KE2 Temp + Valve Control (pn 21301)
For Medium Temperature Applications with Air Defrost
Installation Manual
Abbreviations - Alphabetical Listing
Abbreviation Name Type Description
AdF AdF Air Dierential Setpoint Number of degrees air temp must be above room temp setpoint (tS) to return system to refrigeration mode
Adr Adr Modbus Address Setpoint Controller’s address for communications
ALS ALS Alarm Status Variable Pressing ENTER from ALS will show active alarm list; scroll through list using up or down arrow.
ASA ASA Room/Air Sensor Alarm Alarm Alarm occurs when the room temperature sensor input is open or shorted
bi bi Bipolar Setpoint Option under (Ub) Motor Type when using a CUS (custom) valve
Cd2 CD2 CDS 2-7 Valve Setpoint Option under EDt valve selection for pressure regulating valves
Cd9 CD9 CDS 9 Valve Setpoint Option under EDt valve selection for pressure regulating valves
CEL CEL Celsius Setpoint Option for temperature units
CLA CLA Clear Alarms Manually Manual Allows user to manually clear alarms
COr COr Compressor Relay Variables Current state of liquid line solenoid/compressor relay
CrL CrL Carel Valve Setpoint Option under EDt (Expansion Device Type) when SH (Superheat) is selected
CtL CtL Control Type Setpoint Select the type of control: SH (Electronic Expansion Valve), SHt (Electronic ExpansionValve with Thermostat) EPR
(Electronic Pressure Regulating Valve), HGB (Electronic Hot Gas BypassValve),
CUS CUS Custom Setpoint Used for Custom defrost schedule or Custom valve option
d1 d1 Defrost #1 Setpoint Start time of Defrost #1 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d2 d2 Defrost #2 Setpoint Start time of Defrost #2 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d3 d3 Defrost #3 Setpoint Start time of Defrost #3 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d4 d4 Defrost #4 Setpoint Start time of Defrost #4 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d5 d5 Defrost #5 Setpoint Start time of Defrost #5 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d6 d6 Defrost #6 Setpoint Start time of Defrost #6 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d7 d7 Defrost #7 Setpoint Start time of Defrost #7 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d8 d8 Defrost #8 Setpoint Start time of Defrost #8 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d9 d9 Defrost #9 Setpoint Start time of Defrost #9 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d10 d10 Defrost #10 Setpoint Start time of Defrost #10 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d11 d11 Defrost #11 Setpoint Start time of Defrost #11 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
d12 d12 Defrost #12 Setpoint Start time of Defrost #12 when in defrosts per day (dPd) is custom (CUSt); based on 24-hour clock
dEr dEr Derivative Setpoint Should not be adjusted unless instructed by KE2 Therm technical support
dFt dFt Defrost Time Setpoint Maximum time system is allowed in defrost
diS diS Disabled Setpoint Choice under Start time when setting CUS (custom) dPd (defrosts per day)
dPd dPd Defrost Per Day Setpoint Number of defrosts per day 0-12, CUS (custom)
ds1 ds1 Danfoss KVS 15 Valve Setpoint Option under EDt (valve selection) for pressure regulating valves
ds4 ds4 Danfoss KVS 42 Valve Setpoint Option under EDt (valve selection) for pressure regulating valves
Edt Edt Expansion Device Type Setpoint Valve Selection
EPr EPr Electronic Pressure Regulating Setpoint Type of control option under CtL (control type)
ES1 ES1 ESR 12 Valve Setpoint Option under EDt valve selection for pressure regulating valves
ES2 ES2 ESR 20 Valve Setpoint Option under EDt valve selection for pressure regulating valves
FAH FAH Fahrenheit Setpoint Default for all temperatures displayed
FAC FAC Factory Default Manual Manual option to return controller to Factory Default settings
HAO HAO High Alarm Oset Setpoint Number of degrees above the Temperature Setpoint (tS) for a HighTemp Alarm (HtA) condition.
HGb HBHot Gas Bypass Valve Setpoint Option under CtL (ControlType)
HPA HPA High Pressure Alarm Alarm
Occurs when the temperature reading is above the Pressure setpoint + High Alarm Oset setpoint for the
amount of time in setpoint High Low Alarm Delay.; High Temperature or pressure alarm is cleared and disabled
while in defrost.
HS HS KE2-HSV Valve Setpoint Electronic expansion valve option under EDt (valve selection)
HSH HSH High Superheat Alarm Alarm Occurs when superheat is 2 or more degrees above set point and valve is 100% open for 90 minutes; Clears when
superheat is within 2 degrees of setpoint
HtA HtA High Temperature Alarm Alarm
occurs when the temperature reading is above theTemperature set point + Temperature dierential set point
+ High Alarm Oset set point for the amount of time in set point High & Low Alarm Delay; HighTemperature or
pressure alarm is cleared and disabled while in defrost
inL inL Inlet Temperature Variable Temperature measured at the evaporator inlet. Only if SH and tt are selected as the input
inP inP Input Type Setpoint Select type of control: EPR & HGb - PrS (pressure) or tPr (temp); EEV - Pt (pressure/temp)or tt (temp/temp)
int int Integral Setpoint A coecient to the valve control algorithm that increases valve responsiveness
iSA iSA Inlet Sensor Alarm Alarm Valve closes and turns system o.
LAO LAO Low Alarm Oset Setpoint Number of degrees below theTemperature Setpoint (tS) for a LowTemp Alarm (LtA) condition.
LPA LPA Low Pressure Alarm Alarm Pressure is below Low Pressure Cutout (LPC) after 3 consecutive attempts to start the system
LPC LPC Low Pressure Cut Out Setpoint Pressure at which controller de-energizes the Compressor/Liquid Line Solenoid relay (COr)