
KE2 ControlledEnvironment
Quick Start Guide
Parameter Name Description Range Default Current
ROOM TEMP Room temperature to be maintained -50°F to 90°F 55°F
HUMIDITY TARGET Room humidity to be maintained 0% to100% 65%
DEFROST TYPE Method of defrost used on the evaporator coil: Electric, Air, Hot Gas with Liquid Line Solenoid/Compressor relay o, Hot Gas with
Liquid Line Solenoid/compressor relay on ELEC, AIR, HOT GAS COMP ON, HOT GAS COMP OFF AIR
VALVE TYPE Type of valve used on the system: mechanical, KE2 HSV (electric) MECHANICAL, KE2 (ONLY KE2 HSV), CUSTOM KE2 (HSV)
MIN SUPERHEAT The low superheat value that the controller will override pressure control 4 TO 20 5°F
MAX SUPERHEAT The high superheat value that the controller will override pressure control 20 to 60 25°F
MAX OPERATING PRES The maximum allowable suction pressure, (not applicable if VALVE TYPE = MECHANICAL) 10 to 150 150 PSIG
MIN OPERATING SETPOINT The minimum allowable suction pressure
0 to 150 PSIG 0 PSIG
REFRIGERANT The type of refrigerant used in the refrigeration system 404A, R507, 407A, 407C, 422A, 422D, 134A, R22, R717, 438A, 408A, 409A, 407F, 410A, R744 404A
CUSTOM
EEV
ONLY
MOTOR STEP RATE
Step rate for the EEV in steps per second 30 to 400 steps per second 200 steps per second
MAX VALVE STEPS
Number of steps for full stroke of EEV 200 to 6400 steps 1300 steps
HUMIDITY CONTROL Humidity sensor ON, OFF ON
AUX TEMP1 MODE
Conguration mode of the auxiliary temperature sensor if VALVE TYPE = MECHANICAL T1 SUCTION TEMP, MONITOR, TI ROOM TEMP, TI COIL TEMP
T1 SUCTION TEMP
AUX RELAY MODE Conguration mode of the auxiliary relay. ALARM RELAY, 2ND COMP RELAY, 2ND FAN RELAY, 2ND DEF RELAY 2 SPEED FAN CTL,
LIGHTS RELAY, PERM DEF, HUMIDIFIER RELAY ALARM RELAY
FAN SPEED Control variable fan speed by using setpoint as % o and on -100% to 100% 0%
MIN COMP RUN TIME Minimum amount of time the liquid line solenoid/compressor relay must remain on after it is energized 0 to 15 minutes 2 minutes
MIN COMP OFF TIME Minimum amount of time the liquid line solenoid/compressor relay must remain o before it can be energized again. 0 to 15 minutes 5 minutes
REFRIG FAN MODE Fan operation while in refrigeration mode ON WITH COMPRESSOR, PERMANENT, MANAGED ON WITH COMPRESSOR
DEFROST MODE The method the controller uses to determine when to initiate a defrost. DEMAND, SCHEDULED, RUN TIME DEMAND
DEFROSTS / DAY If DEFROST MODE = SCHEDULED: The number of evenly spaced defrosts per day the controller will initiate. 0 to 8 4
1ST DEFROST DELAY If DEFROST MODE = SCHEDULED: The amount of time from controller power up until the rst defrost is initiated. 0 to 240 minutes 120 minutes
DEFROST FAN STATE Whether or not to run the evaporator fans during defrost ON/OFF OFF if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF
ON if DEFROST TYPE = AIR
DEFROST TERM TEMP The temperature the coil sensor(s) must exceed in order to terminate defrost. The defrost relay is de-energized at this point. 35°F to 90°F 50°F if DEFROST TYPE = ELEC, HOT GAS COMP ON, HOT GAS COMP OFF
40°F if DEFROST TYPE = AIR
DEFROST PARAMETER The maximum amount of time the defrost relay will be energized for schedule defrosts. 0 to 90 minutes 25 minutes if DEFROST TYPE = ELEC
10 minutes if DEFROST TYPE = HOT GAS COMP ON, HOT GAS COMP OFF
40 minutes if DEFROST TYPE = AIR
DRAIN TIME Time to be in drain mode (drip time) 0 to 15 minutes 2 minutes
COMP RUN TIME If DEFROST MODE = RUN TIME: The amount of time liquid line solenoid/compressor relay is energized before the next defrost is initiated. 0 to 24 hours 6 hours
ELEC DEFROST MODE If DEFROST TYPE = ELEC: Whether to leave the defrost relay energized during the defrost cycle or to utilize advanced defrost algorithm. PULSE, PERMANENT PERMANENT
FAN DELAY TEMP After defrost, the coil sensor reading must fall below this temperature set point in order for the controller to resume normal fan operation. -40°F to 35°F 20°F
MAX FAN DELAY TIME Maximum amount of time after defrost to resume normal fan operation. 0 to 20 minutes 2 minutes; 0 if Room Temp Setpoint is > 35°F
PUMP DOWN TIME Minimum amount of time between de-energizing the liquid line solenoid/compressor relay and energizing the defrost relay. 0 to 10 minutes 0 minutes
MULTI AIR TEMP CTRL Set to use average or warmest air temp when multiple air temps are available WARMEST, AVERAGE WARMEST
BONDED
CNTRLRS
ONLY
MULTI EVAP COOL Select whether to sync bonded contollers or let run independently in COOL or OFF modes SYNC, INDEPENDENT SYNC
MULTI EVAP DEFROST Select whether to sync bonded controllers or let run independently in DEFROST or DRAIN modes SYNC, INDEPENDENT SYNC
MULTI EVAP SENSOR Select whether to SHARE or NOT SHARE sensor readings for bonded controllers SHARED, NOT SHARED SHARED
HIGH TEMP ALARM OFFSET The number of degrees above ROOM TEMP for a HIGH TEMP ALARM condition. 0°F to 99.9°F 10°F
HIGH TEMP ALARM DELAY Minutes the room temperature must remain above ROOM TEMP + HIGH TEMP ALARM OFFSET before issuing a HIGH TEMP ALARM 0 to 120 minutes 60 minutes
LOW TEMP ALARM OFFSET The number of degrees below ROOM TEMP for a LOW TEMP ALARM condition. 0°F to 20°F 4°F
LOW TEMP ALARM DELAY Minutes the room temperature must remain below ROOM TEMP - LOW TEMP ALARM OFFSET before issuing a LOW TEMP ALARM 0 to 30 minutes 10 minutes
HUMIDITY ALARM OFFSET
The %RH above or below ROOM HUMIDITY for HIGH HUMIDITY ALARM condition or LOW HUMIDITY ALARM condition
0% to 25% 5%
HUMIDITY ALARM DELAY
Time the %RH must remain above or below ROOM HUMIDITY, HUMIDITY DIFF, HUMIDITY ALARM OFFSET before issuing a HIGH HUMIDITY ALARM OR LOW HUMIDITY ALARM
0 TO 360 minutes 120 minutes
DOOR ALARM DELAY If DIG IN (1, 2 and/or 3) MODE = DOOR SWITCH: The amount of time, in minutes, before an alarm condition is initiated if door is open and room
temperature is 5 degrees above ROOM TEMP + AIR TEMP DIFF 0 to 180 minutes 30 minutes
DIG IN 1 MODE Sets the function of the digital input DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF DISABLED
DIG IN 1 STATE Sets whether the switch activates when opened or closed OPEN, CLOSED OPEN
DIG IN 2 MODE Sets the function of the digital input DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF, DFR INTERLOCK,
DFR LOCKOUT DISABLED
DIG IN 2 STATE Sets whether the switch activates when opened or closed OPEN, CLOSED OPEN
DIG IN 3 MODE Sets the function of the digital input DISABLED, 2ND ROOM TEMP, DOOR SWITCH, EXT ALARM, SYSTEM OFF, LIGHTS SWITCH, DISABLED
DIG IN 3 STATE Sets whether the switch activates when opened or closed OPEN, CLOSED OPEN
2ND ROOM TEMP If DIG IN (1, 2 and/or 3)MODE = 2ND ROOM TEMP: This value becomes the ROOM TEMP setpoint when the digital input is active -50°F to 90°F -50°F
SUCT PRES OFFSET An oset added or subtracted from the suction line pressure transducer reading -5.0 to 5.0 psig 0.0 psig
SUCT TEMP OFFSET An oset added or subtracted from the suction temperature sensor reading -5.0°F to 5.0°F 0.0°F
AIR TEMP OFFSET An oset added or subtracted from the room temperature sensor reading -5.0°F to 5.0°F 0.0°F
COIL TEMP OFFSET An oset added or subtracted from the coil temperature sensor reading -5.0°F to 5.0°F 0.0°F
HUMIDITY OFFSET An oset added or subtracted from the humidity sensor reading -5% to 5% RH 0%
TEMP UNITS Units for temperature’s display in °F or °C FAHRENHEIT/CELSIUS FAHRENHEIT
AIR TEMP DIFF The number of degrees above ROOM TEMP before the controller will go into REFRIGERATION mode 0.1°F to 5°F 1°F
HUMIDITY DIFF The number of %RH above or below before the controller will go into DEHUMIDIFICATON or HUMIDIFICATION mode 0% to 25% 5%
DEHUMIDIFY OFFSET An oset from ROOM TEMP to keep cooling if humidity is above setpoint -20°F to 0°F 0°F
EXT DIGITAL SWITCH Provides external output to control: HEATER, HUMIDIFIER, or DEHUMIDIFIER RELAY HEATER SWITCH, DEHUMIDIFY RELAY, HUMIDIFIER RELAY HEATER
HEATER OFF DIFF ROOM TEMP minus HEATER OFF DIFF setpoint turns heaters o -99.9°F to 0°F -99.9°F
HEATER ON DIFF ROOM TEMP minus HEATER ON DIFF setpoint turns heaters on -100°F to -0.1°F -100°F
EXTREME TEMP DIFF ADVANCED TOPIC: Call KE2 Therm for assistance
PROPORTIONAL A coecient to the valve control algorithm that increases valve responsiveness 3 0 to 255
INTEGRAL A coecient to the valve control algorithm that increases valve responsiveness 5 0 to 255
DERIVATIVE Should not be adjusted unless instructed by KE2 Therm technical support 3 0 to 255
Q.1.23 November 2014
Page 18
© Copyright 2014 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Setpoints Menu
Table 3 - Controller Menus and Menu Parameters