4 JUDO PROFI
Design of Backwash water connection
the rinse water valve] a few meters away to
the next wastewater connection. When piv-
oting a pipe for the derivation of the rinse
water it has to be paid attention to the fact
that the spherical faucets are not twisted,
because these are pasted in by means of
thread locking devices.
Design of Backwash water con-
nection
The dimensioning of the channel cross sec-
tions for the backwash water depends on
the local conditions. For example the down-
ward gradient of the wastewater pipe, the
quantity of the detours, length of the sewage
pipe.
Commissioning
Before starting up (initial putting into service
or start-up after maintenance work), fill the
Backwash Protective Filter with water and
vent!
Operation
For cleaning the filter the handwheel is un-
twisted to the left as far as it will go and
closed to the right afterwards, till no more
rinse water water flows out. Rough impuri-
ties can be removed by opening the sludge
trap ball valve that is built in before the
backwash ball valves. According to DIN
standard 1988 it is recommended to back-
wash the filter approximately every 2
months. Depending on the water flow as
well as on the kind of coarse-grained and
fine-grained impurities and the extent to
which these are existing in the water, a
backwashing can be necessary within
shorter time intervals. The backwashing
takes place at full water line pressure. At
pressures higher than 2 bar, it is necessary
that the backwash stream is throttled by
means of the backwash ball valve. Doing
this it is prevented, that the sieve cloth is
damaged by a too strong pressuring of the
suction tube. At the same time the rinse wa-
ter consumption is reduced. With a flush
valve opened to one hundred percent and a
pressure between 2 bar and 3 bar the back-
wash volume current amounts to approx.
0.5 litres/per second concerning the filter
unit JPF DN65, and to approx. 1 liter/ per
second concerning the filter units JPF
DN80-DN100.
External Cleaning
Use only clear drinking water to clean the
housing and transparent filter hood.
Domestic all-purpose cleaners and glass
cleaners can contain up to 25% solvents or
alcohol (spiritus).
These substances can chemically attack the
plastic parts, which can lead to brittleness
right up to a burst.
These kinds of cleaners must therefore
not be used.
Customer Service
We wish you anytime a trouble-free opera-
tion.
Should occur, however, short-comings,
sometime or if there are queries, our cus-
tomer service will be pleased to be at your
disposal for further information.
Warranty and Services
In order to comply with the legal warranty
claim, according to DIN 1988, Part 8, it is
necessary that the "… backwashing takes
place at least every 2 months, after operat-
ing conditions exist … ".
Regular servicing is indispensable in order
to continue to achieve a successful treat-
ment for many years after the unit is put into
service. In the building services sector this is
covered by DIN 1988, Part 8.
A servicing agreement is the best way to en-
sure a good operating function beyond the
warranty period.
Wherever possible, the regular servicing
work and supply with consumables and
wearing materials, etc. should be carried out
by the specialist trade or the factory’s cus-
tomer service department.