
Grid-Tied String Inverter
Blue Planet PVI
Attention!
In disturbed grids or installations that have to be disconnected from the grid occasionally due to
disturbances, yield data and operating hours may not be displayed properly. This is not an inverter error.
Even if such incorrect values are shown the inverter continues to work properly and without any yield loss.
Similarly, disturbed grids may cause inverter shutdowns during the day, although no obvious errors have
occurred. In this case, the inverter display returns the message “Grid Failure“, and incorrect
measurements may be caused as described above. After such shutdown conditions the inverter continues
to operate properly.
PV Generator LED (green):
This LED is illuminated from a generator voltage of approx. 100 V onward and extinguishes as soon as the
generator voltage falls below 80 V. The PV generator LED signals that the inverter is in its active state and
the inverter controls are enabled. If this LED is not lit up the inverter will not be able to start grid feeding.
Under normal operating conditions the LED is illuminated in the morning when there is enough daylight, and
extinguishes again when it gets dark.
Grid feeding LED (green):
This LED is illuminated during the grid feeding process. To this effect, the generator voltage must first exceed
a value of 130 V for 3-4 minutes, ensuring that the PV generator provides enough power. This means that the
“Grid Feeding“ LED is not lit up unless the PV generator LED is illuminated.
Under normal operating conditions the inverter starts grid feeding in the morning and terminates this process
as it becomes dark. On cloudy days or during the winter months the grid feeding process can be interrupted
at certain times, depending on the PV generator and the actual grid feeding capacity, and can be resumed
later on. This process can be repeated for several times, especially in the morning and evening.
Disturbance LED (red):
This LED is enabled in the event of the following disturbances:
Grid overvoltage or low voltage
Grid impedance or grid frequency fault
Excessive generator voltage
Excessive generator power
Shutdown due to excessive temperature
Defective device.
In general, any of these disturbances will lead to termination of the grid feeding process. If the cause of
the disturbance has been remedied, grid feeding will be resumed after a starting-up period of approx. 4
minutes.
Exception: Failure of phase L1 (grid phase to which electrical power is fed).
In the event of a failure of the grid feeding phase the Disturbance LED is not lit up. In this case, all LED’s and
the display are extinguished and the inverter is shut-down completely. Only after the grid feeding phase is
available again can the inverter resume its normal operation.