List of p
Degrees 1 to 99
r1 Degrees 0 to r2
r2 Higher value for SP Degrees r1 to 999
d0 Cooling or heating control Option Co/Ht
c0 Minimum stopping time Seconds 0 to 999
c2 Óutput status with probe error Range On/Of
P1 Ambient probe adjustment Degrees -30 to 30
P5 Ambient probe type Range tcJ,tch,tcS
H5 Access code to parameters Numeric 0 to 255
A0 Alarm 1 hysteresis Degrees 1 to 999
A1 Alarm 1 threshold Degrees 0 to 999
A2 Alarm 1 exclusion time Seconds 0 to 999
A3 Alarm 1 type Range OFF,HI,LO
A4 Alarm 2 hysteresis Degrees 1 to 999
A5 Alarm 2 threshold Degrees 0 to 999
A6 Alarm 2 exclusion time Seconds 0 to 999
A7 Alarm 2 type Range OFF,HI,LO
r1 =
r2 = Higher value for SP
Cooling or heating control
c0 =Minimum stopping time of the load
c2 = Output status with probe error
P1= Ambient probe adjustment
P5= Ambient probe type
H5 =Access code to parameters (it is set to 00 from factory)
A0, A1, A2, A3 = Alarm 1 parameters
A4, A5, A6, A7 = Alarm 2 parameters (similar to alarm 1)
arameters
Description Units Range
SP Set Point Degrees r1 to r2
r0
Parameter descriptions
Differential or hysteresis
Lower value for SP
SP =Set point. Temperature we wish to regulate the
machine (variable from r1 to r2)
r0 =Differential or hysteresis
Lower value for SP
d0 =
If d0 = Ht and TS is the temperature of ambient probe:
If TS >= SP the load is disconnected
If TS <= SP-r0 the load is connected
if d0=Co then:
If TS <= SPthe load is disconnected
If TS >= SP+r0 the load is connected
P2=tcJ (J type), P2=tch (K type), P2=tcS (S type)
If A3=OFF alarm 1 disabled
IfA3=HI then a high-temperature alarm is set:
if TS >= SP+A1 the alarm 1 is activated
if TS <= SP+A1-A0 the alarm 1 is de-activated
IfA3=LO then a low-temperature alarm is set:
if TS <= SP-A1 the alarm 1 is activated
if TS >= SP-A1+A0 the alarm 1 is de-activated
The alarm 1 is not activated until the time since instrument
is turn on is higher than A2
Parameter programming
Led indication, buzzer and display messages
Maintenance, cleaning and repair
After final installation of the unit, no routine maintenance is
required.
Set Point (SP) is the only parameter the user can
access without code protection.
•Press SET. SP text will appear on the display.
•Press SET again.The real value is shown on the display.
•The value can be modified with the UP and DOWN arrows.
•Press SET to enter any new values.
•Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.
Access to all code protected parameters.
•Press SET for 8 seconds. The access code value 00 is
shown on the display (unit comes with code set at 00 from
factory).
• With the UP and DOWN arrows, code can be set to user
needs.
•Press SET to enter the code. If the code is correct, the first
parameter label is shown on the display (SP).
• Move to the desired parameter with the UPand DOWN
Keys.
•Press SET to view the value on the display.
• The value can be modified with the UPand DOWN arrows.
•Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
•Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.
*The keyboard code can be reset to ZERO by turning
off the controller and turning it on again while
keeping the SET key depressed.
The led OUT indicates if the load is connected or not.
In normal operation, the probe temperature will be shown on
the display. In case of alarm or error, the following messages
can be shown:
• Er = Memory Error
• oo = Open Probe Error
• -- =Ambient temperature out of range
In case of alarm or error the internal buzzer is activated. The
buzzer can be silenced pressing the SET and DOWN arrows
at the same time (when a new alarm or error occurs the
buzzer sounds again).
Clean the surface of the display controller with a soft and
damp cloth. Never use abrasive detergents, petrol, alcohol
or solvents.
All repairs must be made by authorised personnel.