
Do not connect two or more devices at a time. The start-up
of many devices requires high power. Devices should be
connected one at a time according to their power rating.
ATTENTION – DANGER!
1. Check oil level.
2. For model KS 5500iEG S - set the fuel switch FUEL
CHOICE to LPG.
The inverter generators KS 2100iG S, KS 3100iG S
use smart fuel switching system. In order to use
LPG as fuel you need to connect a hose to the
corresponding connector on the generator panel
and open the valve on the gas cylinder. The solenoid valve will automatically shut off the gasoline supply
from the gasoline tank.
3. Connect the LPG hose to the LPG input on the generator control panel (connect end Aof a hose to the
LPG input on the generator control panel, as shown in Fig. 3.).
4. Connect the hose end with the reducer to the gas cylinder (connect end Bof hose to the gas cylinder,
as shown in Fig. 3).
5. Open the gas valve on the cylinder, making sure that no gas is leaking.
6. Press the pressure relief valve on the reducer 2-3 times (see Fig. 3).
7. When using for the first time, fill the gas line with gas by turning the key (pressing start button) to the
“OFF” position and slowly pull the starter handle to the full cord length 2 to 3 times.
8. For manual start KS 5500iE G model, press MAIN POWER button to “ON” position, pull the manual starter
until a slight resistance is felt, then pull it toward you relatively sharply. Slowly return the manual starter by
hand, do not release it abruptly. For electric start - press MAIN POWER button to “ON” position, then press
the ELECTRIC START button. If the engine does not start on the first try, press the ELECTRIC START button
again in 3-5 seconds.
9. To start KS 2100iG S, KS 3100iG S models, turn the Multifunctional engine switch to the “START” position
(fig. 2). Pull the handle of manual starter until a slight resistance is felt, then pull it relatively sharply. Slowly
return the handle manual starter by hand, do not release it abruptly. Turn the Multifunctional engine switch
to the “RUN” position (fig. 2).
A B
Fig. 3
RUNNING GENERATOR ON LPG (KS 2100iG S, KS 3100iG S , KS 5500iEG S)RUNNING GENERATOR ON LPG (KS 2100iG S, KS 3100iG S , KS 5500iEG S)
Disconnect the load from the generator before changing
fuel. The ECONOMY MODE switch must be in the “OFF”
position. Gasoline remains in the carburetor make it di-
cult to start the engine on LPG.
IMPORTANT!
Let the generator run out of gasoline until it stops. When switching from gasoline to LPG
operation, the generator may be unstable during the rst 2-3 minutes and the low voltage
protection may trip. If the red indicator (overload indicator) lights up in 2-3 minutes after
running the generator on LPG when it is running stable, press the AC Reset BUTTON on a pan-
el of generator to restore voltage supply. To do this, close the fuel valve with the generator
running and wait until the generator stops completely. To do this, close the fuel valve while
the generator is running (set the FUEL CHOICE knob to OFF) to stop the gasoline supply to
the fuel system for the KS 5500iE G, wait for the generator to come to a complete stop. Then
start the generator on LPG. You can also drain the remaining gasoline from the carburetor
before starting the generator on LPG.
TO START LPG/GASOLINE GENERATOR IN GASOLINE MODE TO START LPG/GASOLINE GENERATOR IN GASOLINE MODE (KS 2100(KS 2100iiG S, KS 3100G S, KS 3100iiG S)G S)
1. Close the gas valve on the cylinder.
2. Open the vent on the fuel cap to the “ON”.
3. Turn the Multifunctional engineswitch to the “START” position (fig. 2).
4. Pull the manual starter until a slight resistance is felt, then pull it toward you relatively sharply. Slowly turn
the manual starter by hand, do not release it abruptly.
5. Turn the Multifunctional engineswitch to the “RUN” position.
www.ks-power.de/en |10