janitza Prophi 12R User manual

Doc. no. 2.020.009.1.a 4.0.E - 01/2020
Janitza electronics GmbH
Vor dem Polstück 6
35633 Lahnau / Germany
Telefonischer Support: +49 6441 9642-22
E-Mail: [email protected]
www.janitza.com
www.janitza.de
Power Factor Controller
Prophi®12R / 12RS
Manual
Manual
Version 4.0 - E
SupplyVoltage: 110-440V
Version 4.0 E, 11/2019
cos 0.987 IND
1 2 3 4 5 6 7 8 9 10 11 12
j
AUTO MODE
------------------
Power Factor Controller
Prophi12R/ Prophi 12RS

Prophi®12R / 12 RS
2
!
CAUTIONS:
1. High voltage !
2. The device may only be used indoor !
3. Make sure that the discharge time set in controller
matches capacitor discharge time !
UNDERCOMPENSATED
------------------
Q-Diff= 82kvar
1 2 3 4 5 6 7 8 9
HARMONICS [V]
23456789
10 11 12 13 14 15 16 17
2.0%
1.0%
0%
AUTO-MODE
ERROR MESSAGE
DISPLAY-MODE
BARGRAPH-MODE
10 11 12 A M
AUTO MODE
------------------
cos 0.987 IND
1 2 3 4 5 6 7 8 9 10 11 12 A M
j
------------------
phi
cos
Q
dif
0.960
19.5
kvar
IND
1 2 3 4 5 6 7 8 9
10 11 12 A M
------------------

Prophi®12R / 12 RS
3
CONTENTS
Section 1 General / type series and accessories 3
Section 2 Installation of the controller / connection diagram 5
2.1 Current measurement 6
2.2 Programming of phase-correction
2.3 Error messages: Alarm- / Message relay 7
Section 3 Operating modes 7
Section 4 Automatic operation / display functions 8
Section 5 Programming
5.1 Automatic initialization 9
5.2 Manual programming 10
5.3 Programming lock 13
Section 6 Manual operation 1&2 / Programming of fixed stages 14
Section 7 Service menu, Test run 15
Section 8 Expert mode 16
8.1 Expert mode 1
8.2 Expert mode 2 18
Section 9 Control principle 19
Section 10 Display editor 20
Section 11 Initial operation 20
Section 12 Maintenance and warranty 20
Section 13 Interface 21
Annex: Annex 1 Troubleshouting 23
Annex 2 Technical data 24
Annex 3 Table of control series 25
Description of control-series editor
Annex 4 Default settings 26
Application Mixed dynamic compensation 28
Cascading of controllers
Application Real current measurement 29
Alarm and status notifications 30
Handling-diagram / short reference 31
Application Coupling of compensation systems 27
- 2 -

Prophi®12R / 12 RS
4
Section1 General
The power factor controller Prophi 12 (single phase) enlarges the product range of power
factor control devices by a useful combination of the well known features with the
advantages of a better visualization.
The big graphic display enables a user-friendly programming and gives further benefits
such as larger display in the Display-mode and the display of various parameters in
bargraph-mode.
With the additional “ESCAPE”-button a backward navigation in all menus is possible.
The “HELP”-button allows an interactive help in the particular menu item
(German/English).
The controller is characterized by its user friendly operating interface via menu driven
plain text display. The display of several grid parameters, the storage of different values
as well as the possibility of test run allow a simple error analysis and system monitoring.
If required, an automatic initialization is possible which reduces the start-up operation to
a minimum.
R 12 respectively 13 switching outputs
RExtended supply-voltage range 110...440V
R20 pre-programmed control series with self optimized intelligent control behavior
RControl series editor for individual control series
ROperation and display completely menu-driven
RIlluminated graphic display 128 x 64 dots
R4 quadrant operation
RAutomatic initialization possible
RDisplay of several grid parameters also in large letters
RDisplay of harmonics of voltage and current, also as bar diagram
RDisplay and monitoring of temperature
RMonitoring of the particular capacitor output
RStorage of maximum values of grid parameters as well as switching operations
and switch-in times of particular capacitor contactors
RManual/automatic operation
RProgramming of fixed steps or skipping of single outputs possible
RZero voltage switch off
RError display of different states and alarm output (relay)
RError storage
RTest run of the system with error analysis
RPanel-mounted instrument 144 x 144 x 53 mm
RFirmware update possible
Version with interface only:
Radditional external input (function programmable), e.g. for 2nd parameter set
Radditional freely programmable alarm relay, e.g. for fan, status notification
Rserial interface RS485, for controller coupling, integration into networks
Rvisualization, programming and data processing via PC by enclosed software
RParameterization of the controller via PC
RUsage as system interface
RUsage with accessory MMI6000/MMI7000 for real current or remote measuring
RConnection of system accessory (e.g. datalogger)
- 3 -

Prophi®12R / 12 RS
5
The controller is supplied as standard for an operating voltage of 110...440 VAC (+-10%),
a measuring voltage of 30...440 V~ (L-N) resp. 50...760V~(L-L) and a measuring current
of 5A or 1A. A voltage converter is required for different operating voltages.
Caution!
Voltages which exceed the specified voltage range can damage the
device !
- 4 -
!
Operating mode:
- Automatic
- Program.
- Manual oper.
- Service
- Expert Mode
- Osci - Mode
- Display Editor
ENTER/ OK
Confirmation
storage of
values
Increase
selected
parameter
HELP
opens
Help pages
Reduce
selected
parameter
Escape
previous
page/value
in the display
Front view
Rear view
H
H
E
E
L
L
P
P
E
E
S
S
C
C
Alarm relay
Power Factor Controller
1 2
EXT. IN-/OUTPUT
ON INTERFACE RS 485
SERVICE
Gnd B A PE
ext. Input
110...230V
message-
relay
terminating-
resistor
capacitor contactors 1 - 6 capacitor contactors 7 - 12
P1 P21 72 83 94 105 116 12
MADE IN GERMANY
RJ45
Art.no.:
Ser.no.:
50 - 760 V~ (L-L)
Meas.voltage: 30 - 440 V~ (L-N)
Supply volt.: 110...440VAC 50/60Hz
L N L1 N k l
(L3) (L2)
a b
supply volt. meas.voltage meas.current

Prophi®12R / 12 RS
6
Section 2 Installation and connection of the controller
The device is designed to be incorporated into the front panel of a PFC-cabinet. It requires
a switchboard section of 138 x 138 mm to DIN 43700/ IEC 61554. The controller is
inserted from the front and is attached by means of the appended clamps. The
controller may be inserted only by qualified technicians and must be operated in
accordance with the specified safety regulations.
Before the device is connected up, all leads and cables must be checked to ensure that no
current is flowing through them and the current converter must be short-circuited. Care
should be taken to ensure that the measuring voltage and current are in the correct phase
2
position. The measuring-current circuit must be wired with copper leads of 2.5mm . The
connection should be set up as shown below. The specified safety regulations must be
observed.
The measuring voltage may lie in the range from 30...440 V~ (L-N) resp. 50..760V~ (L-L)
(programming of phase correction needed)
The operating voltage is 110...440 VAC +/- 10%.
The coil voltage for the capacitor contactors and the measuring voltage
must be drawn from the same phase conductor, as only the measuring
voltage is monitored. (Protection against direct reconnection of the
capacitor contactors in the event of momentary single-phase power
failure)
Connection plan
- 5 -
L1 ( R)
L2 ( S)
L3 ( T)
N
meas.current
Im ( 5A/1A)
1. capacitor
branc
h
supply
voltage
Vb
meas.
voltage
Vm k l
P1 P 2
1 2 3 4 5 6 7 8 9 10 11 12
capacitor
co ntactors 1-6
alarm
relay
ca pacitor
co ntactor s 7-12
power factor
controller
T 6,3 A
T 2A
T 2A
PE
K1
a b
Ub Um Im
(L) (N) L1 N k l
(L3) (L2)
Power feed Load side
!

Prophi®12R / 12 RS
7
2.1 Current measurement
When installing the current converter, care should be taken to ensure that the load
current and capacitor-current flows through it. The outputs of the compensation network
must be installed behind the current converter (in the direction of current flow). If the
device is connected up via sum-current converters, the overall conversion ratio is
entered.
2.2 Programming of phase-correction - e.g. connection directly L-L (400V)
Adjustment of phase-correction between voltage and current in the meas. system is done
in expert mode 1
Example :
Meas.current: L1
Meas. voltage: L3-L2
Phase U/I [ 90°]
- 6 -
L1 ( R)
L2 ( S)
L3 ( T)
N
Me as.cu rrent
su pply-
voltage
Vb
me as. -
vo ltage
L2 -L3 k l
T 2A
T 2A
PE
Ub Um Im
(L) (N) L3 L2 k l
using meas. current meas. voltage phase-angle
Preset: L1 L1 - N 0°
L1 L1 - L2 30°
L1 (k<->l) L2 - N 60°
L1 L3 - L2 90°
L1 L3 - N 120°
L1 L3 - L1 150°
L1 (k<->l) L1 - N 180°
L1 (k<->l) L1 - L2 210°
L1 L2 - N 240°
L1 L2 - L3 270°
L1 (k<->l) L3 - N 300°
L1 (k<->l) L3 - L1 330°
kK k K
lL l L
Feed 1 Feed 2
K L K L
Measurement via sum current converter
Current
measurement
k l
k l
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A/5A
C.converter ratio is: 2000/5A

Prophi®12R / 12 RS
8
Display-Mode Harmonics as bar-diagram
Active capacitor
branches
Control direction
(here connected-in)
Supply display
(for 4-quadrant
operation)
The control direction is symbolized
by a closed arrow
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (discharge
time) is running before an impending
switching step
A double arrow symbolizes fast
switching of several branches
Connecting-in
Connecting-out
By pressing the cursor buttons,
the display of capacitor stages can be changed:
AUTO MODE
------------------
cos 0.987 IND
1 2 3 4 5 6 7 8 9 10 11 12
j
------------------
------------------
U HARMONICS [V]
I
Q
23456789
10 11 12 13 14 15 16 17
223.0 V
268 A
107
kvar
2.0%
1.0%
0%
By activating the ENTER-button the selected display can be stored as standard main display.
2.3 Error-Messages: Alarmrelay / Message-relay*
The PROPHI 12R is equipped with an alarm relay. Version /RS features an additional message relay.
The functions may be programmed as follows:
Alarm relay: Setting under Message relay: Setting under Remark
Programming: 14 Alarm relay INTERFACE: 1 MESSAGE RELAY
0 13th step Alarm relay=13.th step
1 OFF OFF
2 ERROR ERROR ERROR-summary report
3 ERROR inverse ERROR inverse List of errors see page 12
4 FAN FAN ERROR:relay closed in case of error
5 Supply Supply ERROR inverse (factory setting):
6 Undercurrent Undercurrent contact open in case of error
7 Harmonics Harmonics
8 Overcompensated Overcompensated
9 Undercompensated Undercompensated
10 Warning switch. oper. Warning switch. oper.
11 Modbus-Error Modbus-Error
12 \ Modbus-Error \ Modbus-Error
13 MMI-Error MMI-Error
14 C-defect C-defect
15 Fixed step OUT ext. input triggers fixed step
Adjustment and masking of all ERRORS is possible in the ExpertMode 2. The adjustment is valid for
both relays.
Section 3: Operating modes
When the operating voltage is switched on, the device briefly displays its designation and software
version, then changes to its normal operating status (automatic operation).
further messages
compare last cover
page !

Prophi®12R / 12 RS
9
Section 4 Automatic operation - display of network parameter
The device is set to automatic operation as standard (not AUTO-INIT). Capacitor stages
are then automatically connected in or out in order to reach the target power factor. This
happens if the required reactive power is approx. 1/3 higher than the value of the
smallest capacitor step.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER” key:
Action Display
ENTER 1 LINE VOLTAGE in V /%
ENTER 2 APPARENT CURRENT in A /%
ENTER 3 REACTIVE POWER in kvar /%
ENTER 4 ACTIVE POWER in kW /%
ENTER 5 APPARENT POWER in kVA /%
ENTER 6 DIFF. kVAR TO TARGET COS
ENTER 7 FREQUENCY in Hz /min / max
ENTER 8 TEMPERATURE in °C / °F
ENTER 9 HARMONICS V / %, I / %
Selection via arrow-keys
ENTER 10 HARMONICS THD-V/%, THD-I/%
11 Compensation power in kvar
ENTER 12 ENERGY
(kWh, kvarh, consumption, delivery)
reset in: service / max.value reset
ENTER Software version
ENTER Return to: 1
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 120 seconds, the display automatically returns to the operating status!
Under “13 Date-Time” the date format 12h/24h setting can be changed by the arrow
buttons (only version /RS).
ENTER
ENTER 13 DATE - TIME
Repeated pressing of the "Operating Mode” key takes the user to the various menus:
- 8 -
Auto operation Programming
Expert Mode 2
Manual operat.
Display-Editor back to 1
Service
Expert Mode 1
AUTO-MODE
------------------
AUTO-MODE
------------------
3 REACTIVE POWER
118 kvar
10 HARMONICS THD rel.
V 1.7% I 0.8%
INTERFACE

Prophi®12R / 12 RS
10
5.1. Automatic initialization
available only, if in ExpertMode 2: „2 Auto-Init = YES“
With the automatic initialization the PROPHI 12 will automatically recognize the
parameters of the PFC-system. It also serves as plausibility check and storage of these
parameters - the user only has to make very little or even no adjustments.
Start of the initialization process is done from the menu point “PROGRAMMING” by
pressing the button “ ”
AUTO-INIT [YES] to be confirmed with pressing the ENTER button.
Now either the values of the current transformer OR the value of the smallest step of the
system have to be keyed in. The input of one of these values is absolutely mandatory.
After input (confirm with ENTER) the automatic test run of the controller is executed.
é
3 test-runs will be performed during which all stages are being switched on and off. All
necessary parameters are collected, evaluated and stored. Under certain circumstances
3 additional test-runs may be required for a proper initialization.
After successful finalization of AUTO-INIT the device will switch to normal operation.
In case of recognition of any discrepancies (plausibility) or of inaccurate connection, the
detected error will be displayed in plain text after finalization of AUTO-INIT and can be
eliminated. (see possible error messages at the end of the manual). AUTO-INIT may be
repeated then.
- 9 -
AUTO-INIT
------------------ AUTO-INIT
------------------ AUTO-INIT
------------------
1 CURRENT TRANSF.
[ UNKNOWN ]
4 POWER 1.STAGE
[25].00 kvar
START TEST
E
E
S
S
C
C
Section 5: Programming
Pressing the key once takes the user into the PROGRAMMING mode.
[ ].
The values are changed by pressing the keys:
Subsequent pressing of the key stores the value and takes the user to the next
parameter.
“ESCAPE” allows return to previous menu item.
To quit programming mode in any step, press the key:
The display always shows the parameter and the set value. Values that can be edited are
generally put into square brackets

Prophi®12R / 12 RS
11
5.2. Manual programming (program menu)
0 LANGUAGE: This selects the language of the operating menu
(German, English, Spanish, Portuguese, French,RU,Cz,NL,PL,TR, IT)
1 I-CONVERTER PRIM: [ 5...13000] A
This selects the primary current of the current converter. Adjustment is
via the é / ê keys. Save and continue with ENTER
2 I-CONVERTER SEC: [ 5 or 1] A
This sets the secondary current of the current converter
Selection via é / ê. Save and continue with ENTER
3 END STOPP: [ 12/13 resp.] switching to 13. stage in item 14
By setting the end stopp, the number of active capacitor branches is
matched to the respective capacitor bank. This is done via the é / ê
keys. The visible symbols of the capacitors correspond to the connected
outputs. Preset = 12
Save and continue with ENTER
4 CONTROL SERIES: [ 1...20 + E ]
The ratio of the capacitor branch power determines the control series,
the power of the first capacitor always being assigned the value 1. The
control series required for the compensation network is again selected
via the é/ê keys. If the required control series should exceptionally not
be present (Annex 3), the user may define a special one (control series
"E”).More on this point in the control-series editor in Annex 3.
5 CONTROL PRINCIPLE: The control preference may be selected here:
SEQUENTIAL connection
LOOP connection
INTELLIGENT loop connection (default setting)
COMBINED CHOKE
See Section 9 for an explanation of the various control modes.
Selection with é / ê keys. Save and continue with ENTER
6 POWER 1. STAGE: [ 0.01 ... 255.99 ] kvar
To determine the controller's response sensitivity, the dimensions of
the network's smallest capacitor (stage 1) must be known. They are
entered in two steps in kvar. The integral kvar values (before the
comma) are initially selected via the é / ê keys and saved with
ENTER. The positions after the comma are then selected, again via the
é / ê keys. If the response sensitivity is being undercut, a warning will
occur ( indication of “!” in the display )
Save and continue with ENTER
7 TARGET COS PHI: [ 0.1 ind ... 0.1 cap ] or TAN PHI [9.0 ind ... 9.0cap]
By setting the target cos phi, the power factor to be attained via the PF
correction is defined. It is also set via the é / ê keys.
Switch-over
NEW: In ExpertMode /item28 its possible to program an OFFSET-value.
So each prim. current can be select!
COS/TAN PHI in the ExpertMode 1: 21 DISPLAY
- 10 -

Prophi®12R / 12 RS
12
- 11 -
8 MEASURING VOLTAGE [ 30 ... 760]V~
Programming the measuring voltage of the system.
The values programmed here always refer to the voltage at the clamps of the
device !
The voltage is selected via the é /ê keys. Save and continue with ENTER.
9 V - CONVERTER RATIO [ NO / 230V ... 380kV ]
When a measuring-voltage converter (e.g. for HV-measurement) is used, its
conversion ratio should be programmed here.
(Input of prim.voltage is here, sec. voltage is automatically from item 8)
Selection via the é /ê keys. Save and continue with ENTER.
10 CONNECTING TIME
This refers to the time between connecting the capacitors to increase the
momentary network capacitance. It should be noted that in practical operation the
real connection time is affected by the discharge time (locking time).
Setting range: 1 sec. ... 137 min. (long time for HV- networks)
Default setting: 40 sec.
Selection is performed via the é /ê keys. Continue with ENTER
11 DISCONNECTING TIME
This refers to the time between disconnecting the capacitors to reduce the
momentary network capacitance.
Setting range: 1 sec. ... 137 min. (long time for HV- networks)
Default setting: 40 sec.
Selection is performed via the é /ê keys. Continue with ENTER
12 DISCHARGE TIME
This is the time for which an individual output is blocked between connecting and
disconnecting. This blocking time has priority over connecting and disconnecting
times. It depends on the capacitor discharge rating and thus is specified by the
compensation network. The discharge time of a conventional network without
additional fast-discharge resistors or chokes should be set to no less than 40
seconds. For setting of a second discharge time compare 'Expert Mode1' point 12
Setting range: 1 sec ...137 min. Default setting: 60 sec.
Selection is performed via the é /ê keys. Continue with ENTER
L1 (R) L1 (R)
L2 (S) L2 (S)
L3 (T) L3 (T)
N
Meas. Current
Im (X/1A)
Operating
voltage
Ub
Meas.
Voltage
Um
T 2A
T 2A
PE
Ub UmIm
High voltage Low voltage
20 kV / 400 V
20000
100

Prophi®12R / 12 RS
13
13 ALARM TEMP [ 40...85]°C
The alarm temperature programmed here is the temperature at which the
capacitor stages are disconnected in steps. The controller’s alarm relay
responds after ten minutes. (Factory settings) At the same time the display
shows the cause of the alarm (over-temperature). If the temperature drops
again, the required branches are automatically re-connected in steps.
(Factory setting: 55°C) Hysteresis: 5 degrees
The selection is performed with the é /ê keys. Save and continue with ENTER.
14 ALARM RELAY
can be programmed here for one of the following functions:
ERROR = Summary report
0 13th step Relay output = 13th capacitor step
1 OFF
2 ERROR Contact closed in case of error (except voltage sag)
3 ERROR inverse Contact open in case of error (factory setting)
ERROR resp. ERROR inverse is a collective report and
includes the following errors:
Overtemperature, Meas.voltage, Overvoltage,
Undervoltage, Over- Undercompensated, Overcurrent,
Harmonics
4 FAN for external fan
Parameterization under “15 FAN temperature”
5 SUPPLY Message when real-power is supplied
6 UNDERCURRENT Measuring current below minimum
7 HARMONICS Exceeding of THD-V limit value (7%)
Parameterization under “16 Harmonics”
8 OVERCOMPENSATED
9 UNDERCOMPENSATED
10 Warning switch. oper. Exceeding of set switching operations value
11 MODBUS-ERROR only version -/RS
12 \ MODBUS-ERROR Modbus-Error inverse - only version -/RS
13 MMI-ERROR only version -/RS
14 C-defect only version -/RS
Section each is done with the é / ê buttons. Save/continue with ENTER
- 12 -

Prophi®12R / 12 RS
14
15 FAN TEMP * [15...70]°C
Input of the switching threshold for the fan. *Only active if option 'Fan' is selected
16 HARMONICS THD-V (harmonic limit) [7] % (OFF or 0.1 - 25.5)%
A limit for the total harmonic distortion (in%) can be entered here. When this
threshold is exceeded, a message is given. THD-V is the ratio of the
geometric sum of the harmonics to the fundamental. -,- means OFF
16 HARMONICS THD-I (harmonic limit) [7] % (OFF or 0.1 - 25.5)%
see above, Preset is OFF (-,-)
17 HARMONICS
selection of harmonics for bar graph-display in Display-Mode
[3. 5. 7. - 19.] Odd up to 19th (factory setting)
[3. 5. 7. - 33.] Odd up to 33th
[2. 3. 4. - 17.] Even and odd up to 17th
18 CONTRAST
Adjustment of optimal contrast for the display possible
*only active if under „INTERFACE: 3 EXT. INPUT“ the function
„2nd parameter set“ is activated
From factory side the values of the 2nd parameter are set equal to the ones of
the normal parameters. By changing of particular parameters for example the
target cos-phi can be changed here. Other cases of application are transformer
switch over or change of switching times.
By applying a control voltage (110…230V) at the external input the 2nd
parameter set is activated with following indicated values:
19. CT primary, 20. CT sec., 21. End-stopp, 22. Control series,
23. Control principle, 24. Output 1st st., 25. Target cos-phi, 26. Switch-on time,
27. Switch off time, 28. Discharge time.
ere an additional capacitive power is switched on independent from target
cos-phi and controlling - e.g. transformer direct compensation.
(value programmable via arrow-keys).
BASIC SETTINGS: [ NO ] ( YES / NO )
When the selection is made with YES and confirmed with ENTER, all parameters
are reset to the basic setting made by the PFC-system manufacturer.
(Optimal network values when the controller was supplied with a complete PFC-
system). If the controller is supplied from the works, this point corresponds to
the default setting.
CAUTION: All user settings are lost!
5.3 Programming lock
The PROPHI 12 is equipped with a programming lock to ensure protection from
unauthorized or inadvertent changes to the system parameters. The
lock can be activated
in Expert Mode1 - item9. If the lock is active, all parameters can be checked but not
changed.
19 - 28 Programming of all values of the 2nd parameter set (version /S485 only)
29 Q-OFFSET [NO] (multiple of 1st stage)
H
- 13 -
2

Prophi®12R / 12 RS
15
Section 6 Manual operation (initial operation, maintenance, service)
Programming of fixed stages
In manual operation, capacitor branches can be connected/disconnected in the set
control series and switching time - irrespective of prevailing power-line conditions.
Manual operation 1: The starting condition is STOPP (no stages connected).
Connections are made by pressing the é key (CAP ON).
Pressing ê initially leads back to STOPP mode.
Repeated pressing of ê leads to the disconnection of stages (CAP OFF).
The active operating status and active power factor are always shown on the display.
Pressing ENTER takes the user to the Manual operation 2.
Normally, all stages are programmed for automatic operation (default setting).
Here all controller outputs (C1 - C12) may be permanently defined in succession
(continued switching via ENTER) for the following statuses:
FIXED: The output is continuously connected, e.g. for fixed PFC. The output is
marked by an underlined capacitor symbol.
AUTO: Automatic (normal) operation
The relevant output is marked by a capacitor symbol.
OFF: The output is continuously disconnected - e.g. for temporarily disconnecting a
defective capacitor. The capacitor symbol for this output is faded out. Minus ( - )
appears.
ON: The selected stage will be switched ON (maybe putting into operation)- in case
a discharge-time is active - it will be shown at the display
The active stage is blinking. The required status is set via é /ê. By pressing ENTER, the
user saves this step and moves to the next stage.
The programmed statuses for the outputs also remain visible on the display in automatic
operation.
After the required settings have been made, pressing the "Operating Mode” key takes the
user to the next menu ("Service”) or further to "Automatic Operation”.
- 14 -
MANUAL MODE 1
------------------ MANUAL MODE 1
------------------ MANUAL MODE 1
------------------
STOP 1.000 CAP ON 0.871 CAP CAP OFF 0.871 CAP
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
device-Stop connection of steps disconnection of steps
MANUAL MODE 2
------------------ MANUAL MODE 2
------------------ MANUAL MODE 2
------------------
C1 - [AUTO] C1 - [ FIXED] C1 - [ON] 20 s
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12

Prophi®12R / 12 RS
16
Section 7 Service menu
The service menu is reached by the operating-mode key.
The stored maximum values of the network parameters can be displayed here as well as
the number of switching operations of the individual capacitors and their operating time.
The desired stages [in square brackets] can be selected via the arrow keys.
* In Version /RS the max.values are stored including time-stamp!
In addition, a fault memory is available, in which the last 50 fault states of the system are
stored with fault code and in plain text. (This allows, for example, capturing short lived
events of overtemperature or overvoltage)
Action Display
ENTER 1 min/max. VOLTAGE in V
ENTER 2 max. REACTIVE POWER in kvar
ENTER 3 max. ACTIVE POWER in kW
ENTER 4 max. APPARENT POWER in kVA
ENTER 5 max. TEMPERATURE in °C / °F
ENTER 6 max. THD - V / THD - I in %
ENTER 7 RESET the maximum and energy values
ENTER 8 SWITCHING OPERATIONS C [1] - ...
+/- to C [12]
ENTER 9 OPERATING TIME C [1] - ... in h
+/- to C [12]
ENTER 10 ERROR MEMORY E [1] - .... in plaintext
ENTER 11 ERROR MEMORY RESET
ENTER 12 TEST RUN
ENTER 13 C-POWER (only after a test-run or AUTO-INIT)
ENTER 14 SERVICE INTERVAL (--- / 2 ... 100 month)
after this time a service message will appear
ENTER 15 - 27 input of a tel.no. for service-message
max. 13 digits
ENTER Back to 1
TEST-RUN
This menu point allows the user to check the settings of the PFC controller. After activation
of the test run, the controller switches each stage ON and OFF successively and calculates
the output of the capacitors connected (this procedure is done three times to eliminate
possible errors). The values calculated are stored and can be retrieved in the following
menu item (C-POWER). At the same time, a plausibility check is conducted with the values
programmed. Discrepancies are displayed in plain text afterwards. The following errors
can be displayed:
- No measuring voltage
present
- Measuring voltage too high - check programming
- Measuring voltage too low - check programming
- No measuring current? - Short circuit link in current transformer?
- Phase angle current transformer? k/l or phase transposed ?
- Current transformer ratio / 1. step power wrong ?
- Control series? - check programming
- End stop? - check programming
- Capacitor defect or wrong power input
Note: The results displayed are messages intended to help the user trace the cause of the
error. Final evaluation remains the responsibility of the user. Under complicated (high load
fluctuations) grid conditions, 100% error recognition cannot be guaranteed.

Prophi®12R / 12 RS
17
- 16 -
Section 8.1 Expert mode 1
The expert mode is meant for the adjustment of values which normally should not be
changed. As a protection against mal-operation this level has an access code.
Factory setting: “6343” The password can be changed in point 22 of expert mode 1.
1 PASSWORD ???? (Factory setting: 6343)
2 BASIC SETTING NEW [NO] (available: NO/YES)
Storage of active programming as a new basic setting (usually performed by the
PFC-system manufacturer).
Caution: The original values are overwritten in the process!
3 SWITCHING OPERATIONS RESET [NO] (available: NO/YES)
The stored switching operations of all capacitor stages are reset to zero. Caution: No
information is then available about the switching frequency of the stages and thus
the status of the network. (Reset of individual stages in Expert-mode 2 )
4 OPERATING TIME RESET [NO] (available: NO/YES)
The stored operating times of all outputs are set to zero.
(Reset of individual stages in Expert-mode 2 )
5 INTEGRATION TIME [1] s (1...255 sec.)
The integration time (the time required to form the mean values of a
measurement) can be changed for special applications.
6 SWITCHING POWER max [100] kvar (multiples of the smallest stage)
This factor specifies the maximum power which may be switched in one switching
step. It can be used to control the intelligent control system, which switches several
stages as a function of the power-factor requirement.
(Factory setting: 4 times the power of the first stage)
7 SWITCH.TRIGGER IND [66]% (30...100%)
Threshold for switching ON of next stage. (a-value)
Should not be changed in the normal case!
8 SWITCH.TRIGGER CAP [66]% (30...100%)
Threshold for switching OFF next stage. (b-value)
It should not be changed in the normal case!
9 OPERATING LOCK [NO] (NO / YES)
10 SWITCHING OPERATIONS WARNING [50,000] (1000 ... 255,000)
After an output has performed this number of switching operations, a warning
message is displayed. ( Abrasion of capacitor contactors and capacitors)
11 FAST DISCHARGE [NO] (NO or X for the desired stages)
If only some stages of a network are equipped with fast discharge equipment, those
stages can here be indicated with X. In this case, the desired discharge time for these
stages can be specified in the next menu point.
[1] s (1s ..programmed normal discharge time)
Only available when fast discharge is programmed. The specified discharge time is
then also included in the normal display.
12 DISCHARGE TIME

Prophi®12R / 12 RS
18
13 PHASE I [L1] Adjustment of current phase position
Selection of phase of current transformer
14 PHASE V [L1-N] Between which conductors has the measuring voltage of the
controller been connected:L-L resp. L-N of all phases possible.
Phase correction between voltage and current in the measuring system. (refer p.6)
15 C-TEST [YES] ( YES / NO)
The power of the particular capacitor stage is calculated during each switching
operation and compared with the stage output of the capacitor. If the result varies
from the nominal value, an error message is generated. This test can be stopped
here. In coupling-mode C-TEST is inactive!
16 C-FAULT (+) [150]%
( -) [ 50]%
The deviation from the rated value of the capacitor, for a fault message is generated.
17 TEST ATTEMPTS [6] ( 2...9)
When at least this number of successive measurements has resulted in a fault in the
capacitor power, a C-fault message is output.
18 OUTPUT 1. STEP [0...255] (0...2550; 0...25500)
The range for entering the stage output can be increased to [0...25500] here
(e.g. for high-voltage measurement)
19 CONTROL [3] PHASE [CAP]
The measuring system of the controller is based on a single phase measurement.
3-phase CAP (factory setting): The measurement is converted and all outputs are
displayed 3-phase (presuming symmetry in the grid).
1-phase CAP: Display and control is only performed for the measured 1-phase value
(for example 1-phase compensation in non-symmetric grids)
3-phase IND: set-up of an inductive compensation with reactors possible (3- phase)
1-phase IND: set-up of an inductive compensation 1-phase
3-phase C/I : Mixed compensation possible (CAP/IND)
1-phase C/I : (Realization according separate application solution)
20 SUPPLY Setting of the controller in case supply of electric power takes place
[1] --- (no reaction) factory setting
[2] switch-off stepwise
[3] total switch off
[4] 2.cos-Phi
21 DISPLAY [cos
j] (cos j / tan j)
Switch over between cosinus or tangens
j in the display (all menus)
22 PASSWORD CHANGE? (YES/NO)
The password for ExpertMode can be changed here. All combinations of letters
and figures are possible
27 ERROR - DISPLAY BACKLIGHT
If an error or warning message appears in the display -the backlight can change
to red light for better attention. (modification: OFF/ white/ red/ pink)
28 CT - OFFSET [0] (-4 ...1000)
The here selected value will be added to the „primary CT“-value (in Programming/
item 1) Therefore all possible CT-ratios are possible.

Prophi®12R / 12 RS
19
Section
8.2. Expert mode 2
The
additional 2nd expert mode includes all messages for operation, warning and error
which
are displayed by the PROPHI 12. Here they may be deactivated separately. When
deactiv
ated, the indication of the message in the display as well as possible activation of
the
relay or effects on the control behavior are suppressed.
1
PASSWORD ???? (Factory setting: 6343)
Changing of code is possible in ExpertMode1 / item 22
2
Activation / Deactivation / Setting if delay time
of particular operation, warning and error messages - s. above:
Meas.
-voltage; Overvoltage; Overcompensated; Undercompensated; Harmonics!;
Ov
ertemperature; Overcurrent; Undervoltage; Switch.Operations!; Undercurrent;
Auto-Init
3
ERROR ME.RELAY [10] min. (1...255min.)
Time after which the alarm relay will respond
4
UNDERVOLTAGE [50] % (20 ...100 %)
meas. voltage below this threshold will switch OFF all
stages at the same time
5
OVERVOLTAGE [130] % (105 ...140 %)
meas. voltage above this threshold will switch OFF
the stages step by step
If the measure voltage returns to the permissible range,
the stages will switch ON again.
6
FREQUENCY [42...80 Hz] (50Hz / 60Hz / 42...170Hz / 16.7Hz)
Measurement by the controller is done automatically in grids of 40 … 80 Hz.
In grids with extremely poor voltage quality it is recommend to select a fix
frequency (50 or 60 Hz) to avoid measuring errors due to voltage sags.
7
OVERCOMPENSATED [QDIF] ( 0.1 ... 0.99 CAP]
QDIFF = factory setting; the threshold for alarm-message
“overcompensated“ can be changed here
8
UNDERCOMPENSATED [QDIF] ( 0.1 ... 0.99 IND]
QDIFF = factory setting; the threshold for alarm-message
“undercompensated“ can be changed here
9
SWITCH. OPERATIONS C 1 RESET [NO] (YES/NO) to
C12 RESET [NO] (YES/NO)
Reset of switching operations of particular capacitors possible
10
OPERATION TIME C 1 RESET [NO] (YES/NO) to
C12 RESET [NO] (YES/NO)
Reset of operation time of particular capacitors possible
Additionally
, switching operations and operation times of the capacitors can be reset.
Service-Interval;
M
odbus-Error; MMI-Error; Remote-disconnect; Remote-stop; Remote-connect;
MODBUS-remote;
Current<; BusError extern; C-defect; Current>?; Overload equip.;
External
Error; C-Error Off;

Prophi®12R / 12 RS
20
- 19 -
Section 9 Control principle
The control response of the device can be selected in programming mode.
The controller has four different control modes:
1. Sequential connection
In sequential connection, the required capacitor stages are successively connected
and disconnected in stages (last in - first out). The ranking of each step always
corresponds to the power of the smallest stage.
Advantage: Exact definition of the next capacitor to be connected in each case
Disadvantage: Long settling time, high switching frequency of the small stages
In order to shorten the settling time, the controller switches several stages
simultaneously for a large power-factor requirement. This applies to all
control types. The maximum dimensions of the simultaneously switching
branches can be changed in expert mode. If the value of the smallest stage
is pre-selected, the conventional sequential connection is obtained.
2. Loop connection
In this variant, the controller operates in loop mode (first in - first out) which
minimizes the wear on the capacitor bank, i.e. where stages are of equivalent
dimensions, the stage which was disconnected for the longest period of time is
always connected next.
Advantage: Balanced utilization of equivalent stages and thus an increased
operating life of the capacitor bank.
Disadvantage: This mode can only be used in control series with groups of the same
stage power and long settling time, as every switching step corresponds to the value
of the smallest stage.
3. Intelligent loop connection (default setting )
The intelligent control principle combines the advantages of the network-sparing
loop connection (first in - first out) with a much faster settling time, even for large
load skips, and reaches this goal with the fewest possible switching operations of the
capacitor stages. The optimized time response is achieved by the simultaneous
switching of several or larger capacitor groups as a function of the missing power
factor in the power line. Both the number of real switching frequencies of the
capacitors as well as the turn-on times of the branches are considered.
Advantage: Reaches the target cos phi in a fast-optimized settling time with a low
switching frequency of the capacitors.
4. Combined de-tuning (special case for combined de-tuned banks)
Within a combined de-tuned application, 2 adjoining equal steps are switched with
just one joint choke. This pairwise de-tuning requires an appropriate closed control
series (i.e. 1:1:1:1..., 1:1:2:2..., 1:1:2:2:4:4... or similar)
The condition for the switching behavior is defined in such a way that the number of
activated odd steps is always greater than or equal to the number of activated even
steps. The controller complies with the requirements of the control regime while
largely conforming to the intelligent switching behavior.
The particular capacitor steps are permanently monitored. In case of a defect
capacitor or higher deviation from the nominal output the capacitor will be
displayed inverted.
This manual suits for next models
1
Table of contents
Other janitza Controllers manuals
Popular Controllers manuals by other brands

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-F Series user manual

EMKO
EMKO esm-4450 instruction manual

Bticino
Bticino AXOLUTE HD4657M3 quick start guide

Rockwell Automation
Rockwell Automation External Dynamic Brake Kit installation instructions

Omega
Omega DPF700 quick start

Teufel
Teufel Raumfeld Base Setup guide