FUNC DP Value
off off Real-time leakage current.
1 blink Sensitivity setting.
2 blink Delay time setting.
3 off Previous tripped leakage current.
Message Description
'E Ct' Error in ZCT connection
'tESt' Replay tripped under test mode
'OFL' 'Overflow'. The measurement exceeded
the display range for the respective
sensitivity setting range.
Display range for sensitivity setting range
1: From 0.00A to 0.22A
Display range for sensitivity setting range
2: From 0.00A to 0.10A
Display range for sensitivity setting range
3: From 0.00A to 3.10A
Table 2: Function codes
Table 3: Display messages
3. PUSH-BUTTONS OPERATION
a) Trip test
Press the 'TEST' button to simulate a trip
condition
b) Trip reset
Press the 'RESET' button to reset the
relay when tripped
c) View setting
When the relay is not under tripped
condition, pressing the 'RESET' button
will scroll through the various functions of
the relay
Figure 1: Scroll sequence
d) Program setting
Only function codes 1 and 2 can be
programmed.
Step 1: Press RESET key until the
function digit shows required
function.
Step 2: Press the UP and DOWN key
simultaneously to enter
programming mode. The function
digit blinks to indicates the relay
is in programming mode
Step 3: Use the UP or DOWN key to
select the desired value.
Step 4: To save the selected value, press
the UP and DOWN key
simultaneously. This will exit the
programming mode with the
selected setting being saved.
To exit programming mode without saving the
selected setting, press the 'RESET' key once.
4. REMOTE CONTROL INPUTS *
a) Remote test input
This digital input is similar to the TEST
push-button. To remotely test the relay,
make a connection between terminals 4
and 6 of the relay.
b) Remote reset input
This digital input is to remotely reset the
relay when tripped. To reset the relay, make
a connection between terminals 4 and 5 of
the relay.
5. OUTPUT CONTACTS
a) Trip contact:
This is a latching type contact. It is
activated under following conditions :
- broken connection between the relay and
the ZCT
- leakage current exceeded the sensitivity
setting
b) 50% pre-fault contact *
- Activated when leakage current reaches
50% of the sensitivity setting
c) Safety contact *
- Activated when the auxiliary supply is
connected and the relay is functioning
normally
- De-activated when connection to the ZCT
from relay is interrupted or auxiliary supply
failure
FUNCTION 1 FUNCTION 2 FUNCTION 3off