manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Johnson Controls
  6. •
  7. Thermostat
  8. •
  9. Johnson Controls TEC3000 Series User manual

Johnson Controls TEC3000 Series User manual

TEC3000 Series Networked and Wireless
Single- or Two-Stage Economizer Thermostat
Controllers Installation Guide
Applications
The TEC3000 Series Single- or Two-Stage Economizer
Thermostat Controllers are stand-alone and field-
selectable BACnet® MS/TP or N2 networked devices.
Wireless networked models of the TEC3000 Series
Thermostat Controller are also available. Series Single- or
Two-Stage Economizer Thermostat Controllers provide
control of the following:
• Unitary rooftop units (RTUs)
• Unitary RTUs with economizers
• Unitary heat pumps
• Unitary heat pumps with economizers
• Unitary RTUs with hot gas reheat
• Unitary RTUs with hot gas reheat and economizers
The networked models feature a field-selectable
Building Automation System (BAS) BACnet MS/TP or N2
communication capability that enables remote monitoring
and programming for efficient space temperature control.
The wireless models are compatible with the WNC1800/
ZFR182x Pro Series Wireless Field Bus System that enables
communication with a building automation system (BAS).
The wireless models (TEC30xx-xx-000) are compatible
only with the WNC1800/ZFR182x Pro Series Wireless Field
Bus System that enables communication with a building
automation system (BAS). The new wireless models
(TEC31xx-14-000) are compatible only with WRG1830/
ZFR183x Pro Series Wireless Field Bus System. All models
include a USB port configuration that reduces installation
time to allow simple backup and restore features from a
USB drive, which enables rapid cloning of configuration
between similar units.
Some models have occupancy sensing capability built into
the device. These thermostat controllers maximize up to
30% energy savings in high-energy usage commercial
buildings, such as schools and hotels, during occupied
times by using additional standby setpoints.
All models feature an intuitive onboard touchscreen
UI with backlit display that makes setup and operation
quick and easy. Only the single-speed fan configuration is
supported for fan coil equipment types.
All models contain a build-in humidity sensor to support
dehumidification on RTUs with hot gas reheat and RTUs
with auxiliary dehumidifier installed. When no heating
is required, the thermostat controller monitors the
space humidity and activates dehumidification control as
necessary. Heat, reheat or both are used as required to
prevent over-cooling while achieving humidity setpoint
and maintain the space temperature.
Important: The TEC3000 Series Thermostat
Controller is intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the thermostat
controller could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of
or protect against failure or malfunction of the
thermostat controller.
Important: Le TEC3000 Series Thermostat
Controller est destiné à transmettre des données
entrantes à un équipement dans des conditions
normales de fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement du
thermostat controller risque de provoquer des
blessures ou d'endommager l'équipement
contrôlé ou un autre équipement, la conception du
système de contrôle doit intégrer des dispositifs de
protection supplémentaires. Veiller dans ce cas à
intégrer de façon permanente d'autres dispositifs,
tels que des systèmes de supervision ou d'alarme,
ou des dispositifs de sécurité ou de limitation, ayant
une fonction d'avertissement ou de protection en
cas de défaillance ou de dysfonctionnement du
thermostat controller.
North American emissions
compliance
United States
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to Part15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference ina
residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if notinstalled
and used in accordance with the instructions, may cause
harmful interference to radio communications.However,
there is no guarantee that interference will not occur
in a particular installation. If this equipment doescause
harmful interference to radio or television reception,
which can be determined by turning the equipment
offand on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and
receiver.
• Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
LIT-12013163
2020-07-06
TEC3330-1x-xxx, TEC3331-1x-xxx, TEC3630-1x-xxx,
TEC3631-1x-xxx, TEC3030-1x-xxx, TEC3031-1x-xxx,
TEC313x-14-xxx
• Consult the dealer or an experienced radio/TV
technician for help.
Canada
This Class (B) digital apparatus meets all the requirements
of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes
les exigences du Réglement sur le matériel brouilleurdu
Canada.
Installation
Parts included
• One TEC3000 Series Thermostat Controller with integral
mounting base
• One installation instructions sheet
Location considerations
For networked models, locate the TEC3000 Series
Thermostat Controller:
• On a partitioning wall, approximately 5 ft (1.5 m) above
the floor in a location of average temperature, to allow
for vertical air circulation to the TEC
• Away from direct sunlight, radiant heat, outside walls,
outside doors, air discharge grills, stairwells, and from
behind doors
• Away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or sources
of electrical interference
• In a clear path between the integrated passive infrared
(PIR) occupancy sensor, if equipped, and the space it
monitors
For wireless models, also locate the thermostat controller:
• Outside of a recessed area, metal enclosure, or shelving
unit
• On the same building level as the other wireless devices
on the same personal area network (PAN)
• At least 2 in. (51 mm) away from any metal obstruction
• In the direct line of sight to other wireless devices on
the same PAN. Signal transmission is best if the path
between the TEC3000 and other wireless devices is
direct as possible. Line of sight is desirable but not
required. See Table 1 and Table 2 for the recommended
and maximum distances.
• Away from metal and large solid obstructions, that
includes equipment rooms and elevator shafts and
concrete or brick walls, between the TEC3000 and
the ZFR182x or ZFR183x Router/Repeater or ZFR Pro
Coordinator Radio
• Within range of two or more wireless devices on the
same PAN. Redundancy in the layout provides the best
reliability in wireless installations
• At least 20 ft (6 m) from a microwave oven
For integrated PIR models, make sure that the thermostat
controller is located centrally, where occupant movement
is frequent. Ensure that the unit is not blocked by a plastic
tamper resistant enclosure (such as the GRD10A-608). The
plastic enclosure blocks the occupancy sensing capability.
The use of insulating foam pads is necessary for
installations where wiring passes through the wall to the
thermostat.
For wireless models, the effective transmission range and
distance for indoor applications vary because of wireless
signal absorption and reflection due to metal obstructions,
walls or floors, and furniture that is found in building
interiors.
Table 1: Indoor line-of-sight transmission ranges
ZFR182x
Range type Transmission distance
WNC Coordinator
Radio, ZFR Pro
Repeater
TEC3000 Wireless
Thermostat
Controller
Recommended 50 ft (15.2 m) 50 ft (15.2 m)
Line of sight,
maximum
250 ft (76.2 m) 100 ft (30 m)
Note:
• Allow for sufficient clearance to insert a USB drive
into the USB port
• For more details about using ZFR Pro Series
communication devices, refer to the WNC1800/
ZFR182x Pro Series Wireless Field Bus System
Technical Bulletin (LIT-12012356).
Important: Only connect memory devices
to the USB port. Do not use it for charging
external devices.
Table 2: Indoor line-of-sight transmission ranges
ZFR183x
Range type Transmission distance
WNC Coordinator
Radio, ZFR Pro
Repeater
TEC3000 Wireless
Thermostat
Controller
Recommended 250 ft (76.2 m) 50 ft (15.2 m)
Line of sight,
maximum
4000 ft (1219.2 m) 100 ft (30 m)
Note:
• Actual range depends on the site and installation
conditions. See Technical Documentation for more
information.
• For more details about using ZFR Pro Series
communication devices, refer to the WNC1800/
ZFR183x Pro Series Wireless Field Bus System
Technical Bulletin (LIT-12013553).
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide2
Figure 1: Thermostat controller shown without
occupancy sensor, dimensions, in. (mm)
Table 3: Thermostat controller features
Callout Description
1 Security screw
2 Display
3 USB port
Installing the thermostat controller
1. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson
Controls® T-4000-119 Allen-Head Adjustment Tool
(order separately) to remove the security screw if it
is installed on the top of the thermostat controller
cover as illustrated in Figure 2.
2. Pull the top edge of the cover and open the
thermostat controller as illustrated in Figure 2.
Important: The cover is not secured on the
bottom. Do not drop the cover.
Important: If you are installing more than one
thermostat controller, keep track of which cover
attaches to which base. The controller version
and the base version must match to ensure
correct operation.
Important: Use correct Electrostatic Discharge
(ESD) precautions during installation and
servicing to avoid damage to the electronic
circuits of the thermostat controller.
Figure 2: Removing the security screw from the thermostat
controller cover, shown without occupancy sensor, and
removing the thermostat controller cover
3. Align the thermostat controller mounting base on
the wall with the security screw on the top and use
the base as a template to mark the two mounting
hole locations. See Figure 3.
- If you need to install the thermostat controller
on an electrical junction box, use 2-1/2 in. x
4 in. (63 mm x 101 mm) square boxes with
mud ring covers and avoid smaller 1-1/2 in.
x 4 in. (38 mm x 101 mm) square or 3 in. x 2
in. (76 mm x 51 mm) boxes. This procedure
ensures that you have enough space for
cabling, if needed.
- For surface-mounted applications, use durable
mounting hardware, such as wall anchors, that
cannot be easily pulled out of the mounting
surface.
4. Pull approximately 6 in. (152 mm) of wire from the
wall and insert the wire through the center hole
in the thermostat controller mounting base. See
Figure 3.
5. Secure the mounting base to the wall surface using
two mounting screws (user supplied) as illustrated
in Figure 3.
Note: Do not overtighten the mounting screws.
Figure 3: Mounting hole locations, dimensions, in. (mm)
and securing the thermostat controller mounting base to
the wall
Note: When you mount the unit on the wall, you
can hang the front cover on the end of the back
cover as illustrated in Figure 4.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 3
Figure 4: Hanging the thermostat controller front cover
Wiring
About this task:
When you replace an existing thermostat controller,
remove and label the wires to identify the terminal
functions.
WARNING
Risk of Electric Shock
Disconnect the power supply before making electrical
connections to avoid electric shock.
AVERTISSEMENT
Risque de décharge électrique
Débrancher l'alimentation avant de réaliser tout
raccordement électrique afin d'éviter tout risque de
décharge électrique.
CAUTION
Risk of Property Damage
Do not apply power to the system before checking
all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to
the equipment.
ATTENTION
Risque de dégâts matériels
Ne pas mettre le système sous tension avant
d'avoir vérifié tous les raccords de câblage. Des
fils formant un court-circuit ou connectés de façon
incorrecte risquent d'endommager irrémédiablement
l'équipement.
Important: Make all wiring connections in
accordance with local, national, and regional
regulations. Do not exceed the electrical ratings of
the TEC3000 Series Thermostat Controller.
Important: Use correct ESD precautions during
installation and servicing to avoid damage to the
electronic circuits of the thermostat controller.
To wire the thermostat controller, complete the
following steps:
1. Strip the ends of each wire 1/4 in. (6 mm) and
connect them to the appropriate screw terminals as
indicated in Table 5.
Note: For more details on wiring the MS/
TP Communications Bus, refer to the MS/
TP Communications Bus Technical Bulletin
(LIT-12011034).
2. Attach the communication wires to the terminal
block.
Note: If multiple wires are inserted into the
terminals, make sure to twist the wires together
before you insert them into the terminal
connectors.
3. Carefully push any excess wire back into the wall.
Note: Seal the hole in the wall with fireproof
material to prevent drafts from affecting the
ambient temperature readings.
4. For networked models, set the bus end-of-line (EOL)
termination switch to the desired location.
You can designate the thermostat controller as
the end of the Field Controller (FC) Bus and N2
Bus through the bus EOL termination switch.
The default position is OFF. If the thermostat
controller is at the end of a daisy chain of
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide4
devices on the FC Bus and N2 Bus, set the EOL
switch to the ON position. See Figure 5.
Figure 5: EOL switch position (left) and installing the
thermostat controller cover (right)
5. Reattach the thermostat controller cover to the
mounting base, bottom side first.
Important: Make sure you reattach the cover
that corresponds to its correct base. The CPU
board number needs to match the base board
number. Otherwise, an operation error occurs
after you reattach a cover and base that do
not belong together. The example in Figure 6
indicates that a TEC3612-16 is mounted on the
base of a TEC3312-16. See Table 4 for TEC3000
model names and code numbers.
Figure 6: Error code indicating mismatched boards
Table 4: TEC3000 model names and code numbers
Name 1Code
number1
Name Code
number1
TEC3012-13 30 TEC3313-14 05
TEC3012-14 31 TEC3322-13 08
TEC3012-16 33 TEC3322-14 09
TEC3013-14 35 TEC3322-16 0B
TEC3022-13 38 TEC3323-14 0D
TEC3022-14 39 TEC3330-13 10
TEC3022-16 3B TEC3330-14 11
TEC3023-14 3D TEC3330-16 13
Table 4: TEC3000 model names and code numbers
Name 1Code
number1
Name Code
number1
TEC3030-13 40 TEC3331-14 15
TEC3030-14 41 TEC3612-13 18
TEC3030-16 43 TEC3612-14 19
TEC3031-14 45 TEC3612-16 1B
TEC3112-14 49 TEC3613-14 1D
TEC3113-14 4D TEC3622-13 20
TEC3122-14 51 TEC3622-14 21
TEC3123-14 55 TEC3622-16 23
TEC3130-14 59 TEC3623-14 25
TEC3131-14 5D TEC3630-13 28
TEC3312-13 00 TEC3630-14 29
TEC3312-14 01 TEC3630-16 2B
TEC3312-16 03 TEC3631-14 2D
1 The two-character code number is listed within the error
code to indicate that the CPU board and base board do not
belong together.
6. Use a 1/16 in. (1.5 mm) Allen wrench or Johnson
Controls T-4000-119 Allen-Head Adjustment Tool
(order separately) to reinstall the security screw
on the top of the thermostat controller cover. See
Figure 2 for security screw placement.
7. Remove the protective plastic cover sheet from the
display.
Important: If the display is dirty, gently wipe
it clean with isopropyl alcohol or ethyl alcohol.
Do not scrub hard as to avoid damaging the
surface. Do not use other cleaners such as
water, ketones, and aromatic solvents, since
they may damage the polarizer.
Note:
- For VAV and two-pipe systems, connect
the valve to the heating output.
- Only one transformer is required for each
TEC.
- Power to the AUX contact comes from
the reheat coil.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 5
Terminal identification
Table 5: Terminal identification (See Wiring diagrams for details)
FunctionTerminal label
TEC3030, TEC3031, TEC313x TEC3330, TEC3331 TEC3630, TEC3631
24 V 24 VAC hot from the sensor
Y1 Cooling stage 1
Y2 Cooling stage 2
AUX Auxiliary binary output
AUX Auxiliary power input
W1 OB Heating 1 (RTU mode)/Reversing valve (O/B) (Heat Pump mode)
1RH1Power for W1 and W2
W2 SUP Heating 2 (RTU mode)/Supplemental heat (Heat Pump mode)
OAD Outdoor air damper, 0 VDC - 10 VDC
2COM2Common
COM2Common
G Fan
BI-2 Configurable binary input 2
BI-1 Configurable binary input 1
RSEN Configurable analog input 1
OAT Configurable analog input 3
SAT Configurable analog input 2
NET+ n/a Not connected Field bus+/N2+
NET- n/a Not connected Field bus-/N2-
NET COM n/a Not connected Isolated common for field bus
1 RH needs to be connected for W1 and W2 to energize. For heating systems with an isolated power supply, connect RH to the R
terminal of the heating system. For systems that switch the hot supply to the heating commands, connect the jumper to 24 V. For
systems that switch the neutral supply to the heating commands, connect the jumper to COM.
2 For the networked models, the common terminals, which do not include NET COM, are internally connected and can be used for all
inputs and outputs. For the wireless models, the common terminals are connected and can be used for all inputs, outputs, and 24
VAC ground or common.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide6
Wiring diagrams
See Table 5 for terminal identification.
Figure 7: Staged wiring diagram - Rooftop Unit
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 7
Figure 8: Staged wiring digram - Heat Pump
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide8
Figure 9: Staged wiring diagram - Rooftop Unit with Auxiliary Dehumidifier
Note: See Figure 12 for auxiliary contact wiring
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 9
Figure 10: Staged wiring digram - Heat Pump with Auxiliary Dehumidifier
Note: See Figure 12 for auxiliary contact wiring
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide10
Figure 11: Staged wiring diagram - Rooftop Unit with Hot Gas Reheat
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 11
Figure 12: AUX contact wiring
Figure 13: Binary input wiring
Setup and adjustments
Important: Table 14 provides a full list of TEC3000
menu settings. In the upcoming sections, step-by-
step instructions are included on how to access and
adjust the more commonly used menus.
Overview
About this task:
Figure 14 shows the thermostat controller home screen
in both the light and dark themes. You can customize
it to show or hide various elements from the occupant.
See Table 6 for a listing of the touchscreen icons and
Table 14 to identify the home screen settings under the
Display Settings. When screen customization is used in
conjunction with a passcode, the building owner can
control which options the occupant can access and adjust.
Important: If lockout levels are used, some icons
are hidden. Table 7 provides details of these levels.
Figure 14: Thermostat controller home screen (shown
with light and dark themes)
To switch between the modern, classic, light, and
dark themes, complete the following steps:
1. Press the Menu icon.
2. Press Settings.
3. Press Display Settings.
4. Press Change Color Theme.
5. Select one of the four options available.
Result
Multiple pages are available on the display. The page that
you currently view is emphasized with a filled dot. The
other available page displays as an empty dot.
In the modern theme, the cooling, or blue, and heating, or
orange, circles show whether the cooling or heating mode
is active.
Figure 15: Thermostat controller home screen in
cooling mode (left) and heating mode (right)
Customizing the home screen
About this task:
Customizing the Home screen settings include:
• Brightness
• Enable Backlight
• Units
• Time
• Time Zone
• Time Format
• Date
• Date Format
You can also show or hide these items on the Home
screen:
• Fan Button
• Temperature
• Humidity
• Off Button
• Hold Button
• Setpoint
• Alarms
• Occupancy Status
• Unit Status
• Date/Time
To customize the Home screen, complete the following
steps:
1. Press the Menu icon.
2. Press Display Settings.
3. Enable or disable elements of the home screen as
appropriate for the building owner and occupants.
4. Set the passcode on the thermostat controller to
prevent the occupants from changing settings that
they should not have access to change.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide12
Touchscreen icons
Table 6 describes the touchscreen icons on the home screen. Press and release a touchscreen icon to activate the TEC.
Additional touchscreen icons appear based on the menu, and those icons are also described in Table 6.
Table 6: Touchscreen icons
Icon Icon name Description
Menu Displays the configuration screens where various settings may be
adjusted.
Alarm Indicates that the thermostat controller has triggered an alarm.
On
Standby
Unit Power Powers the thermostat controller on or off.
• This icon disables all equipment control but does not physically
power down the unit.
• On the modern home screen, if the Unit Power icon is in standby
mode, the temperature and humidity also display in standby mode
to indicate that control off or standby mode is active.
On
Standby
Humidity Indicates the humidity reading.
On
Standby
Degree Indicates that the unit is set to degrees.
Network Communication
(for Networked Models)
No Signal
Indicates that the thermostat controller detected a supervisory
controller and both are online.
Indicates that the thermostat controller did not detect a supervisory
controller.
No Signal
Low Signal
Medium
Signal
High Signal
Radio Signal (for Wireless
Models)
Indicates the strength of the radio signal.
Arrow Up
Arrow Down
Increases or decreases the cooling value on the home screen.
Arrow Up
Arrow Down
Increases or decreases the heating value on the home screen.
Cooling Hold Indicates that cooling hold mode is enabled. To disable Hold mode,
press the button.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 13
Table 6: Touchscreen icons
Icon Icon name Description
Heating Hold Indicates that heating hold mode is enabled. To disable Hold mode,
press the button.
Cooling Setpoint Displays the current cooling setpoint. Indicates that Hold mode is
disabled. To enable Hold mode, press the button.
Heating Setpoint Displays the current heating setpoint. Indicates that Hold mode is
disabled. To enable Hold mode, press the button.
Setpoint Temperature Displays the current setpoint temperature. Indicates that the Show
Hold button is set to No.
Heating Mode Indicates that heating mode is selected.
Cooling Mode Indicates that cooling mode is selected.
Auto Mode Indicates that Auto mode is selected.
On
Auto
Quiet
Fan Overrides for Single-
speed Fans
Adjusts the fan override between On, Auto, and Quiet for single-speed
fans.
Unoccupied
Occupied
Temporarily
Occupied
Standby
Override -
Occupied
Override -
Unnoccupied
Occupancy Status Adjusts the occupancy between Unoccupied, Occupied, Temporarily
Occupied, Standby, Occupancy Override, Unoccupancy Override.
Back Moves the display to the previous screen.
Forward Moves the display to the next screen.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide14
Table 6: Touchscreen icons
Icon Icon name Description
Home Returns the display to the main home screen.
Save Saves the current configuration and parameter settings.
Delete Deletes the scheduled event.
Clear Clears the password entry on the keypad screen.
Exclamation point Indicates that an error has occurred.
User lockout
You can select from three different levels of access at
the local display to manage functionality through the
supervisory controller. This lockout is independent of
any display or passcode settings. The existing temporary
occupancy capability is unaffected by this feature. User
lockout hides the icons that are not operable. The lockout
levels are described in Table 7.
Table 7: User lockout levels
Lockout
level
Capability
State 0 Provides full access to Home Screen
Display Adjustments and icons (default).
State 1 Hides the Menu icon.
State 2 Only allows the screen to trigger
temporary occupancy. Menu, Unit Power,
the Up and Down arrows, and Run/Hold
are hidden.
Using the USB port
Use the USB port to quickly and easily load firmware
upgrades, back up the current settings, and restore
settings to the TEC3000 by using a USB drive. The TEC3000
can recognize eight configuration files or firmware
package files. The USB drive format must be FAT or FAT32.
The drive cannot be NTFS format or USB 3.0. If you are
upgrading firmware or copying configuration files, you
need the passcode if one has been set up. Do not remove
the USB drive until the firmware upgrade is complete.
The TEC3000 may restart and go offline to the NAE after
a firmware upgrade. The upgrade takes approximately
three minutes.
Configurations are copied, except for the Communication
mode. See Choosing the Communication mode (TEC3630,
TEC3631 Models) to configure the networked devices.
Loading the firmware
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Load Firmware.
6. Select the correct firmware version. The correct file
name has the .pkg extension.
7. Press Confirm if you have the correct firmware
version.
The firmware is loaded from the USB drive into the
TEC3000 operating system. The TEC3000 locates the
new firmware only if the new firmware is on the root
drive of the USB drive. See Table 16 if the firmware is
not loaded correctly.
8. Remove the USB drive from the TEC3000 controller
when the update is complete.
The TEC3000 firmware update is complete when the
TEC3000 restarts and returns to the home screen.
Backing up the settings
About this task:
Note: When you back up the settings, the network
settings are not backed up or restored.
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Scroll down the menu and press Update.
5. Press Backup.
A message appears stating that the file is saved
locally and on a USB drive.
6. Press Confirm to save locally and on USB.
The setting files are named based on the TEC3000
model name, date, and time stamp. For example,
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 15
TEC3xx1-00_2018-07-01T1. The files are saved locally
and on the USB drive’s root directory. See Table 16 if
the settings are not backed up correctly.
7. After the settings are saved onto the USB drive,
remove the USB drive from the TEC3000.
Restoring the settings
About this task:
If the TEC3000 is connected to a network (for example,
MS/TP or wireless), you must manually set or verify the
BACnet® Instance ID and BACnet Address, or both, in
the Network Setup page after the restore so they do not
conflict with other devices on the same network.
1. Ensure that the TEC screen is on.
2. Insert the USB drive into the right side of the TEC.
See Figure 1 for the USB port location.
3. Press the Menu icon.
4. Press Update.
5. Press Restore.
6. Select Local Storage or the correct configuration
file created from a previous backup operation.
The setting files are named based on the TEC3000
model name, date, and time stamp (for example,
TEC3xx1-00_2018-07-01T1). The files are saved locally
and on the USB drive’s root directory.
7. Press Confirm if you have the correct file name.
The settings are loaded from the USB drive.
8. After the settings are loaded from the USB drive,
remove the USB drive from the TEC3000.
Choosing the Communication mode
(TEC3630, TEC3631 Models)
1. Ensure the TEC screen is on.
2. Press the Menu icon.
3. Press Setup.
4. Press Network Setup.
5. Press FC Comm Mode.
6. Select BACnet or N2 by pressing the up and down
arrows.
Proceed to Step 7 to perform BACnet communication
and Step 15 to perform N2 communication.
7. Press the back arrow to return to the previous
screen.
8. Press BACnet Instance ID.
9. Enter the unique BACnet® instance ID using the
keypad. This value should be different to the other
controllers on the site.
10. Press Save.
11. Press the back arrow to return to the previous
screen.
12. Press BACnet Address.
13. Enter the BACnet MS/TP address through the
keypad.
14. Press Save.
15. After selecting N2 in Step 6, press Save.
16. Press the back arrow to return to the previous
screen.
17. Press N2 Address.
18. Enter the N2 address through the keypad.
19. Press Save.
Configuring the network settings for
wireless models
1. Ensure the TEC screen is on.
2. Press the Menu icon.
3. Press Setup.
4. Press Network Setup.
5. Press FC Comm Mode and the Wireless Field Bus
appears. This setting cannot be changed.
6. Press the back arrow to return to the previous
screen.
7. Press BACnet Instance ID.
8. Enter the BACnet® instance ID using the keypad.
This value should be different to the other
controllers on the site.
9. Press Save.
10. Press the back arrow to return to the previous
screen.
11. Press BACnet Address.
12. Enter the BACnet address using the keypad. This
value should be different to the other controllers
on the PAN.
13. Press Save.
14. Press the back arrow to return to the previous
screen.
15. Press PAN ID.
16. Enter the PAN ID using the keypad. This value
needs to be the same as set in the associated
ZFR182x or ZFR183x Coordinator Radio.
17. Press Save.
Once the PAN is set, the TEC attempts to connect to
the wireless network. Provided that other devices on
the PAN are in radio range, the connection should
occur within one minute. It can then take up to 10
minutes for the WNC gateway to display that the
device is online.
Configuring the thermostat controller
Use the Menu icon on the home screen to access and
change the basic operating parameters of the thermostat
controller. During normal operation, press the Menu icon
once to access the following parameters:
• Fault Status
• Setpoints
• Schedule
• Display Settings
• Setup
• Trend
• Status
• Update
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide16
Installer configuration menu
The thermostat controller comes from the factory with
default settings for all configuration parameters. The
UI menu navigation and default settings are shown in
Table 14. Before any outputs turn on, the controller must
be configured for the equipment connected. You need
to start from the home screen to perform any of the
following tasks.
Screen reset
The current screen returns to the home screen and turns
off if the current screen is not touched for 3 minutes.
Touch the screen to turn it on again. To disable the
screensaving option, press Display Settings and set
Enable Display Timeout to No.
Selecting Rooftop or Heat Pump mode
About this task:
By default, the thermostat controller is configured for
Rooftop mode. This mode is used for up to two discrete
stages of heating (W1, W2) and up to two discrete stages
of cooling (Y1, Y2). Certain heat pumps do not require an
O/B input and instead take standard W and Y commands
as heat or cool commands, internally sequencing the
equipment. For these type of heat pump units, leave the
controller in Rooftop mode.
When in heat pump mode, the TEC controls up to two
stages of compressors (Y1, Y2) for both heating and
cooling. O/B is controlled through the W1/OB output and
one stage of supplemental heat is controlled through the
W2/SUP output. To configure heat pump mode, complete
the following steps:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Heat Pump.
5. Press Heat Pump Supported and select Yes.
6. If supplemental heating is installed, press Supp
Heating Installed and select Yes.
7. Press Reversing Valve Polarity and set
appropriately for the O/B input on the equipment
based on if the equipment is normally cooling until
the thermostat output is activated or normally
heating (typically, Normally Heat for O and
Normally Cool for B).
8. Press Save and the back arrow to return to the
previous screen.
Configuring heating and cooling stages
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press General.
5. Press Number of Compressors and adjust the
number of compressor inputs on the equipment
being controlled.
6. If the thermostat controller is in rooftop mode,
press Number of Heating Stages and adjust the
number of heating inputs on the equipment being
controlled.
7. Press Save and the back arrow to return to the
previous screen.
Configuring economizer
About this task:
If the equipment has an analog (between 0 VDC to
10 VDC) input for an economizer damper command,
configure the economizer as follows:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Economizer.
5. Press Economizer Installed and select Yes.
6. Press Min Position and set to the percentage that
the damper must be kept open to ensure fresh air
flow in the zone.
7. Press Closed Voltage and set to the voltage output
at which the damper is fully closed.
8. Press Opened Voltage and set to the voltage output
at which the damper is fully opened.
9. Press Save and the back arrow to return to the
previous screen.
The TEC supports three methods of determining
economizer availability. These are Dry Bulb, Single
Enthalpy, and Dual Enthalpy, in increasing order of
accuracy. To run an economizer, outdoor air temperature
(OAT) is required to run in Dry Bulb mode. This can be
provided by connecting a sensor to the OAT input on the
TEC. It also can be provided by writing to NET-OAT from
a Building Automation System (BAS), which overrides
the internal sensor. If Outdoor Air Humidity (OAH) is
also provided by writing to NET-OAH, the dual enthalpy
method is used to determine if economizer cooling should
be used.
All network overrides to the TEC work on a timeout basis.
If the value is written to, it remains active as long as the
BAS writes a new value within 15 minutes of the first one.
If the 15-minute timeout occurs without getting any data
written, the TEC stops using the network data.
When operating in Dry Bulb or Single Enthalpy mode,
it is necessary to provide a Dry Bulb Setpoint or an OA
Enthalpy Setpoint, respectively. The TEC ships with default
values set, but depending on climate it may be necessary
to change these. To access these values, complete the
following steps:
1. Press the Menu icon.
2. Press Setup.
3. Press Equipment Setup.
4. Press Economizer.
5. Press Dry Bulb Setpoint or Outdoor Enthalpy
Setpoint and adjust according.
6. Press Save and the back arrow to return to the
previous screen.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 17
Setting the Control mode
About this task:
The Control Mode informs the controller to run in Cooling
only, Heating only, or Automatic mode, based on the
temperature in the zone relative to the heating and
cooling setpoints. Control Mode does not override
equipment lockouts or changeover. To set the Control
Mode, complete the following steps:
1. Press the Menu icon.
2. Press Setup.
3. Press General Setup.
4. Press Control Mode and select Cooling, Heating,
or Auto as preferred.
5. Press Save and the back arrow to return to the
previous screen.
Setting the Fan mode
About this task:
The Fan Mode informs the controller how to handle
the fan. There are two options for fan configuration: a
Fan Mode available to the installer through the menu
system, and a fan override available as an option to the
end user from the Fan icon on the home screen. See
Customizing the home screen for information on enabling
and disabling end-user controls. The Fan Mode available
to the installer depends on the fan type. The following
options are provided for single-speed fans:
• On—Fan is continuously on
• Auto—Fan cycles on demand with the controller
entering cooling, heating, or dehumidification modes
• Smart—Fan cycles on demand with the controller
entering cooling or heating modes during unoccupied
periods but is continuously running during occupied
and standby periods
The Fan Override icon on the home screen depends
on the fan type. The following options are provided for
single-speed fans:
• On—Overrides the fan to be continuously on
• Auto—Follows the behavior set as Fan Mode
• Quiet—Follows the behavior set as Fan Mode, but
prevents the fan from ever going above minimum
speed. The Quiet option has no effect on equipment
with single-speed fans.
To set the Fan Mode, complete the following steps:
1. Press the Menu icon.
2. Press Setup.
3. Press General Setup.
4. Press Fan Mode and select On, Auto, or Smart.
5. Press Save and the back arrow to return to the
previous screen.
Configuring the zone space or
equipment size
About this task:
With non-binary outputs, the TEC3000 default
configuration is to have a slower temperature response
for larger zones with normal-sized equipment. In
installations with small zones and oversized equipment,
set the Equipment Size parameter to Oversized.
To set the Equipment Size parameter, complete the
following steps:
1. Press the Menu icon.
2. Press Control Setup.
3. Press Tuning.
4. Use the up and down arrows to navigate to
Equipment Size.
5. Press Equipment Setup and select Oversized.
6. Press Save and the back arrow to return to the
previous screen.
Temperature setpoints
About this task:
The thermostat controller provides a flexible setpoint
configuration to give power to the building owner while
being easy to use by the occupant. In addition to a simple
up/down offset adjustment on the home screen for the
occupant, there are six temperature setpoints on the TEC.
The six temperature setpoints are Cooling and Heating
setpoints for Occupied, Unoccupied, and Standby modes.
To set these setpoints, complete the following steps:
1. Press the Menu icon.
2. Press Setpoints and then Temperature.
3. Select the setpoint to adjust and change as
preferred.
4. Press Save and the back arrow to return to the
previous screen.
Note: The TEC enforces a 2-degree deadband
between heating and cooling setpoints. If a
setpoint violates this standard (for example,
cooling setpoint is set to 70 with a heating
setpoint already set to 70), the opposing
setpoint is modified to comply with this
deadband (in the previous example, the
heating setpoint would automatically change to
68).
Result
The occupant has access to an up/down adjustment from
the home screen. This adjustment applies a fixed offset
(+/-) to the currently active setpoint, and this offset holds
until the occupancy state of the controller changes. If
the user taps the setpoint on the home screen, the icon
inverts and displays white text on a black icon. The offset
is held throughout all occupancy periods. For example,
if the TEC is cooling in Occupied mode to an occupied
cooling setpoint of 72 and you raise the setpoint 2
degrees to 74 from the home screen and then select hold,
then the +2 degree offset persists through an occupancy
change. If the occupancy then changes to unoccupied,
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide18
with a setpoint of 80 degrees, the effective setpoint is 82
degrees. This allows the occupant to have a small amount
of control over raising or lowering the temperature, but
the building owner can still set back setpoints during
standby and unoccupied periods. When the setpoint is in
Hold mode, pressing the icon again releases the hold and
immediately sets the setpoint offset back to 0.
When the TEC is in Min/Max mode (Setpoints/Occ
Setpoint Select are equal to Min and Max Setpoint), the
TEC rejects any attempts to change the present value
outside of the valid range. If the present value is outside
of the valid range (for example, if the Occ Setpoint Select
is switched from Setpoint Offset to Min and Max Setpoint),
the present value is reset to be in the center of the valid
range.
The four modes of setpoint operation are described in
Table 8.
Table 8: Setpoint operation
Mode of
setpoint
operation
Details
Occ Setpoint
Select =
Setpoint
Offset and
Heat Cool
Setpoint
Mode =
Individual
Setpoints
This is the default mode and the original
mode of operation that the TEC was
released with (the next three modes are
new). In this mode, the TEC has a heating
setpoint and a cooling setpoint. There is a
common Setpoint Offset (warmer/cooler
adjust) that applies to each setpoint
simultaneously. The range of setpoint
adjustment is two-fold:
• There are large constant ranges
bounding the individual heating and
cooling setpoints.
• There is also a smaller configurable
range limit set to the Setpoint Offset
point (Control Setup > General > Max
Setpoint Offset).
Occ Setpoint
Select = Min
and Max
Setpoints
and Heat
Cool
Setpoint
Mode =
Individual
Setpoints
In this mode, the TEC has a heating
setpoint and a cooling setpoint. Each
setpoint has a configurable range
(Setpoints > Temperature > Min Cooling
Setpoint, Max Cooling Setpoint, Min
Heating Setpoint, and Max Heating
Setpoint). The configurable range values
are bounded by the larger constant
bounds used in Setpoint Offset mode and
are constrained in the following manner:
Min must be below Max and Heating
must be below Cooling, so in order from
least to greatest, the values are: Min
Heating Setpoint, Max Heating Setpoint,
Min Cooling Setpoint, and Max Cooling
Setpoint.
Occ Setpoint
Select =
Setpoint
Offset and
Heat Cool
Setpoint
Mode =
Common
Setpoint
In this mode, the TEC has one setpoint,
Common Setpoint, for heating and
cooling. There is also a common Setpoint
Offset (warmer/cooler adjust) that only
applies to Common Setpoint. Otherwise,
this setting works the same as when Occ
Setpoint Select = Setpoint Offset and Heat
Cool Setpoint Mode = Individual Setpoints.
Occ Setpoint
Select = Min
and Max
Setpoints
and Heat
Cool
Setpoint
Mode =
Common
Setpoint
In this mode, the TEC has one setpoint,
Common Setpoint, for heating and
cooling. There is a configurable range for
Common Setpoint, Min Setpoint, and Max
Setpoint.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide 19
Configuring occupancy
To adapt to nearly any application, the TEC3000 controller
supports a wide variety of occupancy sources, such as:
• Local stand-alone weekly scheduler
• Remote schedule from BAS
• Occupancy sensor (internal or remote)
• Occupancy binary input (configurable)
• Manual occupancy override
• Temporary occupancy (by interacting with the screen
while in unoccupied mode)
• Temporary occupancy binary input
Occupancy is determined using a top-down decision
matrix as shown in Table 9.
Enumerations may not match the TEC3000 Series
Networked and Wireless Single- or Two-Stage Economizer
Thermostat Controllers Installation Guide (LIT-12013163)
and the TEC3000 Series Field-Selectable BACnet MS/TP or
N2 Networked Thermostat Controllers Technical Bulletin
(LIT-12011956) for NAE releases prior to 7.x.
Table 9: Occupancy determination
Sequence of operation (highest to lowest priority) Status indicated
Manual
Occupancy
Mode
(OCCOVRD-
MODE)
1Occupancy BI
(BI1-S, BI2-S)1
2, 3Temporary
Occupancy2,3
Occupancy
Schedule
(External or
Schedule)
(OCC-
CONFIG, NET-
OCC)
4Motion
Sensor4
Effective
Occupancy
(EFF-OCC)
Occupancy Source
(OCCSOURCE-S)
Occupied Occupied-
Override
Unoccupied
–
Unoccupied-
Override
Occ Override
Closed1Occupied
Open1
– –
Unoccupied
Occupancy BI
True2NOT Occupied Temp
Occupancy
Temp Occ
True3NOT Occupied
–
Temp
Occupancy
Temp Occ BI
True Occupied
False Standby
Occupancy SensorOccupied
Disabled Occupied
Unoccupied Unoccupied
Standby
–
Standby
Occupancy Schedule
True Occupied
False Unoccupied
Occupancy Sensor
No Override
Not
Configured1
False
5 Not Set5
Disabled Occupied Occupancy Schedule
1 Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current state of
the BI when configured as Occupancy.
2 True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when the
schedule is not Occupied.
3 When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual Occupancy Mode
is not No Override, or an Occupancy BI is configured.
4 Built-in occupancy sensing (PIR) or BI configured for Motion NO or Motion NC.
5 Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and the
Schedule is writing Not Set as the schedule.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide20

Other manuals for TEC3000 Series

6

This manual suits for next models

42

Other Johnson Controls Thermostat manuals

Johnson Controls NXT-INT-01 User manual

Johnson Controls

Johnson Controls NXT-INT-01 User manual

Johnson Controls NXT-TSO-01 TSO User manual

Johnson Controls

Johnson Controls NXT-TSO-01 TSO User manual

Johnson Controls TEC2645-4 Service manual

Johnson Controls

Johnson Controls TEC2645-4 Service manual

Johnson Controls TEC2104-1 User manual

Johnson Controls

Johnson Controls TEC2104-1 User manual

Johnson Controls TCN-890x User manual

Johnson Controls

Johnson Controls TCN-890x User manual

Johnson Controls T-4002 User manual

Johnson Controls

Johnson Controls T-4002 User manual

Johnson Controls T9500 User manual

Johnson Controls

Johnson Controls T9500 User manual

Johnson Controls Hx 3 S1-THXU430W User manual

Johnson Controls

Johnson Controls Hx 3 S1-THXU430W User manual

Johnson Controls T-901 User manual

Johnson Controls

Johnson Controls T-901 User manual

Johnson Controls T8690 Operating instructions

Johnson Controls

Johnson Controls T8690 Operating instructions

Johnson Controls T9100 User manual

Johnson Controls

Johnson Controls T9100 User manual

Johnson Controls T7000e User manual

Johnson Controls

Johnson Controls T7000e User manual

Johnson Controls TVI-TD-6007 Series User manual

Johnson Controls

Johnson Controls TVI-TD-6007 Series User manual

Johnson Controls T2000 series User manual

Johnson Controls

Johnson Controls T2000 series User manual

Johnson Controls T7000 Series User manual

Johnson Controls

Johnson Controls T7000 Series User manual

Johnson Controls TEC20x6-4 Series User manual

Johnson Controls

Johnson Controls TEC20x6-4 Series User manual

Johnson Controls T25 User manual

Johnson Controls

Johnson Controls T25 User manual

Johnson Controls T8680 Operating instructions

Johnson Controls

Johnson Controls T8680 Operating instructions

Johnson Controls T6000 Series User manual

Johnson Controls

Johnson Controls T6000 Series User manual

Johnson Controls TEC2104-3 User manual

Johnson Controls

Johnson Controls TEC2104-3 User manual

Johnson Controls FX-WRZRMT10K-0 User manual

Johnson Controls

Johnson Controls FX-WRZRMT10K-0 User manual

Johnson Controls YORK DPC-1R Manual

Johnson Controls

Johnson Controls YORK DPC-1R Manual

Johnson Controls T25 User manual

Johnson Controls

Johnson Controls T25 User manual

Johnson Controls T26 Series User manual

Johnson Controls

Johnson Controls T26 Series User manual

Popular Thermostat manuals by other brands

HaiLin Controls HA202 user manual

HaiLin Controls

HaiLin Controls HA202 user manual

Intermatic Grasslin thermio essential B operating manual

Intermatic

Intermatic Grasslin thermio essential B operating manual

TemperZone TZT-701 user manual

TemperZone

TemperZone TZT-701 user manual

Kanmor 506 Series User brochure

Kanmor

Kanmor 506 Series User brochure

Ideal Boilers touch quick start guide

Ideal Boilers

Ideal Boilers touch quick start guide

Vemer Chronos Key user manual

Vemer

Vemer Chronos Key user manual

Braeburn Builder 1010 user manual

Braeburn

Braeburn Builder 1010 user manual

Viega 15116 user guide

Viega

Viega 15116 user guide

Honeywell T8501D installation instructions

Honeywell

Honeywell T8501D installation instructions

Lux Products Smart Temp TX9000a Series Installation and operating instructions

Lux Products

Lux Products Smart Temp TX9000a Series Installation and operating instructions

Center EHE0200364 installation guide

Center

Center EHE0200364 installation guide

Resol DeltaSol M manual

Resol

Resol DeltaSol M manual

ComfortNET CTK01 Installation and start-up instructions

ComfortNET

ComfortNET CTK01 Installation and start-up instructions

Bticino Smarther X8000W quick start guide

Bticino

Bticino Smarther X8000W quick start guide

North HeatmiserNeo manual

North

North HeatmiserNeo manual

Full Gauge Controls RT-607Ri plus manual

Full Gauge Controls

Full Gauge Controls RT-607Ri plus manual

Thermofilm TT-MTC2-4A User instructions

Thermofilm

Thermofilm TT-MTC2-4A User instructions

GE PROGRAMMABLE THERMOSTAT installation instructions

GE

GE PROGRAMMABLE THERMOSTAT installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.