manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson Controls
  6. •
  7. Control Unit
  8. •
  9. Johnson Controls EM-3000 Series User manual

Johnson Controls EM-3000 Series User manual

EM-3000 Series Meter Quickstart Guide QS - 1
Electronic Circuits
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Va Vb Vc Vref L1 L2 PE
A B C N
A B C N
Ia
Ib
Ic
Power Supply Inputs
L2 is for Neutral
Electronic Circuits
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Va Vb Vc Vn L1 L2 PE
A B C N
A B C N
Ia
Ib
Ic
Power Supply Inputs
WYE with PTs, 3
Phase, 4 Wire
Detail of JP2 Board and
LAN/485 Setting
WYE Direct, 3
Phase, 4 Wire
Front Cover
Support fitted
into its base
Power Supply
Inputs (Inputs
are unipolar)
L2 is for Neutral
Electronic Circuits
Ethernet, RJ45
Jack
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Z K Y + - SH
Va Vb Vc Vn L1 L2 PE
RS485
KYZ Pulse
Output
Wireless Ethernet Connection
RS485 Output
(Do not put the
Voltage on these
terminals!)
Voltage
Inputs
Current
Inputs
Access Holes for
Wiring
JP2
WARNING! During normal operation of the meter
dangerous voltages flow through many parts of the meter,
including Terminals and any connected CTs and PTs, all I/O
modules and their circuits. All Primary and Secondary
circuits can, at times, produce lethal voltages and
currents. Avoid contact with any current-carrying surfaces.
Before performing ANY work on the EM-3000 Series
meter, make sure the meter is powered down and
ALL circuits are de-energized.
IMPORTANT! All wiring is done with the cover open, as shown
on the left. The front cover support fits into its base. Make sure
the support is up before closing the front cover.
Select wiring diagram to meet your application. See User Manual for additional wiring diagrams.
NOTE: Jumper 2 (JP2)
must be set for either
RS485 or Ethernet commu-
nication (see figures on the
left for location of JP2 and
settings). Put the jumper
on positions 2 and 3 for
LAN (Ethernet) communi-
cation, or on 1 and 2 for
RS485 communication.
EM-3000 Series Meter Quickstart Guide
Code No. LIT-12011870
Issued October 25, 2013
EM-3000 Series Meter Quickstart Guide QS - 2
Program Settings Using the Faceplate Buttons: (MENU, ENTER, DOWN ARROW, RIGHT
ARROW) See the figure below for the location of the faceplate buttons.
Access Configuration Mode:
1.Push the MENU button - you will see the display on the right; rSt will be
blinking.
2.Press the DOWN ARROW once. CFG (Configuration) moves to the
top of the display.
3.Press the ENTER button. You will see the Configuration menu, shown
on the right.
MAX
MIN
VOLTS L-N
AMPS
%LOAD
120%-
PRG
%THD
LM2
LM1
90%-
60%-
30%-
VOLTS L-N
W/VAR/PF
VA/H z
Wh
KILO
VARh
VAh
Wh Pulse
MEGA
A
B
C
MENU ENTER
IrDA 0000
0.659
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Va Vb Vc Vref L1 L2 PE
A B C
A B C
Ia
Ic Electronic Circuits
Power Supply Inputs
DELTA with PTs, 3
Phase, 3 Wire
Electronic Circuits
Ia Ia Ib Ib Ic Ic
(+) (-) (+) (-) (+) (-)
Va Vb Vc Vref L1 L2 PE
A B C
A B C
Ia
Ic
Power Supply Inputs
DELTA Direct, 3
Phase, 3 Wire
EM-3000 Series Meter Quickstart Guide QS - 3
4.Press the DOWN ARROW and then press the ENTER button. You will see the CT
numerator setting screen (Ct-n). The current CT numerator is shown in the second
line. To change the setting, press the DOWN ARROW until the value you want is
displayed. Then press the RIGHT ARROW to move to the next digit. Repeat until
the setting is done.
5.Press the ENTER button to go to the CT denominator screen (CT-d). This setting is
display only - it can’t be changed.
6.Press the ENTER button to go to the CT Scaling setting screen (CT-S). The current
Scaling is shown in the second line. Press the DOWN ARROW to choose another
value. You can choose 1, 10, or 100.
7.Press the ENTER button to go to the PT numerator setting screen (Pt-n).The current
PT numerator is shown in the second line. To change the setting, press the DOWN
ARROW until the value you want is displayed. Then press the RIGHT ARROW to
move to the next digit. Repeat until the setting is done.
8.Press the ENTER button to go to the PT-denominator screen (Pt-d). The current
PT denominator is shown in the second line. To change the setting, press the DOWN
ARROW until the value you want is displayed. Then press the RIGHT ARROW to
move to the next digit. Repeat until the setting is done.
9.Press the ENTER button to go to the PT Scaling setting screen (PT-S). The current
Scaling is shown in the second line. Press the DOWN ARROW to choose another
value. You can choose 1, 10, 100, or 1000.
NOTE: See example CT and PT Settings on the next page.
10.Press the ENTER button to go to the Connection setting screen (Cnct). The current
setting is shown in the second line. Press the DOWN ARROW to choose another
value. You can choose 3 EL (element) WYE, 2 Ct del (Delta), or 2.5 EL WYE.
11.Press the ENTER button to go to the meter Address setting screen (Adr). The
meter’s current address is shown in the second line. To change the setting, press
the DOWN ARROW until the value you want is displayed. Then press the RIGHT
ARROW to move to the next digit. Repeat until the setting is done. Valid address-
es are from 001 through 247. If you are using the Ethernet option, do NOT
change anything on this screen.
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
EM-3000 Series Meter Quickstart Guide QS - 4
12.Press the ENTER button to go to the meter Baud Rate setting screen (bAUd). The
meter’s current Baud Rate is shown in the second line. Press the DOWN ARROW
to choose another Baud Rate. You can choose 9600 (choose this for RS485
connection), 19.2 (19200), 38.4 (38400) or 57.6 (57600). If you are using the
Ethernet option, do NOT change anything on this screen.
13.Press the ENTER button to go to the meter Protocol setting screen (Prot). The
meter’s current Protocol is shown in the second and third lines. Press the DOWN
ARROW to choose another communication Protocol. You can choose Mod rtU
(Modbus RTU; choose this for RS485 connection), Mod ASCI (Modbus ASCII), or
dnp (DNP 3.0). If you are using the Ethernet option, do NOT change
anything on this screen.
14.Press the ENTER button to go to the Scroll setting screen (SCrL). The current
setting is shown in the second line. Press the DOWN ARROW to choose another
setting. You can choose YES (the meter readings will scroll on the display) or no
(the meter readings will not scroll on the display).
15.Press the MENU button twice. You will see the Store Settings screen (Stor ALL?)
The default setting is YES. To save the settings you’ve made, press the ENTER
button. You will see the confirmation screen (Stor ALL done) and then the meter
resets.
NOTE: If you do not want to save your settings, press the RIGHT ARROW. YES
changes to no. Press the ENTER button.
Example CT Settings:
200/5 Amps: set the Ct-n value as 200, Ct-S value as 1.
800/5Amps: set the Ct-n value as 800, Ct-S value as 1.
2000/5 Amps: set the Ct-n value as 2000, Ct-S value as 1
10,000/5 Amps: set the Ct-n value as 1000, Ct-S value as 10.
Example PT Settings:
14400/120 Volts: set the Pt-n value as 1440, Pt-d value as 120, Pt-S value as 10.
138000/69 Volts: set the Pt-n value as 1380, Pt-d value as 69, Pt-S value as 100.
345000/115 Volts: set the Pt-n value as 3450, Pt-d value as 115, Pt-S value as 100.
345000/69 Volts: set the Pt-n value as 345, Pt-d value as 69, Pt-S value as 1000.
Refer to the EM-3000 Series Meter Installation and Operation Manual (LIT-12011874) for important
product application information. Also refer to the manual for additional wiring options and program-
ming information. The manual is on the enclosed CD.
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER
A
B
C
-
-
-
MENU ENTER

Other manuals for EM-3000 Series

1

Other Johnson Controls Control Unit manuals

Johnson Controls LP-FXGPRSU-0 User manual

Johnson Controls

Johnson Controls LP-FXGPRSU-0 User manual

Johnson Controls Mercury P2000 CKM-MR16IN Manual

Johnson Controls

Johnson Controls Mercury P2000 CKM-MR16IN Manual

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls VP101DBB User manual

Johnson Controls

Johnson Controls VP101DBB User manual

Johnson Controls Penn A19K Series User manual

Johnson Controls

Johnson Controls Penn A19K Series User manual

Johnson Controls NIE39 User manual

Johnson Controls

Johnson Controls NIE39 User manual

Johnson Controls GM 20 Series User manual

Johnson Controls

Johnson Controls GM 20 Series User manual

Johnson Controls FX-PCX2721 User manual

Johnson Controls

Johnson Controls FX-PCX2721 User manual

Johnson Controls PENN P70 Series Manual

Johnson Controls

Johnson Controls PENN P70 Series Manual

Johnson Controls MS-IOU4710-0U User manual

Johnson Controls

Johnson Controls MS-IOU4710-0U User manual

Johnson Controls tyco AMD-2 User manual

Johnson Controls

Johnson Controls tyco AMD-2 User manual

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls S1-TTSCC User manual

Johnson Controls

Johnson Controls S1-TTSCC User manual

Johnson Controls tyco AMD-1 User manual

Johnson Controls

Johnson Controls tyco AMD-1 User manual

Johnson Controls VF Series User manual

Johnson Controls

Johnson Controls VF Series User manual

Johnson Controls Tyco HSM3408 User manual

Johnson Controls

Johnson Controls Tyco HSM3408 User manual

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls IOM3731 User manual

Johnson Controls

Johnson Controls IOM3731 User manual

Johnson Controls Mercury 3 Series Manual

Johnson Controls

Johnson Controls Mercury 3 Series Manual

Johnson Controls VP140 User manual

Johnson Controls

Johnson Controls VP140 User manual

Johnson Controls C450CCN-2 User manual

Johnson Controls

Johnson Controls C450CCN-2 User manual

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls

Johnson Controls Tyco DV-5a Series User manual

Johnson Controls V46SA Series User manual

Johnson Controls

Johnson Controls V46SA Series User manual

Johnson Controls Penn System 450 Series User manual

Johnson Controls

Johnson Controls Penn System 450 Series User manual

Popular Control Unit manuals by other brands

Inbeca Ecotouch user manual

Inbeca

Inbeca Ecotouch user manual

ADC HiGain H2TU-C-319 List 4E Quick installation

ADC

ADC HiGain H2TU-C-319 List 4E Quick installation

NI PXIe-6674T user manual

NI

NI PXIe-6674T user manual

WAGO SPEEDWAY 767 Series manual

WAGO

WAGO SPEEDWAY 767 Series manual

Siemens MLC installation instructions

Siemens

Siemens MLC installation instructions

GCE druva LINE 200 operating instructions

GCE

GCE druva LINE 200 operating instructions

Vimar V53108 manual

Vimar

Vimar V53108 manual

Motorola MVME2400 Series Installation and use

Motorola

Motorola MVME2400 Series Installation and use

Dell PowerEdge M420 Administrator's guide

Dell

Dell PowerEdge M420 Administrator's guide

Toshiba HX7 Series Specifications

Toshiba

Toshiba HX7 Series Specifications

Danfoss EKF Series installation guide

Danfoss

Danfoss EKF Series installation guide

RS 571-439 Instruction leaflet

RS

RS 571-439 Instruction leaflet

Bailey Infi 90 INIIR01 Instruction

Bailey

Bailey Infi 90 INIIR01 Instruction

GRASS VALLEY XCU user guide

GRASS VALLEY

GRASS VALLEY XCU user guide

ECG AD8232 Assembly manual

ECG

ECG AD8232 Assembly manual

Gefa HGT Series operating instructions

Gefa

Gefa HGT Series operating instructions

ICPDAS ECAT-2045-32 quick start

ICPDAS

ICPDAS ECAT-2045-32 quick start

Vimar by-me 01958 instruction sheet

Vimar

Vimar by-me 01958 instruction sheet

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.