Benchy Sparkling - Instruction Manual
Page 10 of 12 www.KegLand.com.au Last Updated 20/07/2021 10:11 AM
Mains Water Installation
Before connecting your mains water up to the Benchy Sparkling ensure that the sparkling water and
cold-water outlets are connected to a tap or plugged and all push in fittings are connected and all
hosing is secure.
IMPORTANT: For first time setup, keep the mains water supplying the Benchy Sparkling off until
the unit has been connected to all dispensing taps and CO2.
An easy way to redirect your mains water is to install a diverter valve with ¼ inch push in fitting
(KL17756) onto your mains water supply valve which has a ½ inch thread. 4mm x 6.35mm (1/4 inch)
PE water line (KL11143) is suggested to be used between the diverter and the Benchy sparkling.
It is suggested that the pressure of your mains water supply is reduced to 15psi higher than the
pressure set on the CO2 regulator. To reduce the mains water pressure, we would recommend using
an inline regulator with a 0-150 psi mini gauge (KL15035 and KL15011). It is also suggested that a
check valve is placed between the mains outlet and the soda carbonator. We recommend using a
duotight check valve that is easy to install in line with your hosing (KL07047).
Push your water line securely into the water inlet push in fitting on the Benchy Sparking (Inlet 4 in
Figure 1).
CO2Gas Cylinder and Regulator Installation
Tightly connect a type 30 regulator (KL07429) to your CO2 cylinder (KL01489 or KL01496) and ensure
the regulator pressure adjustment knob is turned completely counter clockwise to set the pressure
at 0psi. Push 8mm OD EVA Barrier tubing into the duotight fitting on the regulator and then push
this tubing into the gas inlet push in fitting on the Benchy Sparkling (Inlet 1 in Figure 1).
IMPORTANT: After you have attached your Benchy Sparkling to your dispensing taps and
connected your Gas supply and mains water supply EVA Barrier hosing to the push in fittings on
the unit it is important to perform a leak test on the system. Failure to do so could result in your
CO2 cylinder emptying faster than expected or water leaks occurring.
Leak Testing
It is essential to perform a pressure (leak) test prior to dispensing any sparkling or cold still water
from the Benchy Sparkling and every time your CO2 cylinder is swapped.
The Benchy Sparkling needs to be pressure tested to a pressure that is at least 1.5 times the pressure
that will be used for dispensing. For example, if your dispensing pressure is 50 psi then the pressure
test should be conducted at around 75psi.
A pressure test can be conducted via multiple methods which are outlined below. It is a good idea to
perform both of the pressure test methods to be certain the system is holding pressure:
1. Pressure decay test
Step 1. Ensure mains water into the Benchy Sparkling is turned off, the regulator adjustment knob is
turned fully counter clockwise and the unit is connected too all dispensing taps.