Coupling mode
- 11 -
PROGRAM-MODE
1 LANGUAGE [1]
[ ENGLISH ]

Prophi®15T-III
13
!Allocation of switching outputs 1…15 to the capacitors according to the selected
connection variant and the desired CONTROL-MODE.
Especially in ”Mixed Mode“ where some outputs are used for single phase
capacitors, and others for 3-phase-capacitors the proper connection must be
assured!
In the HELP-function the controller directly displays the correct allocation of
outputs (AUTO-MODE: Help-page 7-9).
=== PROGRAM-MODE ===
CONTROL-MODE [1]:
3-phase measuring / max. 3x5 single phase capacitors L-N
(3 current transformers needed), values displayed and calculated per phase.
Connection of measuring current and measuring voltage (refer to page 6).
Controlling is done with max. 5 outputs per phase in case of switching of single-
phase capacitors L-N.
L1 (R)
L2 (S)
L3 (T)
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 1 4 15
Transistor-
output 1-5
Monitoring
24VDC
Transistor-
outp ut 6-1 0
Transistor-
output 11-15
PE
N
Example:
3x 5 Sin gle ph ase capacitor s (L-N)
Output assignment
C1.1 (C1 at L1 -N)
C1.2 (C1 at L2 -N)
C1.3 (C1 at L3 -N)
C2.1 (C2 at L1 -N)
C2.2 (C2 at L2 -N)
C2.3 (C2 at L3 -N)
C3.1 (C3 at L1 -N)
C4.1 (C4 at L1 -N)
C5.1 (C5 at L1 -N)
C3.2 (C3 at L2 -N)
C4.2 (C4 at L2 -N)
C5.2 (C5 at L2 -N)
C3.3 (C3 at L3 -N)
C4.3 (C4 at L3 -N)
C5.3 (C5 at L3 -N)
T1
(T2)
(T3)
(T4)
(T5)
T6
(T7)
(T8)
(T9)
(T10)
T11
(T12)
(T13)
(T14)
(T15)
C1.1
(C2.1)
(C3.1)
(C4.1)
(C5.1)
C1.2
(C2.2)
(C3.2)
(C4.2)
(C5.2)
C1.3
(C2.3)
(C3.3)
(C4.3)
(C5.3)
Aux. voltage
24VDC
e.g. TSM-LC-I
- 12 -

Prophi®15T-III
14
=== PROGRAM-MODE ===
CONTROL-MODE [2]: MIXED-MODE 3-phasige measuring
3 current transformers required. Values displayed and calculated per phase. Connection of
measuring current and measuring voltage see page 6/Var.1.
Controlling done with max. 4 outputs per phase for switching of single phase capacitors L-N.
The rest of the outputs (min. 3, max. 12) are used for switching of three-phase capacitors
to control the base load.
Partitioning into single-phase / three-phase capacitors is done at
Programming: 5 ENDSTOP!
The allocation of the switching outputs to the particular capacitors can be retrieved in AUTO-
MODE on HELP-pages 7…9.
CONTROL-MODE [3]:
3-phase measuring / max. 3x5 single-phase capacitores L-L
3 current transformers required. Values displayed and calculated per phase.
Controlling done with max. 5 outputs per phase, switching of single phase capacitors L-L
L1 (R)
L2 (S)
L3 (T)
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 1 4 15
Transistor-
output 1-5
Monitoring
24VDC
Transistor-
outp ut 6-1 0
Transistor-
output 11-15
PE
N
T1
(T2)
(T3)
(T4)
T6
(T7)
(T8)
(T9)
T11
(T12)
(T13)
(T14)
C1.1
(C2.1)
(C3.1)
(C4.1)
C1.2
(C2.2)
(C3.2)
(C4.2)
C1.3
(C2.3)
(C3.3)
(C4.3)
Aux. voltage
24VDC
C1.1 (C1 at L1 -N)
C1.2 (C1 at L2 -N)
C1.3 (C1 at L3 -N)
C2.1 (C2 at L1 -N)
C2.2 (C2 at L2 -N)
C2.3 (C2 at L3 -N)
C3.1 (C3 at L1 -N)
C4.1 (C4 at L1 -N)
C3.2 (C3 at L2 -N)
C4.2 (C4 at L2 -N)
C3.3 (C3 at L3 -N)
C4.3 (C4 at L3 -N)
C1S (C 1 3-ph as.)
C2S (C 2 3-ph as.)
C3S (C 3 3-ph as.)
3 x Thr ee pha se steps
4 x3 Single ph ase st eps
T5
(T10)
(T15)
C1S
( C2S )
( C3S )
Output assignment
e.g. TSM-LC-I TSM-LC-N
L1 (R)
L2 (S)
L3 (T)
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 1 4 15
Transistor-
output 1-5
Monitoring
24VDC
Transistor-
outp ut 6-1 0
Transistor-
output 11-15
PE
N
Output assignment
C1.1 (C1 at L1-L2)
C1.2 (C1 at L2-L3)
C1.3 (C1 at L3-L1)
C2.1 (C2 at L1-L2)
C2.2 (C2 at L2-L3)
C2.3 (C2 at L3-L1)
C3.1 (C3 at L1-L2)
C4.1 (C4 at L1-L2)
C5.1 (C5 at L1-L2)
C3.2 (C3 at L2-L3)
C4.2 (C4 at L2 -L3)
C5.2 (C5 at L2 -L3)
C3.3 (C3 at L3-L1)
C4.3 (C4 at L3-L1)
C5.3 (C5 at L3-L1)
T1
(T2)
(T3)
(T4)
(T5)
T6
(T7)
(T8)
(T9)
(T10)
T11
(T12)
(T13)
(T14)
(T15)
C1.1
(C2.1)
(C3.1)
(C4.1)
(C5.1)
C1.2
(C2.2)
(C3.2)
(C4.2)
(C5.2)
C1.3
(C2.3)
(C3.3)
(C4.3)
(C5.3)
Aux. voltage
24VDC
e.g. TSM-LC-I

Prophi®15T-III
15
=== PROGRAMM-MODE ===
CONTROL-MODE [4]: 3-phase measuring / max. 15 three-phase capacitors
CONTROL-MODE [5]: 1-phase measuring / max. 15 three-phase capacitors
Connection of current and voltage compare page 6/ Var.1 resp. Var.2
Controlling of 15 outputs
CONTROL-MODE [6]: 1-phase measuring / max. 15 three-phase capacitors
with capacitor current measurement
According variant 5, but the free current inputs (L2 or L3) are used for capacitor current
measurement for real monitoring of capacitors.
CONTROL-MODE 7 - 14: HYBRID-MODE
The connection of the outputs is done according the related switching diagrams MODE 1-4. In
Hybrid-Mode the Prophi 15T-III is connected with one or two controllers Prophi 12RS via the
system interface (Interface2). In this case the Prophi 15T-III takes over the dynamic part and
the Prophi 12RS takes over the slowly changing loads (s. application page 29).
CONTROL-MODE 15 - 16: COUPLING MODE
The coupling mode is used to couple 2 independent dynamic compensations systems which
are connected to each other via a coupling switch. The signal of the coupling switch is fed to
the master controller (s. application page 28).
- 14 -
L1 (R)
L2 (S)
L3 (T)
P1 1 2 3 4 5 P2 6 7 8 9 10 P3 11 12 13 1 4 15
Transistor-
output 1-5
Monitoring
24VDC
Transistor-
outp ut 6-1 0
Transistor-
output 11-15
PE
N
Aux. voltage
24VDC
C1S 3-phas .
C6S 3-phas .
C11S 3-phas.
C2S 3-phas .
C7S 3-phas .
C12S 3-phas.
C3S 3-phas .
C8S 3-phas .
C13S 3-phas.
C4S 3-phas .
C9S 3-phas .
C14S 3-phas.
C5S 3-phas .
C10S 3-phas.
C15S 3-phas.
15 x three pha se steps
T3 T2 T1
C15S C2S ...... .. C1S
Output assignment
e.g. TSM-LC-N

Prophi®15T-III
16
=== PROGRAMM-MODE ===
3 I-CONVERTER PRIM [1000 ] A / X ( 5 ... 13000) A
Selects the primary current of the current converter.
Sequential adjustment of L1...L3.
via the é / ê keys. Save and continue with ENTER
4 I-CONVERTER SEC 1000 A /[ 5 ]A ( 1 / 5 A )
This sets the secondary current of the current converter.
Selection via é / ê. Save and continue with ENTER
5 END STOPP
Programming of the maximum number of active
capacitor branches.
Depending on the selected operation mode the
maximum number of connected capacitors at the output
groups L1…L3 and (if available) for the output groups S
(three-phase capacitors) are set.
The visible symbols of the capacitors correspond to the
connected outputs.
Input via é / ê. Save and continue with ENTER
6 CONTROL SERIES [1] ( 1...20 + ED )
The ratio of the capacitor branch powers determines the
control series, the power of the first capacitor always
being assigned the value 1.
Selection of desired control series consecutively for
L1…L3 and for S (three-phase outputs).
If the required control series should not be present, the
user may define a special one in control series “ED” ( see
Annex 1: Control-series editor )
7 CONTROL PRINCIPLE
The control preference may be selected here:
SEQUENTIAL connection
LOOP connection
INTELLIGENT loop connection (default setting)
COMBINED CHOKE
See Section 13 for an explanation of the control modes.
Selection with é / ê keys.
Save and continue with ENTER
8 POWER 1st STAGE [0.01 ... 255.99] / [10...2550] kvar
To determine the controller's response sensitivity, the
dimensions of the smallest capacitor (stage 1) must be
known. They are entered in two steps in kvar. The
integral kvar values (before the comma) are initially
selected via the é / ê keys and saved with ENTER.
The positions after the comma are then selected, again
via the é / ê keys.
If the capacitor value is below the response sensitivity, a
warning will occur ( indication of “!”
in the display )
- 15 -
PROGRAM-MODE
7 CONTR.PRINC. 3]
[ INTELLIGENT ]
PROGRAM-MODE
3 I-CONVERTER PRIM
[ 1000]A / 5 A
1000]A / 5 A
1000]A / 5 A
L1
L2
L3
PROGRAM-MODE
8 POWER 1.STAGE
[ 25].00 kvar
25 .00 kvar
25 .00 kvar
L1-N
L2-N
L3-N
PROGRAM-MODE
6 CONT.SERIES L1-N
12333
12333
12333
[ 3]
3
3
L1-N
L2-N
L3-N
1 2 3 4 5
PROGRAM-MODE
5 END STOP L1-N
[ 5]
5
5
L1-N
L2-N
L3-N
1 2 3 4 5

Prophi®15T-III
17
- 16 -
=== PROGRAM-MODE ===
9 TARGET COS PHI [ 0.98 ind ] ( 0.3 ind ... 0.3 cap )
By setting the target cos phi, the power factor to be
attained via the PF correction is defined.
Save and continue with ENTER.
10 TARGET 2nd cosPhi [ NO ] ( 1...3 )
1: NO ( no 2nd target cosPhi,
continue with 14 )
2: Timer ( 2nd cos-phi - activated by timer,
scheduler with 12,13 )
3: Energy supply (2nd target cos-phi - activated by
energy-supply)
[ 0.9 IND ] (0.3 ind ... 0.3 cap )
Set point for the 2nd target cosPhi
( only available if selected under 10 )
[ HH:MM:SS ]
Switch-on time of the timer for the 2nd target-cos phi
( only available if selected under 10 )
[ HH:MM:SS ]
Switch-off time of the timer for the 2nd target-cos phi
( only available if selected under 10 )
14 MEASURING VOLTAGE L-L [400]V ( 50...760) V
Programming of measuring voltage.
The values programmed here always refer to the
voltage at the clamps of the controller !
Selection via é / ê. Save / continue with ENTER
15 V-CONVERTER [ NO ] (410V - 79kV / 400V )
When a measuring-voltage converter (e.g. for HV-
measurement) is used, its conversion ratio is to be
programmed here.
Selection via é / ê. Save / continue with ENTER
16 FREQUENCY [50] Hz (50 / 60Hz)
Input of the grid frequency of the measuring voltage
(needed for measuring system)
17 CONNECTING TIME: [ 1000 ] ms (50...1000ms)
The time between connecting the capacitors to increase
the momentary network capacitance. It should be noted
that in practical operation the real connection time is
affected by the discharge time (locking time).
Selection via é / ê. Save / continue with ENTER
11 TARGET 2nd cosPhi
12 SWITCH ON TIME
j2
13 SWITCH OFF TIME
j2
PROGRAM-MODE
12 SWITCH ON TIME j2
ON [16]: 00 MO-FR
OFF 07 : 00 MO-FR
PROGRAM-MODE
15 V-CONVERTER
PRIMARY SECONDARY
[20000V] / 100V
PROGRAM-MODE
10 TARGET 2nd cos j
[ TIMER ]
PROGRAM-MODE
9 TARGET cos j
[ 0.98 IND]

Prophi®15T-III
18
=== PROGRAM-MODE ===
18 DISCONNECT TIME: [ 1000 ] ms ( 50...1000)ms
The time between disconnecting the capacitors to
reduce the momentary network capacitance.
Selection via é / ê. Save / continue with ENTER
19 DISCHARGE TIME: [ 1000 ] ms ( 50...1000)ms
This is the time for which an individual output is blocked
between disconnecting and connecting. It depends on
the discharge device of the capacitor.
Selection with buttons é / ê. Save /Continue with
ENTER
20 ALARM TEMPERATURE [ 55 ] °C ( 20...80 )°C
The alarm temperature programmed here is the
temperature at which a stepwise disconnection of the
capacitors is performed. After 10 min. the standard
alarm relay of the controller will respond. At the same
time, the display shows the cause of the alarm (over
temperature).
When the temperature drops again, the required
branches are automatically re-connected in steps.
Selection with é / ê. Save / Continue with ENTER
21 FAN TEMPERATURE [ 30 ] °C (ON/OFF/15...70°C)
Threshold for the fan relay for control of a cabinet fan.
22 MESSAGE RELAY [Supply ] ( 1...3 )
The message relay can be programmed for one of the
following options as required:
1 - OFF
2 - Supply: Message when active power is supplied.
3- Under current:
Message when the measuring current is not met. Signal
is generated when the current value drops below the
response sensitivity of the controller.
4 - Harmonics:
Message when the limiting value of the total harmonic
distortion factor (THD-V) is exceeded. This value can be
parameterized under ”38 Harmonics” (in %).
5 - ERROR - System current measuring
6 - ERROR - Com1 (interface error)
7 - ERROR - Com2 (interface error)
8 - ERROR - Com1/2 (interface error)
- 17 -
S
U
H
E
E
Display:
Display:
Display:
Display:
Display:
PROGRAM-MODE
19 DISCHARGE TIME
C-ON 200 ms
C-OFF 200 ms
C-DIS [ 200]ms
PROGRAM-MODE
20 ALARM TEMPERATURE
[ 55°C]
PROGRAM-MODE
22 MESSAGE RELAY [2]
[ HARMONICS ]

Prophi®15T-III
19
=== PROGRAM-MODE ===
23 EXTERNAL INPUT [ NO ] ( 1...4 )
Setting of the desired action upon applying a control
voltage of 110...230V~ at the external input.
1 - NO (no action)
2 - 2nd parameter set (switchover to 2nd parameter set)
This selection simultaneously activates the following
points 24…37 for programming of the values of the
2nd parameter set.
3 - External error (Display of an error message)
4 - Coupling operation parallel
(Selection of coupling operation via 2 CONTROL-MODE)
Programming of 2nd parameter set
(only active if 23 EXTERNAL INPUT is set to 2nd parameter set)
As a standard, the values of the 2nd parameter set equal the
values of the normal parameter set. Possible applications are for
example: changing of target cos-phi, switch-over of current
transformer or switch-over the switching times.
By triggering a 110...230V~ signal at the external input, the
2nd parameter set is activated with following values:
The programming of the 2nd parameter set is performed
equivalent to the programming of the standard parameters
(3-11; 17-19)
38 HARMONICS [ 7 ]% (0,5...25,5)%
Threshold value THD-V (in%). In case this value is exceeded a
message will be displayed. THD-V ist the ratio of the geometric
sum of unequal harmonics to the 1st harmonic. In any case, a
warning will be displayed. Warning via message relay will only be
executed if selected in 22.
24. I-converter prim
25. I-converter sec
26. End stop
27. Control serie
28. Control principle
29. Power 1st stage
30. Target cos-Phi (2nd parameter set) nominal value
31. 2nd target cos-Phi (2nd parameter set)NO/supply/Timer
32. 2nd target cos-Phi (2nd parameter set) nominal value
33. Switch on time target cos-Phi-2
34. Switch off time target cos-Phi-2
35. Connecting time
36. Disconnecting time
37. Discharge time
- 18 -
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
PROGRAM-MODE
38 HARMONICS
THD-V [ 7.0]%
2
PROGRAM-MODE
30 TARGET cos j
[ 0.98 IND]
PROGRAM-MODE
23 EXT. INPUT [2]
[ 2.PARAMETER SET]
2
2
2
PROGRAM-MODE
24 I-CONVERTER PRIM
[ 1000]A / 5 A
1000]A / 5 A
1000]A / 5 A
L1
L2
L3

Prophi®15T-III
20
=== PROGRAM-MODE ===
39 CLOCK [ HH:MM ], DATE [DD.MM.YY]
Set system-time and date
(Due to an internal battery the time will be kept even in
case of power loss)
Selection with é / ê. Save/continue with ENTER
40 CONTRAST [ 6 ] ( 0...10)
Adjustment of display contrast for best readability
Selection with é / ê. Save/continue with ENTER
41 BASIC SETTINGS [ NO ] (YES/NO)
When selecting YES and confirmated with ENTER, all
parameters are set back to the basic settings of the
panel builder (optimum values for the system if
the controller has been delivered together with the PFC-
system). If the controller has been delivered ex works,
this point corresponds to the default settings.
ATTENTION: All user settings get lost !
Section 6.1: PROGRAMMING LOCK
As a protection against unauthorized changes of the system
parameters, the device is equipped with a programming lock. This
can be activated in the EXPERT MODE. When the lock is active, all
parameters can be checked but not changed.
Alternatives:
Lock active / Not active / Automatic activation after 24 h
- 19 -
PROGRAM-MODE
39 CLOCK
[ 15]: 27
MONDAY
05.03.2019
PROGRAM-MODE
41 BASIC SETTINGS
[NO ]
EXPERT-MODE
7 OPERATING LOCK
[NO ]
Section 7: HELP-Functions / actual output assignment
The Prophi 15T-III features a context related help function.
For each menu item one or more help pages are available which can be accessed directly
with the HELP-button. Scrolling is done with "UP/DOWN" buttons, back retrace with
ESCape.
In automatic operation (==AUTO-MODE==) 9 help pages are available. The first pages
explain the general meaning of used symbols.
On the help pages 7…9 the actual assignment of the internal transistor outputs
to the phases and to the capacitors are shown directly.
This table depends on the CONTROL-MODE that is set and will change
automatically.
The assignment shown here is not trivial, especially in CONTROL-MODE 2
(MIXED MODE) and must be obeyed without exeption!
s. example next page
!
Table of contents
Other janitza Controllers manuals
Popular Controllers manuals by other brands

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-F Series user manual

EMKO
EMKO esm-4450 instruction manual

Bticino
Bticino AXOLUTE HD4657M3 quick start guide

Rockwell Automation
Rockwell Automation External Dynamic Brake Kit installation instructions

Omega
Omega DPF700 quick start

Teufel
Teufel Raumfeld Base Setup guide